PSR-SCP- 24DC/MXF1/4X1/2X2/B - Safety relays

Multifunctional safety relay for emergency stop and safety doors up to SIL 3, Cat. 4, PL e, automatically or manually monitored activation, 4 N/O contacts, 3 safety functions, 2 shutdown levels, plug-in screw terminal block

  • Up to Cat. 4/PL e in accordance with EN ISO 13849-1, SIL 3 in accordance with EN IEC 62061, SIL 3 in accordance with IEC 61508
  • 3 safety functions in one device
  • Low housing width of only 22.5mm
  • No software configuration required
  • Also available with push-in connection
Technical Specifications

Product properties

ApplicationEmergency stop
ApplicationSafety door
Mechanical service life10x 106 cycles
Relay typeElectromechanical relay with force-guided contacts in accordance with IEC/EN 61810-3

Electrical properties

Maximum power dissipation for nominal condition3 W
Nominal operating mode100% operating factor

Air clearances and creepage distances between the power circuits

Rated Insulation Voltage250 V AC
Rated surge voltage/insulation4 kV/basic isolation (safe isolation, reinforced insulation and 6 kV between input circuit, enabling current paths and safety circuit 1 (13/14, 23/24) and safety circuit 2 (43/44, 53/54).)

General

Nominal input voltage UN24 V DC
Input voltage range in reference to UN0.85 ... 1.1
Typical input current at UN125 mA (with actuated relays)
Typical input current at UN55 mA (Two-channel 24 V/0 V + max. 200 mA control (message outputs 32/62) with non-actuated relays)
Current consumptiontyp. 5 mA (Imax/Ix inputs)
Current consumption20 mA (in electric torque)
Voltage at input/start and feedback circuit24 V -15 % / +10 % (first channel: 24 V; second channel: 0 V)
Filter timemax. 1.5 ms (Test pulse duration; for all equivalent inputs)
Filter timemin. 7.5 ms (Test pulse rate; for all equivalent inputs)
Typical response time175 ms (monitored/manual start)
Typical response time250 ms (automatic start)
Typ. starting time with Us250 ms (when controlled via A1)
Typical release time25 ms (when controlled via S11/I1,I3,I5 and S21/I2,I4,I6)
Typical release time20 ms (when controlled via A1)
Concurrence
Recovery time1 s (Availability time after activation of sensor circuit: 100ms)
Maximum switching frequency0.5 Hz
Protective circuitSurge protection; Suppressor diode
Max. permissible overall conductor resistance100 Ω
Operating voltage display1 x green LED
Status display5x LED green

Output data

Contact switching type4 enabling current paths
Contact switching type2 semiconductor alarm outputs
Contact MaterialAgCuNi, +0.2 ... 0.4 µm Au
Maximum Switching Voltage250 V AC/DC
Minimum Switching Voltage10 V AC/DC
Limiting Continuous Current6 A (N/O contact)
Limiting Continuous Currentmax. 100 mA (Alarm output (24 V DC))
Maximum Inrush Current6 A
Inrush current, minimum10 mA
Sq. Total current72 A2 (ITH2 = I12 + I22+ I32+ I42)
Interrupting rating (ohmic load) max.1500 VA (250 V AC, τ = 0 ms)
Interrupting rating (ohmic load) max.66 W (220 V DC, τ = 0 ms)
Interrupting rating (ohmic load) max.66 W (110 V DC, τ = 0 ms)
Interrupting rating (ohmic load) max.100 W (48 V DC, τ = 0 ms)
Interrupting rating (ohmic load) max.144 W (24 V DC, τ = 0 ms)
Maximum interrupting rating (inductive load)48 W (24 V DC, τ = 40 ms)
Maximum interrupting rating (inductive load)43 W (48 V DC, τ = 40 ms)
Switching capacity min.0.1 W
Switching capacity (360/h cycles)5 A (0,1 Hz; DC13; 24 V)
Switching capacity (3600/h cycles)3 A (AC15; 230 V)
Output fuse6 A gL/gG NEOZED (N/O contact)
Output fuse4 A gL/gG NEOZED (for low-demand applications)

Connection technology

pluggableyes

Conductor connection

Connection MethodScrew connection
Conductor cross section rigid0.2 mm² ... 2.5 mm²
Conductor cross section flexible0.2 mm² ... 2.5 mm²
Conductor cross-section AWG24 ... 12
Stripping length7 mm
Screw threadM3

Dimensions

Width22.5 mm
Height112.2 mm
Depth114.5 mm

Material specifications

Coloryellow

Safety data

Stop category0

Safety data: EN ISO 13849

Category4
Performance level (PL)e (5 A DC13; 3 A AC15; 8760 cycles/year)

Safety data: EN 50156

Safety Integrity Level (SIL)3

Safety data

Safety Integrity Level (SIL)3
Safety Integrity Level (SIL)3
Safety Integrity Level (SIL)3

Ambient conditions

Degree of ProtectionIP20
Min. degree of protection of inst. locationIP54
Ambient Temperature (Operation)-20 °C ... 45 °C (see derating curve)
Ambient temperature (storage/transport)-25 °C ... 85 °C
Maximum altitude≤ 2000 m (Above sea level)
Max. permissible humidity (storage/transport)75 % (on average, 85% infrequently, non-condensing)
Max. permissible relative humidity (operation)75 % (on average, 85% infrequently, non-condensing)

Air clearances and creepage distances between the power circuits

Standards/regulationsIEC 60664-1

Mounting

Mounting TypeDIN rail mounting
Assembly instructionsSee derating curve
Mounting Positionvertical or horizontal

Why Proax for Phoenix Contact 2902725?

Proax is an authorized distributor of Phoenix Contact 2902725 and one of Phoenix Contact's largest distributors in North America. Our highly skilled in-house technical team is ready to assist with any technical needs.

Have a question in mind? to help you get the right product as quickly as possible for your project. We're always here to help!

Short Lead Time
Highly Trained Staff
Live Chat
Technical Support
Local Inventory
60+ Years Experience
Additional Information

Pack Size1
Recommended

Not in stock

Request lead time or order—we'll ensure quick delivery

Phoenix Contact Availability