SKU
MPN
PLC-RSC-230UC/21HC/EX
Weight
0.079 kg
This product is Not Cancellable/Not Returnable
Series PLC-RSC
PLC-RSC-230UC/21HC/EX - Relay Module
PLC-INTERFACE, consisting of DIN-rail-mountable basic terminal block in 14 mm with screw connection and plug-in relay with 10 A power contact, 1 changeover contact, 230 V AC/220 V DC input voltage. Approved according to ATEX/IECEx (Zone 2) and Ex Zone Class I, Div. 2.
PLC-RSC
The Phoenix Contact PLC-RSC Series is part of the PLC-INTERFACE family, offering compact relay modules designed for efficient signal isolation and amplification in industrial automation systems. These modules are engineered for DIN rail mounting and feature plug-in miniature relays with power contacts, ensuring reliable performance in various control applications.
Key Features:
Compact Design: With a slim 6.2 mm width, the PLC-RSC modules save space in control cabinets, allowing for high-density installations.
Versatile Contact Configurations: Available with different contact types, including single changeover (SPDT) and double changeover (DPDT) contacts, to suit diverse application needs.
Wide Input Voltage Range: Models support various input voltages, such as 24 V DC, 230 V AC, and 220 V DC, providing flexibility for integration into different control systems.
High Switching Capacity: Designed to handle currents up to 6 A, these modules are suitable for switching both resistive and inductive loads.
Integrated Protective Features: Equipped with reverse polarity protection and freewheeling diodes, the PLC-RSC modules ensure safe and reliable operation.
Manual Operation Option: Certain models include a manual operation lever, facilitating easy testing and maintenance without the need for external actuation.
Technical Specifications
Utilization restriction
EMC note | EMC: class A product, see manufacturer's declaration in the download area |
Product properties
Product family | PLC-INTERFACE |
Application | High continuous currents |
Application | potentially explosive areas |
Operating mode | 100% operating factor |
Mechanical service life | 3x 107 cycles |
Insulation characteristics
Insulation | Safe isolation, reinforced insulation |
Insulation characteristics: Standards/regulations
Insulation | Safe isolation, reinforced insulation |
Overvoltage category | III |
Pollution degree | 3 |
Electrical properties
Maximum power dissipation for nominal condition | 1.04 W |
Test voltage (Winding/contact) | 4 kV AC (50 Hz, 1 min., winding/contact) |
Standards/regulations
Rated Insulation Voltage | 250 V AC |
Rated surge voltage | 6 kV |
Coil side
Nominal input voltage UN | 230 V AC |
Nominal input voltage UN | 220 V DC |
Input voltage range | 179.4 V AC ... 264.5 V AC (20 °C) |
Input voltage range | 171.6 V DC ... 264 V DC (20 °C) |
Drive and function | monostable |
Drive (polarity) | polarized |
Typical input current at UN | 4.5 mA |
Typical response time | 7 ms |
Typical release time | 10 ms |
Protective circuit | Bridge rectifier; Bridge rectifier |
Operating voltage display | Yellow LED |
Switching
Contact switching type | 1 changeover contact |
Type of switch contact | Single contact |
Contact Material | AgNi |
Maximum Switching Voltage | 250 V AC/DC (The separating plate PLC-ATP should be installed for voltages larger than 250 V (L1, L2, L3) between identical terminal blocks in adjacent modules. Potential bridging is then carried out with FBST 8-PLC... or ...FBST 500...) |
Minimum Switching Voltage | 12 V (10 mA) |
Limiting Continuous Current | 10 A |
Limiting Continuous Current | 6 A (value applies to connections 12. If connections 12 are bridged, the normal value applies.) |
Maximum Inrush Current | 30 A (300 ms) |
Min. switching current | 10 mA (12 V) |
Interrupting rating (ohmic load) max. | 240 W (at 24 V DC) |
Interrupting rating (ohmic load) max. | 58 W (at 48 V DC) |
Interrupting rating (ohmic load) max. | 48 W (at 60 V DC) |
Interrupting rating (ohmic load) max. | 50 W (at 110 V DC) |
Interrupting rating (ohmic load) max. | 80 W (at 220 V DC) |
Interrupting rating (ohmic load) max. | 2500 VA (for 250 V AC) |
Interrupting rating (ohmic load) max. bridged | 144 W (for 24 V DC. Value applies to connections 12. If connections 12 are bridged, the normal value applies.) |
Interrupting rating (ohmic load) max. bridged | 1500 VA (for 250 V AC. Value applies to connections 12. If connections 12 are bridged, the normal value applies.) |
Switching capacity | 2 A (at 24 V, DC13) |
Switching capacity | 0.2 A (at 110 V, DC13) |
Switching capacity | 0.2 A (at 250 V, DC13) |
Switching capacity | 6 A (at 24 V, AC15) |
Switching capacity | 6 A (at 120 V, AC15) |
Switching capacity | 6 A (at 250 V, AC15) |
Connection data
Connection Method | Screw connection |
Stripping length | 8 mm |
Screw thread | M3 |
Conductor cross section rigid | 0.14 mm² ... 2.5 mm² |
Conductor cross section flexible | 0.14 mm² ... 2.5 mm² |
Conductor cross section flexible | 0.2 mm² ... 2.5 mm² (Single ferrule) |
Conductor cross section flexible | 2x 0.5 mm² ... 1.5 mm² (TWIN ferrule) |
Conductor cross section AWG | 26 ... 14 |
Tightening torque | 0.6 Nm ... 0.8 Nm |
Dimensions
Width | 14 mm |
Height | 80 mm |
Depth | 94 mm |
Material specifications
Color | gray (RAL 7042) |
Flammability rating according to UL 94 | V0 (Housing) |
Ambient conditions
Degree of protection (Relay) | RT III (Relay) |
Degree of protection (Relay base) | IP20 (Relay base) |
Ambient Temperature (Operation) | -20 °C ... 60 °C (UL) |
Ambient Temperature (Operation) | -40 °C ... 55 °C (ATEX / IECEx) |
Ambient temperature (storage/transport) | -40 °C ... 85 °C |
CE
Certificate | CE-compliant |
ATEX
Identification | II 3G Ex ec nC IIC T4 Gc |
Certificate | IBExU16ATEXB015 X |
IECEx
Identification | Ex ec nC IIC T4 Gc |
Certificate | IECEx IBE 16.0029X |
UKCA Ex (UKEX)
Identification | II 3 G Ex ec nC IIC T4 Gc |
Certificate | PxCIF21UKEX2909514X |
UL, USA
Identification | Class I, Zone 2, AEx nA nC IIC T6 |
UL, USA/Canada
Identification | Class I, Div. 2, Groups A, B, C, D |
UL, Canada
Identification | Class I, Zone 2, Ex nA nC IIC Gc T6 X |
Shipbuilding approval
Certificate | TAE0000196 |
Corrosive gas test
Identification | ISA-S71.04. G3 Harsh Group |
Identification | EN 60068-2-60 |
DNV GL data
Temperature | D |
Humidity | A |
Vibration | B/C |
EMC | B |
Enclosure | Required protection according to the Rules shall be provided upon installation on board |
EMC data
Low Voltage Directive | Conformance with Low Voltage Directive |
Electromagnetic compatibility | Conformance with EMC directive |
Standards/regulations
Standards/regulations | IEC 60947-5-1 |
Standards/regulations | EN 60079-0 |
Standards/regulations | EN 60079-7 |
Standards/regulations | EN 60079-15 |
Mounting
Mounting Type | DIN rail mounting |
Assembly instructions | in rows with zero spacing |
Mounting Position | any |
Accessories
Why Proax for Phoenix Contact 2909521?
Proax is an authorized distributor of Phoenix Contact 2909521 and one of Phoenix Contact's largest distributors in North America. Our highly skilled in-house technical team is ready to assist with any technical needs.