2905628
SKU
PHX2905628
MPN
MINI MCR-2-RPSS-I-2I
Weight
0.127 kg
Series MINI-MCR
MINI MCR-2-RPSS-I-2I - Repeater power supply
4-way power supply doubler with plug-in connection technology. HART-transparent, 0(4) mA ... 20 mA input signal, 0(4) mA ... 20 mA output signals. The device can be used in both signal and power supply doubler modes. Screw connection technology.
Technical Specifications
Utilization restriction
| EMC note | EMC: class A product, see manufacturer's declaration in the download area |
Product properties
| Product family | MINI Analog Pro |
| No. of channels | 2 |
| Type | Signal conditioner |
| Configuration | DIP switches |
Insulation characteristics: GB Standard
| Overvoltage category | II |
| Pollution degree | 2 |
Electrical properties
| Electrical isolation | 4-way isolation |
| Limit frequency (3 dB) | > 1 kHz |
| Signal transmission behavior | In = Out |
| Step response (10-90%) | < 400 µs |
| Maximum temperature coefficient | 0.0075 %/K |
| Maximum transmission error | 0.05 % (of final value) |
Electrical isolation Input/output/power supply
| Rated Insulation Voltage | 300 Vrms |
| Test voltage | 3 kV AC (50 Hz, 60 s) |
| Insulation | Reinforced insulation according to IEC/EN 61010-1 |
Supply
| Nominal Supply Voltage | 24 V DC |
| Supply Voltage Range | 9.6 V DC ... 30 V DC (The DIN rail connector (ME 6,2 TBUS-2 1,5/5-ST-3,81 GN, item no. 2869728) can be used to bridge the supply voltage. It can be snapped onto a 35 mm DIN rail in accordance with EN 60715) |
| Typical current consumption | 40 mA (For 24 V DC and in signal duplicator mode) |
| Typical current consumption | 65 mA (For 24 V DC and in power supply duplicator mode) |
| Typical current consumption | 75 mA (For 12 V DC and in signal duplicator mode) |
| Typical current consumption | 130 mA (For 12 V DC and in power supply duplicator mode) |
| Power consumption | 1.6 W (at IOUT = 20 mA, 500 Ω load) |
Signal: Current
| Description of the input | Sensor circuit |
| Number of Inputs | 1 |
| Current Input Signal | 0 mA ... 20 mA (Signal duplicator mode) |
| Current Input Signal | 4 mA ... 20 mA (Power supply and signal duplicator mode) |
| Input resistance current input | 90 Ω (+1.6 V) |
| Transmitter supply voltage | > 19.5 V |
| Number of Outputs | 2 |
| Non-load voltage | < 20 V |
| Current Output Signal | 0 mA ... 20 mA (Signal duplicator mode) |
| Current Output Signal | 4 mA ... 20 mA (Power supply and signal duplicator mode) |
| Max. current output signal | 25 mA |
| Load/Output Load Current Output | ≤ 500 Ω (per channel) |
| Ripple | < 20 mVPP (500 Ω) |
Connection data
| Connection Method | Screw connection |
| Stripping length | 10 mm |
| Screw thread | M3 |
| Conductor cross section rigid | 0.2 mm² ... 1.5 mm² (with ferrule) |
| Conductor cross section rigid | 0.14 mm² ... 2.5 mm² (without ferrule) |
| Conductor cross section flexible | 0.14 mm² ... 2.5 mm² |
| Conductor cross section AWG | 24 ... 12 (flexible) |
| Tightening torque | 0.5 Nm ... 0.6 Nm |
Ex data
| Ex installation (EPL) | Gc |
| Ex installation (EPL) | Div. 2 |
Data communication (bypass)
| HART Function | Yes |
| Limit frequency (3 dB) | 1 kHz |
Signaling
| Status display | Green LED (supply voltage) |
Dimensions
| Width | 6.2 mm |
| Height | 109.81 mm |
| Depth | 119.2 mm |
Material specifications
| Color | gray (RAL 7042) |
| Housing Material | PBT |
| Fire protection for rail vehicles (DIN EN 45545-2) R22 | HL 1 - HL 2 |
| Fire protection for rail vehicles (DIN EN 45545-2) R23 | HL 1 - HL 2 |
| Fire protection for rail vehicles (DIN EN 45545-2) R24 | HL 1 - HL 2 |
Ambient conditions
| Degree of Protection | IP20 (not assessed by UL) |
| Ambient Temperature (Operation) | -40 °C ... 70 °C |
| Ambient temperature (storage/transport) | -40 °C ... 85 °C |
| Altitude | ≤ 2000 m |
| Permissible humidity (operation) | 5 % ... 95 % (non-condensing) |
CE
| Certificate | CE-compliant |
ATEX
| Identification | II 3 G Ex ec ic IIC T4 Gc |
| Certificate | BVS 19 ATEX E 047 X |
UKCA Ex (UKEX)
| Identification | II 3 G Ex ec ic IIC T4 Gc |
| Certificate | PxCIF21UKEX2902000X |
IECEx
| Identification | Ex ec ic IIC T4 Gc |
| Certificate | IECEx BVS 19.0041X |
CCC / China-Ex
| Identification | Ex nA ic IIC T4 Gc |
UL, USA/Canada
| Identification | UL 508 Listed |
| Identification | Class I, Div. 2, Groups A, B, C, D T5 |
| Identification | Class I, Zone 2, Group IIC T5 |
Shipbuilding approval
| Certificate | DNV GL TAA000021E Rev. 1 |
EAC Ex
| Identification | 2Ex ec ic IIC T4 Gc |
| Certificate | BY/112 02.01 TP012 103.01 00081 |
DNV GL data
| Temperature | B |
| Humidity | B |
| Vibration | A |
| EMC | A |
| Enclosure | Required protection according to the Rules shall be provided upon installation on board |
EMC data
| Noise immunity | EN 61000-6-2 |
| Note | When being exposed to interference, there may be minimal deviations. |
| Electromagnetic compatibility | Conformance with EMC directive |
| Noise emission | EN 61000-6-4 |
Electrostatic discharge
| Standards/regulations | EN 61000-4-2 |
| Comments | Safety measures must be taken to prevent electrostatic discharge. |
Electromagnetic HF field
| Designation | Electromagnetic RF field |
| Standards/regulations | EN 61000-4-3 |
Fast transients (burst)
| Designation | Fast transients (burst) |
| Standards/regulations | EN 61000-4-4 |
Surge current load (surge)
| Standards/regulations | EN 61000-4-5 |
Conducted interference
| Designation | Conducted interferences |
| Standards/regulations | EN 61000-4-6 |
Standards and Regulations
| Electrical isolation | 4-way isolation |
GB Standard
| Standards/regulations | GB 3836.1 |
| Standards/regulations | GB 3836.4 |
| Standards/regulations | GB 3836.8 |
Mounting
| Mounting Type | DIN rail mounting |
| Assembly instructions | The DIN rail connector can be used for bridging the supply voltage. It can be snapped onto a 35 mm EN 60715 DIN rail. |
| Mounting Position | any |
Accessories
Why Proax for Phoenix Contact 2905628?
Proax is an authorized distributor of Phoenix Contact 2905628 and one of Phoenix Contact's largest distributors in North America. Our highly skilled in-house technical team is ready to assist with any technical needs.
Have a question in mind? to help you get the right product as quickly as possible for your project. We're always here to help!
Short Lead Time
Highly Trained Staff
Live Chat
Technical Support
Local Inventory
60+ Years Experience
Additional Information
| Pack Size | 1 |
Recommended