Series VAL-CP-N-PE
VAL-CP-N/PE-175-ST - Type 2 surge protection plug
Replacement plug for VAL-CP surge arrester with N-PE spark gap.
Technical Specifications
Product properties
| IEC test classification | II |
| IEC test classification | T2 |
| EN type | T2 |
| IEC power supply system | TN |
| IEC power supply system | TT |
| Type | DIN rail module, two-section, divisible |
| Number of Positions | 1 |
| Surge protection fault message | optical |
Insulation characteristics
| Overvoltage category | III |
| Pollution degree | 2 |
Electrical properties
| Nominal frequency fN | 50 Hz (60 Hz) |
Connection data
| Connection Method | pluggable |
Dimensions
| Width | 11.7 mm |
| Height | 46.4 mm |
| Depth | 56.4 mm |
Material specifications
| Color | blue grey (RAL 7031) |
| Flammability rating according to UL 94 | V-0 |
| CTI value of material | 600 |
| Insulating material | PBT-FR |
| Material group | I |
| Housing Material | PBT-FR |
Protective circuit
| Mode of protection | N-PE |
| Direction of action | N-PE |
| Nominal voltage UN | 120 V AC (TN - only N-PE) |
| Nominal voltage UN | 120 V AC (TT - only N-PE) |
| Nominal frequency fN | 50 Hz (60 Hz) |
| Maximum continuous operating voltage UC (N-PE) | 150 V AC |
| Residual current IPE | ≤ 1 µA |
| Nominal discharge current In (8/20) µs (N-PE) | 20 kA |
| Maximum discharge current Imax (8/20) µs (N-PE) | 40 kA |
| Follow current interrupt rating Ifi (N-PE) | 100 A (150 V AC) |
| Voltage protection level Up (N-PE) | ≤ 0.95 kV |
| Residual voltage Ures (N-PE) | ≤ 0.4 kV (at In) |
| Residual voltage Ures (N-PE) | ≤ 0.4 kV (at 10 kA) |
| Residual voltage Ures (N-PE) | ≤ 0.4 kV (at 5 kA) |
| Residual voltage Ures (N-PE) | ≤ 0.4 kV (at 4 kA) |
| Residual voltage Ures (N-PE) | ≤ 0.4 kV (at 2 kA) |
| TOV behavior at UT (N-PE) | 1200 V AC (200 ms / withstand mode) |
| Response time tA (N-PE) | ≤ 100 ns |
Ambient conditions
| Degree of Protection | IP20 |
| Ambient Temperature (Operation) | -40 °C ... 80 °C |
| Ambient temperature (storage/transport) | -40 °C ... 80 °C |
| Altitude | ≤ 2000 m (amsl) |
| Permissible humidity (operation) | 5 % ... 95 % |
| Shock (operation) | 30g (Half-sine / 11 ms / 3x ±X, ±Y, ±Z) |
| Vibration (Operation) | 5g (10 ... 500 Hz / 2.5 h / X, Y, Z) |
UL specifications
| Maximum continuous operating voltage MCOV (N-G) | 150 V AC |
| Nominal discharge current In (N-G) | 20 kA |
| Mode of protection | N-G |
| Power distribution system | Single phase |
| Nominal frequency | 50/60 Hz |
| Measured limiting voltage MLV (N-G) | 560 V |
| Follow current (L-G) | 200 A (150 V AC) |
| SPD Type | 4CA |
Air clearances and creepage distances
| Standards/regulations | DIN VDE 0110-1 / IEC 60664-1 / IEC 61643-1 |
| Standards/specifications | IEC 61643-11 |
| Note | 2011 |
| Standards/specifications | EN 61643-11 |
| Note | 2012 |
Mounting
| Mounting Type | on base element |
Why Proax for Phoenix Contact 2859709?
Proax is an authorized distributor of Phoenix Contact 2859709 and one of Phoenix Contact's largest distributors in North America. Our highly skilled in-house technical team is ready to assist with any technical needs.