Official Distributor
SKU
MPN
AXL E EIP IOL8 DI4 M12 6P
Weight
0.557 kg
This product is Not Cancellable/Not Returnable
Series AXL-E-EIP-IOL8
AXL E EIP IOL8 DI4 M12 6P - Communication module
Axioline E, EtherNet/IP™, M12 connector, IO-Link ports Class A: 4, connection method: M12 connector, connection technology: 3-conductor, IO-Link ports Class B: 4, connection method: M12 connector, connection technology: 3-conductor, Digital inputs at pin 2 for class A ports: 4, 24 V DC, connection technology: 3-conductor, Plastic housing, degree of protection: IP65/IP67
- Connection to EtherNet/IP™ network using M12 connectors (D-coded)
- Transmission speed of 10 Mbps and 100 Mbps
- Connection of four IO-Link devices with additional digital input
- Connection of four IO-Link actuators with additional power supply
- Connection of IO-Link ports using M12connectors (A-coded, 5-pos.)
- IO-Link specification V1.1.2
- Diagnostic and status indicators
- Short-circuit and overload protection of the sensor supply
- IP65/IP67 degree of protection
Technical Specifications
Dimensions
Width | 60 mm |
Height | 185 mm |
Depth | 30.5 mm |
Drill hole spacing | 198.5 mm |
Note on dimensions | The height is 212 mm including fixing clips. |
Utilization restriction
EMC note | EMC: class A product, see manufacturer's declaration in the download area |
Material specifications
Housing Material | Pocan® |
Color | anthracite |
Ethernet/IP™
Number of interfaces | 2 |
Connection Method | M12 connector |
Note on the connection method | D-coded |
Number of Positions | 4 |
Transmission Speed | 10/100 Mbps (with auto negotiation) |
Equipment type | EtherNet/IP™ device |
System-specific protocols | EtherNet/IP™ protocols ACD |
System-specific protocols | EtherNet/IP™ protocols DLR |
System-specific protocols | EtherNet/IP™ protocols IGMP v2 |
Protocols Supported | SNMP v1 |
Protocols Supported | HTTP |
Protocols Supported | TFTP |
Protocols Supported | FTP |
Protocols Supported | BootP |
Protocols Supported | DHCP |
Specification | CIP Edition 3.11EIP adaptation of CIP 1.12 |
Digital:
Input name | Digital inputs at pin 2 for class A ports |
Description of the input | IEC 61131-2 type 1 |
Number of Inputs | 4 |
Connection Method | M12 connector, X01 ... X04 have double occupancy |
Connection technology | 3-conductor |
Input voltage range "0" signal | -0.3 V DC ... 5 V DC |
Input voltage range "1" signal | 15 V DC ... 30 V DC |
Nominal input voltage UIN | 24 V DC |
Nominal input current at UIN | typ. 3 mA |
Sensor current per channel | max. 200 mA (from L+/L-) |
Total sensor current | max. 1.6 A (from L+/L-) |
Input Frequency | 0.5 kHz |
Input filter time | < 1000 µs |
Protective circuit | Overload protection, short-circuit protection of sensor supply |
Digital
Description of the input | IO-Link ports in digital input (DI) mode |
Number of Inputs | max. 8 (EN 61131-2 type 1) |
Connection Method | M12 connector, X01 ... X04 have double occupancy |
Connection technology | 3-conductor |
Nominal input voltage UIN | 24 V DC |
Input voltage range "0" signal | -0.3 V DC ... 5 V DC |
Input voltage range "1" signal | 15 V DC ... 30 V DC |
Nominal input current | typ. 3 mA |
Sensor current per channel | max. 200 mA (from L+/L-) |
Total sensor current | max. 1.6 A (from L+/L-) |
Input filter time | < 1000 µs |
Input Frequency | 0.5 kHz |
Protective circuit | Overload protection; yes |
Protective circuit | Short-circuit protection for the sensor supply; yes |
IO-Link
Number of Ports | 4 |
Connection Method | M12 connector |
Connection technology | 3-conductor |
Port Type | Class A |
Cycle Time | min. 2 ms (MasterCycleTime: PDInput* + PDOutput* + OnReqData* < = 17 Bytes, COM3; * see "IO-Link Interface and System Specification V1.1.2") |
Number of Ports | 4 |
Connection Method | M12 connector |
Connection technology | 3-conductor |
Port Type | Class B |
Cycle Time | min. 2 ms (MasterCycleTime: PDInput* + PDOutput* + OnReqData* < = 17 Bytes, COM3; * see "IO-Link Interface and System Specification V1.1.2") |
Digital
Output description | IO-Link ports in digital output (DO) mode |
Connection Method | M12 connector, X01 ... X04 have double occupancy |
Connection technology | 3-conductor |
Number of Outputs | max. 8 |
Nominal Output Voltage | 24 V DC |
Maximum Output Current per channel | 150 mA |
Maximum Output Current per module | 1.2 A |
Nominal load, ohmic | 3.6 W (160 Ω, at nominal load) |
Nominal load, inductive | 3.6 VA (0.8 H, 160 Ω, at nominal load) |
Signal delay | max. 150 µs (when switched on) |
Signal delay | max. 200 µs (when switched off) |
Switching rate | 1 per second, maximum (at nominal inductive load) |
Switching rate | 5500 per second, maximum (at nominal ohmic load) |
Limitation of the voltage induced on circuit interruption | -15 V DC |
Output voltage when switched off | max. 1 V |
Output current when switched off | max. 300 µA |
Protective circuit | Overload protection; yes |
Protective circuit | Short-circuit protection; yes |
Behavior with overload | Shutdown with automatic restart |
Product properties
Product family | Axioline E |
Type | Stand-Alone |
Special Properties | Plastic housing |
Potentials
Voltage supply US | 24 V DC |
Power supply at US | max. 4 A |
Current consumption from US | typ. 8 mA |
Current consumption from US | max. 1.2 A |
Supply: IO-Link
Nominal voltage for I/O supply | 24 V DC |
Nominal current for every IO-Link port | max. 150 mA (at C/Q (pin 4), maximum of 1.6 A over all 8 IO-Link C/Q and L+ cables) |
Nominal current for every IO-Link port | max. 200 mA (at L+/L- (pin 1 and pin 3), during startup, up to 1.6 A for short periods) |
Nominal current for every IO-Link port | max. 2 A (at UA (IO-Link B ports, pin 2 and pin 5)) |
Permissible cable length | < 20 m (to the sensor) |
Protective circuit | Overload protection; yes |
Supply: Module electronics and sensors
Designation | Supply of module electronics and sensors (US) |
Connection Method | M12 connector (T-coded) |
Number of Positions | 4 |
Supply Voltage | 24 V DC |
Supply Voltage Range | 19.5 V DC ... 31.2 V DC (including all tolerances, including ripple) |
Current consumption | typ. 180 mA ±15 % (at 24 V DC) |
Current consumption | max. 12 A |
Supply: Actuators
Designation | Supply of actuators (UA) |
Connection Method | M12 connector (T-coded) |
Number of Positions | 4 |
Supply Voltage | 24 V DC |
Supply Voltage Range | 18 V DC ... 31.2 V DC (including all tolerances, including ripple) |
Current consumption | typ. 28 mA ±15 % (at 24 V DC) |
Current consumption | max. 12 A |
Electrical isolation/isolation of the voltage ranges
Test voltage: 24 V supply (communications power and sensor supply, IO-Link ports)/bus connection (Ethernet 1) | 500 V AC, 50 Hz, 1 min. |
Test voltage: 24 V supply (communications power and sensor supply, IO-Link ports)/bus connection (Ethernet 2) | 500 V AC, 50 Hz, 1 min. |
Test voltage: 24 V supply (communications power and sensor supply, IO-Link ports)/FE | 500 V AC, 50 Hz, 1 min. |
Test voltage: Bus connection (Ethernet 1)/FE | 500 V AC, 50 Hz, 1 min. |
Test voltage: Bus connection (Ethernet 2)/FE | 500 V AC, 50 Hz, 1 min. |
Test voltage: Bus connection (Ethernet 1)/bus connection (Ethernet 2) | 500 V AC, 50 Hz, 1 min. |
Test voltage: 24 V supply (actuator supply)/24 V supply (communications power and sensor supply, IO-Link ports) | 500 V AC, 50 Hz, 1 min. |
Test voltage: 24 V supply (actuator supply)/bus connection (Ethernet 1) | 500 V AC, 50 Hz, 1 min. |
Test voltage: 24 V supply (actuator supply)/bus connection (Ethernet 2) | 500 V AC, 50 Hz, 1 min. |
Test voltage: 24 V supply (actuator supply)/FE | 500 V AC, 50 Hz, 1 min. |
Connection data
Connection Method | M12 connector |
Ambient conditions
Ambient Temperature (Operation) | -25 °C ... 60 °C |
Degree of Protection | IP65/IP67 |
Air pressure (operation) | 70 kPa ... 106 kPa (up to 3000 m above sea level) |
Air pressure (storage/transport) | 70 kPa ... 106 kPa (up to 3000 m above sea level) |
Ambient temperature (storage/transport) | -25 °C ... 85 °C |
Permissible humidity (operation) | 5 % ... 95 % |
Permissible humidity (storage/transport) | 5 % ... 95 % |
Standards and Regulations
Protection class | III (IEC 61140, EN 61140, VDE 0140-1) |
Accessories
Why Proax for Phoenix Contact 2701496?
Proax is an authorized distributor of Phoenix Contact 2701496 and one of Phoenix Contact's largest distributors in North America. Our highly skilled in-house technical team is ready to assist with any technical needs.
Have a question in mind? to help you get the right product as quickly as possible for your project. We're always here to help!
Short Lead Time
Highly Trained Staff
Live Chat
Technical Support
Local Inventory
60+ Years Experience
Additional Information
Pack Size | 1 |
Recommended
- 2701491 - Axioline E, EtherNet/IP™, M12 connector, IO-Link ports Class A: 4, connection method: M12 connector, connection technology: 3-conductor, IO-Link ports Class B: 4, connection method: M12 connector, connection technology: 3-conductor, Digital inputs at pin 2 for class A ports: 4, 24 V DC, connection technology: 3-conductor, Metal housing, degree of protection: IP65/IP67
- 2701541 - Axioline E, Ethernet, M12 connector, IO-Link ports Class A: 4, connection method: M12 connector, connection technology: 3-conductor, IO-Link ports Class B: 4, connection method: M12 connector, connection technology: 3-conductor, Digital inputs at pin 2 for class A ports: 4, 24 V DC, connection technology: 3-conductor, Metal housing, degree of protection: IP65/IP67
- 2701536 - Axioline E, Ethernet, M12 connector, IO-Link ports Class A: 4, connection method: M12 connector, connection technology: 3-conductor, IO-Link ports Class B: 4, connection method: M12 connector, connection technology: 3-conductor, Digital inputs at pin 2 for class A ports: 4, 24 V DC, connection technology: 3-conductor, Plastic housing, degree of protection: IP65/IP67