Distributed I/O device - AXL E IOL AI1 U M12 S

Axioline E-IO-Link/analog converter for connecting an analog sensor, 0 V ... 10 V, M12 fast connection technology, straight version

  • Straight version
  • 1 IO-Link interface
  • 1 analog input
  • Connection of sensor in 3-conductor technology
  • Voltage range: 0 V ... 10 V
  • IO-Link and sensor connections via M12 connectors
  • Functional ground connection for local connection to functional ground
  • Supply of the module electronics and the sensor via the IO-Link interface of the IO-Link master
  • Diagnostic indicator
  • IO-Link specification V1.1.1
Technical Specifications

Note

Utilization restrictionEMC: class A product, see manufacturer's declaration in the download area

Dimensions

Width16.6 mm
Height29 mm
Depth79.5 mm

Ambient conditions

Ambient Temperature (Operation)-25 °C ... 60 °C
Ambient temperature (storage/transport)-25 °C ... 85 °C
Permissible humidity (operation)5 % ... 95 %
Permissible humidity (storage/transport)5 % ... 95 %
Air pressure (operation)70 kPa ... 106 kPa (up to 3000 m above sea level)
Air pressure (storage/transport)70 kPa ... 106 kPa (up to 3000 m above sea level)
Degree of ProtectionIP65/IP67

General

Net weight34 g
Degree of pollution2
Diagnostics messagesOverrange or underrange Message in the diagnostic code (in the IB IL format)
Diagnostics messagesMeasured value invalid/no valid measured value present Message in the diagnostic code (in the IB IL format)
Diagnostics messagesModule faulty Message in the diagnostic code (in the IB IL format)

Standards and Regulations

Mechanical testsVibration resistance in acc. with EN 60068-2-6/IEC 60068-2-6 Operation: 2g
Mechanical testsVibration resistance in acc. with EN 60068-2-6/IEC 60068-2-6 Storage/transport: 5g
Mechanical testsShock in acc. with EN 60068-2-27/IEC 60068-2-27 Operation: 30g, 11 ms, three shocks in each space direction
Mechanical testsShock in acc. with EN 60068-2-27/IEC 60068-2-27 Storage/transport: 50g, 11 ms, three shocks in each space direction
Mechanical testsContinuous shock according to EN 60068-2-27/IEC 60068-2-27 10g, 16 ms, 1000 shocks, in all space directions
Protection classIII (IEC 61140, EN 61140, VDE 0140-1)

Environmental Product Compliance

REACh SVHCLead 7439-92-1

Why Proax for Phoenix Contact AXL E IOL AI1 U M12 S?

Proax is an authorized distributor of Phoenix Contact AXL E IOL AI1 U M12 S and one of Phoenix Contact's largest distributors in North America. Our highly skilled in-house technical team is ready to assist with any technical needs.

Have a question in mind? to help you get the right product as quickly as possible for your project. We're always here to help!

Short Lead Time
Highly Trained Staff
Live Chat
Technical Support
Local Inventory
60+ Years Experience
Recommended

Available for order