Official Distributor
SKU
MPN
AXL E IOL RTD1 M12 S
Weight
0.051 kg
This product is Not Cancellable/Not Returnable
Series AXL-E-IOL-RTD1
Distributed I/O device - AXL E IOL RTD1 M12 S
Axioline E-IO-Link/analog converter for connecting a temperature measurement resistor, M12 fast connection technology, straight version
- Straight version
- 1 IO-Link interface
- 1 analog input for connecting resistance temperature detectors (RTDs)
- Connection of the sensor in 3- or 4-conductor technology via an M12 connector (A-coded, 5-pos.)
- Functional ground connection for local connection to functional ground
- Supply of the module electronics and the sensor via the IO-Link interface of the IO-Link master
- Diagnostic indicator
- IO-Link specification V1.1.1
Technical Specifications
Note
Utilization restriction | EMC: class A product, see manufacturer's declaration in the download area |
Dimensions
Width | 16.6 mm |
Height | 29 mm |
Depth | 79.5 mm |
Ambient conditions
Ambient Temperature (Operation) | -25 °C ... 60 °C |
Ambient temperature (storage/transport) | -25 °C ... 85 °C |
Permissible humidity (operation) | 5 % ... 95 % |
Permissible humidity (storage/transport) | 5 % ... 95 % |
Air pressure (operation) | 70 kPa ... 106 kPa (up to 3000 m above sea level) |
Air pressure (storage/transport) | 70 kPa ... 106 kPa (up to 3000 m above sea level) |
Degree of Protection | IP65/IP67 |
General
Net weight | 34 g |
Degree of pollution | 2 |
Diagnostics messages | Overrange or underrange Message in the diagnostic code (in the IB IL format) |
Diagnostics messages | Measured value invalid/no valid measured value present Message in the diagnostic code (in the IB IL format) |
Diagnostics messages | Configuration invalid Message in the diagnostic code (in the IB IL format) |
Diagnostics messages | Module faulty Message in the diagnostic code (in the IB IL format) |
Standards and Regulations
Mechanical tests | Vibration resistance in acc. with EN 60068-2-6/IEC 60068-2-6 Operation: 2g |
Mechanical tests | Vibration resistance in acc. with EN 60068-2-6/IEC 60068-2-6 Storage/transport: 5g |
Mechanical tests | Shock in acc. with EN 60068-2-27/IEC 60068-2-27 Operation: 30g, 11 ms, three shocks in each space direction |
Mechanical tests | Shock in acc. with EN 60068-2-27/IEC 60068-2-27 Storage/transport: 50g, 11 ms, three shocks in each space direction |
Mechanical tests | Continuous shock according to EN 60068-2-27/IEC 60068-2-27 10g, 16 ms, 1000 shocks, in all space directions |
Protection class | III (IEC 61140, EN 61140, VDE 0140-1) |
Environmental Product Compliance
REACh SVHC | Lead 7439-92-1 |
Why Proax for Phoenix Contact 2700352?
Proax is an authorized distributor of Phoenix Contact 2700352 and one of Phoenix Contact's largest distributors in North America. Our highly skilled in-house technical team is ready to assist with any technical needs.
Have a question in mind? to help you get the right product as quickly as possible for your project. We're always here to help!
Short Lead Time
Highly Trained Staff
Live Chat
Technical Support
Local Inventory
60+ Years Experience
Additional Information
Pack Size | 1 |
Recommended
- 2701541 - Axioline E, Ethernet, M12 connector, IO-Link ports Class A: 4, connection method: M12 connector, connection technology: 3-conductor, IO-Link ports Class B: 4, connection method: M12 connector, connection technology: 3-conductor, Digital inputs at pin 2 for class A ports: 4, 24 V DC, connection technology: 3-conductor, Metal housing, degree of protection: IP65/IP67
- 2701536 - Axioline E, Ethernet, M12 connector, IO-Link ports Class A: 4, connection method: M12 connector, connection technology: 3-conductor, IO-Link ports Class B: 4, connection method: M12 connector, connection technology: 3-conductor, Digital inputs at pin 2 for class A ports: 4, 24 V DC, connection technology: 3-conductor, Plastic housing, degree of protection: IP65/IP67