Official Distributor
SKU
MPN
QUINT-UPS/ 24DC/12DC/5/24DC/10
Weight
0.735 kg
Series QUINT-UPS
QUINT-UPS/ 24DC/12DC/5/24DC/10 - Uninterruptible power supply
Uninterruptible power supply with IQ technology for DIN rail mounting, input: 24 V DC, output: 24 V DC/10 A and 12 V DC/5 A, including mounted universal DIN rail adapter UTA 107/30
- Easy handling thanks to automatic battery detection, tool-free battery replacement during operation, and communication via the IFS interface
- Optimum use of the buffer time and preventive monitoring of the energy storage
- Rapid battery charging
- Comprehensive signaling and parameterization
- Fast tripping of standard circuit breakers with SFB (selective fuse breaking) technology
- Optimum protection with dip coating for 100 % humidity
- One UPS module - two voltages
- Maximum flexibility, thanks to the dual output
Technical Specifications
DC operation
Input Voltage | 24 V DC |
Nominal input voltage range | 18 V DC ... 30 V DC |
Input voltage range | 18 V DC ... 30 V DC |
Input voltage range DC | 18 V DC ... 30 V DC |
Voltage type of supply voltage | DC |
Buffer period | 3 h (With battery module 38 AH) |
Current consumption | 16 A (maximum, mains operation) |
Current consumption | 104 mA (No load, mains operation) |
Current consumption | 4 A (Charging, mains operation) |
Fixed backup threshold | ≤ 22 V DC |
Variable connect threshold | 1 V/0.1 s |
Recommended breaker for input protection | 16 A ... 20 A (Characteristic B) |
Output data
Efficiency | > 98 % (Mains operation, with charged energy storage) |
Efficiency | > 93 % (Mains operation, with charged energy storage) |
Nominal Output Voltage | 24 V DC |
Output voltage range | 18 V DC ... 30 V DC (UOUT = UIN - 0.5 V DC) |
Nominal output current (IN) | 10 A (-25 °C ... 60 °C) |
Nominal output current (IN) | 5 A (-25 °C ... 60 °C) |
Output current limit | In mains mode according to connected upstream current limiting device |
Output current limit | > 15 A (Battery operation) |
Bridging time | 10800 s |
Derating | 60 °C ... 70 °C (2.5 %/K) |
Derating | 60 °C ... 70 °C (2.5 %/K) |
UPS connection in parallel | yes |
UPS connection in series | no |
Output Power | 240 W |
Total power P12V + P24V | max. 360 W |
Power dissipation | 2.6 W (Mains operation) |
Power dissipation | 4.6 W (Mains operation) |
Power dissipation | 2.9 W (Battery operation) |
Power dissipation | 5.27 W (Battery operation) |
Connection in parallel | yes, up to 2 modules with redundancy module |
Connection in parallel | 2 (Devices) |
Connection in series | No |
Connection in series | no |
Mains operation
Nominal Output Voltage | 12 V DC |
Nominal Output Voltage | 24 V DC |
Output voltage range | 18 V DC ... 30 V DC (UOUT = UIN - 0.5 V DC) |
Nominal output current (IN) | 5 A (-25 °C ... 60 °C) |
Nominal output current (IN) | 10 A (-25 °C ... 60 °C) |
POWER BOOST (IBoost) | 7.5 A (-25 °C ... 40 °C) |
POWER BOOST (IBoost) | 15 A (-25 °C ... 40 °C) |
Selective Fuse Breaking (ISFB) | 60 A (-25 °C ... 60 °C) |
Duration | 12 ms (SFB technology) |
Battery operation
Nominal Output Voltage | 12 V DC |
Nominal Output Voltage | 24 V DC |
Output voltage range | 19.2 V DC ... 27.6 V DC (UOUT = UBAT - 0,5 V DC) |
Nominal output current (IN) | 5 A (-25 °C ... 60 °C) |
Nominal output current (IN) | 10 A (-25 °C ... 60 °C) |
POWER BOOST (IBoost) | 7.5 A (-25 °C ... 40 °C) |
POWER BOOST (IBoost) | 15 A (-25 °C ... 40 °C) |
Selective Fuse Breaking (ISFB) | 65 A (-25 °C ... 60 °C) |
Duration | 15 ms (SFB technology) |
Signal: Alarm
Output description | Relay (floating) |
Maximum Switching Voltage | ≤ 30 V AC/DC |
Continuous load current | ≤ 100 mA |
Signal: Battery charge
Output description | Relay (floating) |
Maximum Switching Voltage | ≤ 30 V AC/DC |
Output Voltage | 24 V |
Continuous load current | ≤ 100 mA |
Signal: Battery mode
Output description | Relay (floating) |
Maximum Switching Voltage | ≤ 30 V AC/DC |
Output Voltage | 24 V |
Continuous load current | ≤ 100 mA |
Signal: POWER BOOST
Output Voltage | 24 V DC |
Continuous load current | 100 mA |
Energy storage
Nominal voltage UN | 24 V DC |
End-of-charge voltage | 24 V DC ... 29 V DC (temperature compensated) |
Charging current | 0.2 A ... 2.88 A |
Nominal capacity range | 1.3 Ah ... 60 Ah |
Battery presence check/time interval | 1 min. |
Battery presence check (cyclic) | 60 s |
Energy storage device connection in parallel | yes, 15 (observe line protection) |
Energy storage device connection in series | no |
IQ Technology | Yes |
Temperature compensation | 42 mV/K (preset) |
Temperature compensation (preset) | 42 mV/K |
Network management | Yes |
Input
Connection Method | Screw connection |
Conductor cross section, rigid min. | 0.2 mm² |
Conductor cross section, rigid max. | 2.5 mm² |
Conductor cross section flexible min. | 0.2 mm² |
Conductor cross section flexible max. | 2.5 mm² |
Conductor cross section AWG min. | 16 |
Conductor cross section AWG max. | 12 |
Stripping length | 7 mm |
Screw thread | M4 |
Tightening torque, min | 0.5 Nm |
Tightening torque max | 0.6 Nm |
Output
Connection Method | Screw connection |
Conductor cross section, rigid min. | 0.2 mm² |
Conductor cross section, rigid max. | 2.5 mm² |
Conductor cross section flexible min. | 0.2 mm² |
Conductor cross section flexible max. | 2.5 mm² |
Conductor cross section AWG min. | 16 |
Conductor cross section AWG max. | 12 |
Stripping length | 7 mm |
Screw thread | M4 |
Tightening torque, min | 0.5 Nm |
Tightening torque max | 0.6 Nm |
Signal
Connection Method | Screw connection |
Conductor cross section, rigid min. | 0.2 mm² |
Conductor cross section, rigid max. | 2.5 mm² |
Conductor cross section flexible min. | 0.2 mm² |
Conductor cross section flexible max. | 2.5 mm² |
Conductor cross section AWG min. | 24 |
Conductor cross section AWG max. | 12 |
Stripping length | 7 mm |
Screw thread | M4 |
Tightening torque, min | 0.5 Nm |
Tightening torque max | 0.6 Nm |
Interfaces
Interface | IFS (Interface system data port) |
Signaling
Types of signaling | LED |
Types of signaling | Relay contact |
Types of signaling | Interface/software |
Signal output
Signalization designation | Power In OK |
Status display | LED |
Note on status display | static on |
Note on status display | static on |
Signal output: Switching output
Signalization designation | Alarm |
Status display | LED |
Note on status display | static on |
Color | red |
Note on status display | static on |
Signalization designation | Battery charge |
Status display | LED bar graph |
Note on status display | dynamic |
Color | red/green |
Note on status display | dynamic |
Signalization designation | Battery mode |
Status display | LED |
Note on status display | static on |
Color | yellow |
Note on status display | static on |
Signal output: Transistor output, active
Signalization designation | POWER BOOST |
Electrical properties
Insulation voltage input/output | 500 V DC |
Insulation voltage input, output / housing | 750 V DC |
Product properties
Product family | QUINT USV |
IQ Technology | Yes |
MTBF (IEC 61709, SN 29500) | > 652000 h (40 °C) |
Insulation characteristics
Protection class | III |
Life expectancy (electrolytic capacitors)
Time | 33941 h |
Dimensions
Width | 35 mm |
Height | 130 mm |
Depth | 125 mm |
Installation dimensions
Installation distance right/left | 5 mm / 5 mm |
Installation distance top/bottom | 50 mm / 50 mm |
Alternative assembly
Width | 123 mm |
Height | 130 mm |
Depth | 39 mm |
Mounting
Mounting Type | DIN rail mounting |
Assembly instructions | alignable: horizontal 5 mm, vertical 50 mm |
Mounting Position | horizontal DIN rail NS 35, EN 60715 |
Material specifications
Housing Material | Metal |
Housing Material | Steel sheet, zinc-plated |
Type of housing | Aluminum (AlMg3) |
Hood version | Galvanized sheet steel, free from chrome (VI) |
Ambient conditions
Degree of Protection | IP20 |
Ambient Temperature (Operation) | -25 °C ... 70 °C |
Ambient temperature (storage/transport) | -40 °C ... 85 °C |
Climatic class | 3K3 (in acc. with EN 60721) |
Max. permissible relative humidity (operation) | ≤ 95 % (25 °C, non-condensing) |
Shock | 18 ms, 30g, in each space direction (according to IEC 60068-2-27) |
Vibration (Operation) | < 15 Hz, amplitude ±2.5 mm (according to IEC 60068-2-6) |
Vibration (Operation) | 15 Hz ... 150 Hz, 2.3g tv = 90 min. |
Standards and Regulations
Rail applications | EN 50121-4 |
Standard – Electronic equipment for use in electrical power installations and their assembly into electrical power installations | EN 50178/VDE 0160 (PELV) |
Standard - Electrical safety | EN 60950-1/VDE 0805 (SELV) |
Approvals
UL approvals | UL Listed UL 508 |
UL approvals | UL/C-UL Recognized UL 60950-1 |
EMC data
Low Voltage Directive | Conformance with Low Voltage Directive 2014/35/EC |
EMC requirements for noise emission | EN 61000-6-3 |
EMC requirements for noise emission | EN 61000-6-4 |
EMC requirements for noise immunity | EN 61000-6-1 |
EMC requirements for noise immunity | EN 61000-6-2 |
Electromagnetic compatibility | Conformance with EMC Directive 2014/30/EU |
Electrostatic discharge
Standards/regulations | EN 61000-4-2 |
Contact discharge | 8 kV (Test Level 4) |
Discharge in air | 15 kV (Test Level 4) |
Comments | Criterion A |
Electromagnetic HF field
Standards/regulations | EN 61000-4-3 |
Frequency Range | 80 MHz ... 1 GHz |
Test field strength | 20 V/m |
Frequency Range | 1 GHz ... 2 GHz |
Test field strength | 10 V/m |
Frequency Range | 2 GHz ... 3 GHz |
Test field strength | 3 V/m |
Comments | Criterion A |
Fast transients (burst)
Standards/regulations | EN 61000-4-4 |
Input | 2 kV (Test Level 3 - asymmetrical) |
Output | 2 kV (Test Level 3 - asymmetrical) |
Signal | 2 kV (Test Level 4 - asymmetrical) |
Comments | Criterion A |
Surge voltage load (surge)
Standards/regulations | EN 61000-4-5 |
Input | 0.5 kV (Test Level 1 - symmetrical) |
Input | 0.5 kV (Test Level 1 - asymmetrical) |
Output | 0.5 kV (Test Level 1 - symmetrical) |
Output | 0.5 kV (Test Level 1 - asymmetrical) |
Signal | 1 kV (Test Level 2 - asymmetrical) |
Comments | Criterion B |
Conducted interference
Standards/regulations | EN 61000-4-6 |
I/O/S | asymmetrical |
Frequency Range | 0.15 MHz ... 80 MHz |
Comments | Criterion A |
Voltage | 10 V (Test Level 3) |
Emitted interference
Standards/regulations | EN 61000-6-3 |
Radio interference voltage in acc. with EN 55011 | EN 55011 (EN 55022) Class B, area of application: Industry and residential |
Emitted radio interference in acc. with EN 55011 | EN 55011 (EN 55022) Class B, area of application: Industry and residential |
Criteria
Criterion A | Normal operating behavior within the specified limits. |
Criterion B | Temporary impairment to operational behavior that is corrected by the device itself. |
Accessories
Why Proax for Phoenix Contact 2320461?
Proax is an authorized distributor of Phoenix Contact 2320461 and one of Phoenix Contact's largest distributors in North America. Our highly skilled in-house technical team is ready to assist with any technical needs.
Have a question in mind? to help you get the right product as quickly as possible for your project. We're always here to help!
Short Lead Time
Highly Trained Staff
Live Chat
Technical Support
Local Inventory
60+ Years Experience
Additional Information
Pack Size | 1 |
Recommended