Series QUINT-UPS
QUINT-UPS/ 24DC/ 24DC/ 5/1.3AH - Uninterruptible power supply
Uninterruptible power supply with IQ Technology and integrated battery for DIN rail mounting, input: 24 V DC, output: 24 V DC/5 A, battery: lead AGM 1.2 Ah, including mounted universal DIN rail adapter UTA 107/30
- Easy handling thanks to automatic battery detection, tool-free battery replacement during operation, and communication via the IFS interface
- Reliable starting of difficult loads with the static POWER BOOST power reserve with up to 1.5 times the nominal current permanently
- Fast tripping of standard circuit breakers with SFB (selective fuse breaking) technology
- Device suitable for universal use thanks to comprehensive license package and extensive parameterization and diagnostics options
Technical Specifications
General
Note on the battery | This product contains a battery with a limited shelf life that must be charged every few months. The product packaging indicates when the battery must be started up or recharged. The general shelf life can be found in the technical data area under “Latest startup”. |
DC operation
Input Voltage | 24 V DC |
Input voltage range | 18 V DC ... 30 V DC |
Input voltage range DC | 18 V DC ... 30 V DC |
Voltage type of supply voltage | DC |
Buffer period | 50 min. (1 A) |
Buffer period | 5 min. (5 A) |
Current consumption | 9.3 A (24 V DC) |
Current consumption | 9.7 mA |
Current consumption | 1.7 A |
Current consumption | 7 A |
Fixed backup threshold | ≤ 22.6 V DC |
Output data
Efficiency | > 97.1 % (Mains operation, with charged energy storage) |
Efficiency | 97.31 % |
Nominal Output Voltage | 24 V DC |
Output voltage range | 18 V DC ... 30 V DC |
Nominal output current (IN) | 5 A (0 °C ... 40 °C) |
Output current limit | > 7.5 A (Battery operation) |
Bridging time | 360 s |
Derating | 60 °C ... 70 °C (2.5 %/K) |
Output Power | 120 W |
Power dissipation | 2.5 W (Mains operation) |
Power dissipation | 2.7 W (Mains operation) |
Power dissipation | 1.9 W (Mains operation) |
Power dissipation | 3.3 W (Battery operation) |
Power dissipation | 3.3 W (Battery operation) |
Power dissipation | 4.1 W (Battery operation) |
Output fuse | 1x 15 A |
Connection in parallel | 2 |
Connection in series | No |
Mains operation
Nominal Output Voltage | 24 V DC |
Output voltage range | 18 V DC ... 30 V DC (UOUT = UIN - 0,1 V DC) |
Nominal output current (IN) | 5 A (0 °C ... 40 °C) |
POWER BOOST (IBoost) | 7.5 A (0 °C ... 40 °C) |
Selective Fuse Breaking (ISFB) | 30 A (0 °C ... 40 °C) |
Duration | 12 ms (SFB technology) |
Battery operation
Nominal Output Voltage | 24 V DC |
Output voltage range | 19.2 V DC ... 27.6 V DC (UOUT = UBAT - 0,5 V DC) |
Nominal output current (IN) | 5 A (0 °C ... 40 °C) |
POWER BOOST (IBoost) | 7.5 A (0 °C ... 40 °C) |
Selective Fuse Breaking (ISFB) | 32.5 A (0 °C ... 40 °C) |
Duration | 15 ms (SFB technology) |
Signal: Alarm
Output description | Relay |
Output Voltage | ≤ 30 V AC/DC |
Continuous load current | ≤ 100 mA |
Signal: Battery charge
Output description | Relay |
Output Voltage | ≤ 30 V AC/DC |
Continuous load current | ≤ 100 mA |
Signal: Battery mode
Output description | Relay |
Output Voltage | ≤ 30 V AC/DC |
Continuous load current | ≤ 100 mA |
Signal
Continuous load current | ≤ 200 mA |
Energy storage
Nominal voltage UN | 24 V DC |
End-of-charge voltage | 24 V DC ... 29 V DC (temperature compensated) |
Charging current | 0.36 A |
Nominal capacity | 1.2 Ah |
Buffer period | 50 min. (1 A) |
Buffer period | 5 min. (5 A) |
Latest startup date (battery only) | 3 Months (0 °C ... 20 °C) |
Latest startup date (battery only) | 1 Months (30 °C ... 40 °C) |
Latest startup (battery only) - range | 1 Months ... 3 Months (20 °C ... 30 °C) |
Battery technology | VRLA-AGM |
Memory medium | VRLA-AGM Battery 1.2 Ah |
Accumulator type | 2x BB Battery BP1.2-12FR (from UPS V/C-level 05) |
IQ Technology | Yes |
Temperature sensor | yes |
Network management | Yes |
Input
Connection Method | Screw connection |
Conductor cross section, rigid min. | 0.2 mm² |
Conductor cross section, rigid max. | 2.5 mm² |
Conductor cross section flexible min. | 0.2 mm² |
Conductor cross section flexible max. | 2.5 mm² |
Conductor cross section AWG min. | 20 |
Conductor cross section AWG max. | 12 |
Stripping length | 7 mm |
Screw thread | M4 |
Tightening torque, min | 0.5 Nm |
Tightening torque max | 0.6 Nm |
Output
Connection Method | Screw connection |
Conductor cross section, rigid min. | 0.2 mm² |
Conductor cross section, rigid max. | 2.5 mm² |
Conductor cross section flexible min. | 0.2 mm² |
Conductor cross section flexible max. | 2.5 mm² |
Conductor cross section AWG min. | 20 |
Conductor cross section AWG max. | 12 |
Stripping length | 7 mm |
Screw thread | M4 |
Tightening torque, min | 0.5 Nm |
Tightening torque max | 0.6 Nm |
Signal
Conductor cross section, rigid min. | 0.2 mm² |
Conductor cross section, rigid max. | 2.5 mm² |
Conductor cross section flexible min. | 0.2 mm² |
Conductor cross section flexible max. | 2.5 mm² |
Conductor cross section AWG min. | 24 |
Conductor cross section AWG max. | 12 |
Screw thread | M4 |
Tightening torque, min | 0.5 Nm |
Tightening torque max | 0.6 Nm |
Interfaces
Interface | IFS (Interface system data port) |
Signaling
Types of signaling | LED |
Types of signaling | Relay contact |
Types of signaling | Interface/software |
Signal output
Signalization designation | Power In OK |
Status display | LED |
Note on status display | static on |
Note on status display | static on |
Signal output: Switching output
Signalization designation | Alarm |
Status display | LED |
Note on status display | static on |
Color | red |
Note on status display | static on |
Signalization designation | Battery charge |
Status display | LED bar graph |
Note on status display | dynamic |
Color | red/green |
Note on status display | dynamic |
Signalization designation | Battery mode |
Status display | LED |
Note on status display | static on |
Color | yellow |
Note on status display | static on |
Product properties
Product family | QUINT UPS ‒ UPS with integrated battery |
Disposal | Used batteries must not be thrown away with household waste, they should instead be disposed of in accordance with applicable national regulations. |
IQ Technology | Yes |
MTBF (IEC 61709, SN 29500) | > 806000 h (40 °C) |
Insulation characteristics
Protection class | III |
Degree of pollution | 2 |
Life expectancy (electrolytic capacitors)
Time | 316800 h |
Dimensions
Width | 88 mm |
Height | 138 mm |
Depth | 125 mm |
Installation dimensions
Installation distance right/left | 5 mm / 5 mm |
Installation distance top/bottom | 50 mm / 50 mm |
Mounting
Mounting Type | DIN rail mounting |
Assembly instructions | alignable: horizontal 5 mm, vertical 50 mm |
Mounting Position | horizontal DIN rail NS 35, EN 60715 |
Material specifications
Housing Material | Metal |
Housing Material | Steel sheet, zinc-plated |
Type of housing | Steel sheet, zinc-plated |
Side element version | Galvanized sheet steel, closed |
Ambient conditions
Degree of Protection | IP20 |
Ambient temperature (storage/transport) | -20 °C ... 40 °C |
Ambient temperature (charge) | 0 °C ... 40 °C |
Ambient temperature (discharge) | -20 °C ... 50 °C |
Climatic class | 3K3 (in acc. with EN 60721) |
Max. permissible relative humidity (operation) | ≤ 95 % (25 °C, non-condensing) |
Shock | 18 ms, 30g, in each space direction (according to IEC 60068-2-27) |
Vibration (Operation) | < 15 Hz, amplitude ±2.5 mm (according to IEC 60068-2-6) |
Vibration (Operation) | 15 Hz ... 150 Hz, 2.3g tv = 90 min. |
Standards and Regulations
Rail applications | EN 50121-4 |
Standard – Electronic equipment for use in electrical power installations and their assembly into electrical power installations | EN 50178/VDE 0160 (PELV) |
Standard - Electrical safety | EN 60950-1/VDE 0805 (SELV) |
Standard - Electrical safety | EN 61558-2-17 |
Approvals
UL approvals | UL/C-UL Recognized UL 60950-1 |
UL approvals | UL Listed UL 508 |
EMC data
Low Voltage Directive | Conformance with Low Voltage Directive 2014/35/EC |
EMC requirements for noise emission | EN 61000-6-3 |
EMC requirements for noise emission | EN 61000-6-4 |
EMC requirements for noise immunity | EN 61000-6-1 |
EMC requirements for noise immunity | EN 61000-6-2 |
Electromagnetic compatibility | Conformance with EMC Directive 2014/30/EU |
Electrostatic discharge
Standards/regulations | EN 61000-4-2 |
Contact discharge | 8 kV (Test Level 4) |
Discharge in air | 15 kV (Test Level 4) |
Comments | Criterion A |
Electromagnetic HF field
Standards/regulations | EN 61000-4-3 |
Frequency Range | 80 MHz ... 1 GHz |
Test field strength | 20 V/m |
Frequency Range | 1 GHz ... 2 GHz |
Test field strength | 10 V/m |
Frequency Range | 2 GHz ... 3 GHz |
Test field strength | 3 V/m |
Comments | Criterion A |
Fast transients (burst)
Standards/regulations | EN 61000-4-4 |
Input | 2 kV (Test Level 3 - asymmetrical) |
Output | 2 kV (Test Level 3 - asymmetrical) |
Signal | 2 kV (Test Level 4 - asymmetrical) |
Comments | Criterion A |
Surge voltage load (surge)
Standards/regulations | EN 61000-4-5 |
Input | 0.5 kV (Test Level 1 - symmetrical) |
Input | 0.5 kV (Test Level 1 - asymmetrical) |
Output | 0.5 kV (Test Level 1 - symmetrical) |
Output | 0.5 kV (Test Level 1 - asymmetrical) |
Signal | 1 kV (Test Level 2 - asymmetrical) |
Comments | Criterion B |
Conducted interference
Standards/regulations | EN 61000-4-6 |
I/O/S | asymmetrical |
Frequency Range | 0.15 MHz ... 80 MHz |
Comments | Criterion A |
Voltage | 10 V (Test Level 3) |
Emitted interference
Standards/regulations | EN 61000-6-3 |
Radio interference voltage in acc. with EN 55011 | EN 55011 (EN 55022) Class B, area of application: Industry and residential |
Emitted radio interference in acc. with EN 55011 | EN 55011 (EN 55022) Class B, area of application: Industry and residential |
Criteria
Criterion A | Normal operating behavior within the specified limits. |
Criterion B | Temporary impairment to operational behavior that is corrected by the device itself. |
Accessories
Why Proax for Phoenix Contact 2320254?
Proax is an authorized distributor of Phoenix Contact 2320254 and one of Phoenix Contact's largest distributors in North America. Our highly skilled in-house technical team is ready to assist with any technical needs.
Have a question in mind? to help you get the right product as quickly as possible for your project. We're always here to help!
Short Lead Time
Highly Trained Staff
Live Chat
Technical Support
Local Inventory
60+ Years Experience
Additional Information
Pack Size | 1 |
Recommended
- The redundancy set consists of two QUINT-PS/1AC/24DC/10 power supplies combined with the active QUINT-ORING/24DC/2X10/1X20 redundancy module, so as to guarantee maximum availability of your system.Primary-switched QUINT POWER supply for DIN rail mounting with SFB (selective fuse breaking) technology, input: 1-phase, output: 24 V DC/10 AActive QUINT redundancy module for DIN rail mounting with Auto Current Balancing ACB technology and monitoring functions, input: 24 V DC, output: 24 V DC/2 x 10 A or 1 x 20 A, including mounted UTA 107/30 universal DIN rail adapter