Official Distributor
SKU
MPN
QUINT-PS/24DC/24DC/10
Weight
1.171 kg
Series QUINT-PS
QUINT-PS/24DC/24DC/10 - DC/DC converter
Primary-switched QUINT DC/DC converter for DIN rail mounting with SFB (Selective Fuse Breaking) Technology, input: 24 V DC, output: 24 V DC/10 A
- Reliable starting of difficult loads, thanks to the static POWER BOOST power reserve with up to 125% nominal current permanently
- Preventive function monitoring indicates critical operating states before errors occur
- Constant voltage: output voltage regenerated even at the end of long cables
- Support conversion to various voltage levels
- Electrical isolation: for setting up independent supply systems
Technical Specifications
DC operation
Nominal input voltage range | 24 V DC |
Input voltage range | 18 V DC ... 32 V DC |
Extended input voltage range in operation | 14 V DC ... 18 V DC (Derating) |
Wide-range input | no |
Input voltage range DC | 18 V DC ... 32 V DC |
Input voltage range DC | 14 V DC ... 18 V DC (Consider derating during operation) |
Voltage type of supply voltage | DC |
Inrush Current | < 15 A (typical) |
Inrush current integral (I2t) | < 2.7 A2s |
Mains buffering time | > 12 ms (24 V DC) |
Current consumption | 14 A (24 V, IBOOST) |
Reverse polarity protection | ≤ 30 V DC |
Protective circuit | Transient surge protection; Varistor |
Input fuse | 25 A (internal (device protection)) |
Recommended breaker for input protection | 16 A ... 20 A (Characteristics B, C, D, K) |
Output data
Efficiency | > 92 % |
Output characteristic | U/I |
Nominal Output Voltage | 24 V DC ±1 % |
Setting range of the output voltage (USet) | 18 V DC ... 29.5 V DC (> 24 V DC, constant capacity restricted) |
Nominal output current (IN) | 10 A (-25 °C ... 60 °C) |
POWER BOOST (IBoost) | 12.5 A (-25 °C ... 40 °C permanent, UOUT = 24 V DC ) |
Selective Fuse Breaking (ISFB) | 60 A (12 ms) |
Magnetic circuit breaker tripping | B2 / B4 / B6 / C2 / C4 |
Derating | 60 °C ... 70 °C (2.5 %/K) |
Feedback voltage resistance | 35 V DC |
Protection against overvoltage at the output (OVP) | < 35 V DC |
Max. capacitive load | unlimited |
Active current limitation | Approx. 18 A |
Control deviation | < 1 % (change in load, static 10 % ... 90 %) |
Control deviation | < 2 % (change in load, dynamic 10 % ... 90 %) |
Control deviation | < 0.1 % (change in input voltage ±10 %) |
Residual ripple | < 20 mVPP |
Output Power | 240 W |
Peak switching voltages nominal load | < 10 mVPP (20 MHz) |
Maximum no-load power dissipation | 1.6 W |
Power loss nominal load max. | 24 W |
Rise time | < 2 ms (UOUT (10 % ... 90 %)) |
Connection in parallel | yes, for redundancy and increased capacity |
Connection in series | yes |
Connection in series | 2 (Devices) |
Signal: DC OK active
Output description | UOUT > 0.9 x UN: High signal |
Switching voltage range | 18 V DC ... 24 V DC |
Maximum Inrush Current | < 20 mA (short-circuit-proof) |
Signal: POWER BOOST, active
Output description | IOUT < IN: High signal |
Switching voltage range | 18 V DC ... 24 V DC |
Maximum Inrush Current | < 20 mA (short-circuit-proof) |
Signal: UIN OK, active
Output description | UIN > 19.2 V: High signal |
Switching voltage range | 18 V DC ... 24 V DC |
Maximum Inrush Current | ≤ 20 mA (short-circuit-proof) |
Signal: DC OK floating
Output description | Relay |
Output Voltage | ≤ 30 V AC/DC |
Maximum Inrush Current | ≤ 100 mA |
Input
Connection Method | Pluggable screw connection |
Conductor cross section, rigid min. | 0.2 mm² |
Conductor cross section, rigid max. | 2.5 mm² |
Conductor cross section flexible min. | 0.2 mm² |
Conductor cross section flexible max. | 2.5 mm² |
Conductor cross section AWG min. | 24 |
Conductor cross section AWG max. | 12 |
Stripping length | 8 mm |
Screw thread | M3 |
Tightening torque, min | 0.5 Nm |
Tightening torque max | 0.6 Nm |
Output
Connection Method | Pluggable screw connection |
Conductor cross section, rigid min. | 0.2 mm² |
Conductor cross section, rigid max. | 2.5 mm² |
Conductor cross section flexible min. | 0.2 mm² |
Conductor cross section flexible max. | 2.5 mm² |
Conductor cross section AWG min. | 24 |
Conductor cross section AWG max. | 12 |
Stripping length | 7 mm |
Screw thread | M3 |
Tightening torque, min | 0.5 Nm |
Tightening torque max | 0.6 Nm |
Signal
Conductor cross section, rigid min. | 0.2 mm² |
Conductor cross section, rigid max. | 2.5 mm² |
Conductor cross section flexible min. | 0.2 mm² |
Conductor cross section flexible max. | 2.5 mm² |
Conductor cross section AWG min. | 24 |
Conductor cross section AWG max. | 12 |
Screw thread | M3 |
Tightening torque, min | 0.5 Nm |
Tightening torque max | 0.6 Nm |
Signaling
Types of signaling | LED |
Types of signaling | Active switching output |
Types of signaling | Relay contact |
Signal output: DC OK active
Status display | "DC OK" LED green |
Color | green |
Signal output: POWER BOOST, active
Status display | "BOOST" LED yellow/IOUT > IN : LED on |
Color | yellow |
Note on status display | LED on |
Signal output: UIN OK, active
Status display | LED "UIN < 19.2 V" yellow/UIN < 19.2 V DC: LED on |
Color | yellow |
Note on status display | LED on |
Signal output: DC OK floating
Note on status display | UOUT > 0.9 x UN: Contact closed |
Electrical properties
Number of phases | 1.00 |
Insulation voltage input/output | 1.5 kV (type test) |
Insulation voltage input/output | 1 kV (routine test) |
Insulation voltage input/output | 1 kV (type test) |
Product properties
MTBF (IEC 61709, SN 29500) | > 763000 h (40 °C) |
Insulation characteristics
Protection class | III |
Degree of pollution | 2 |
Dimensions
Width | 48 mm |
Height | 130 mm |
Depth | 125 mm |
Installation dimensions
Installation distance right/left | 0 mm / 0 mm (≤ 70 °C) |
Installation distance right/left (active) | 15 mm / 15 mm (≤ 70 °C) |
Installation distance top/bottom | 50 mm / 50 mm (≤ 70 °C) |
Installation distance top/bottom (active) | 50 mm / 50 mm (≤ 70 °C) |
Alternative assembly
Width | 122 mm |
Height | 130 mm |
Depth | 51 mm |
Mounting
Mounting Type | DIN rail mounting |
Assembly instructions | alignable: PN ≥50%, 5 mm horizontally, 15 mm next to active components, 50 mm verticallyalignable: PN <50%, 0 mm horizontally, 40 mm vertically top, 20 mm vertically bottom |
Mounting Position | horizontal DIN rail NS 35, EN 60715 |
With protective coating | No |
Material specifications
Housing Material | Metal |
Type of housing | Aluminum (AlMg3) |
Hood version | Galvanized sheet steel, free from chrome (VI) |
Ambient conditions
Degree of Protection | IP20 |
Ambient Temperature (Operation) | -25 °C ... 70 °C (> 60 °C derating, 2.5 %/K, startup at -40°C type-tested) |
Ambient temperature (storage/transport) | -40 °C ... 85 °C |
Ambient temperature (start-up type tested) | -40 °C |
Climatic class | 3K3 (in acc. with EN 60721) |
Max. permissible relative humidity (operation) | ≤ 95 % (at 25 °C, non-condensing) |
Shock | 18 ms, 30g, in each space direction (according to IEC 60068-2-27) |
Vibration (Operation) | < 5 Hz, amplitude ±1.6 mm (according to IEC 60068-2-6) |
Vibration (Operation) | 5 Hz ... 100 Hz, 4g, 90 min. |
Standards and Regulations
Rail applications | EN 50121-4 |
Standard – Electronic equipment for use in electrical power installations and their assembly into electrical power installations | EN 50178/VDE 0160 (PELV) |
Standard - Electrical safety | EN 60950-1/VDE 0805 (SELV) |
Standard – Safety extra-low voltage | EN 60950-1 (SELV) |
Standard – Safety extra-low voltage | EN 60204 (PELV) |
Standard - Safe isolation | DIN VDE 0100-410 |
Approvals
Shipbuilding approval | DNV GL (EMC B) |
UL approvals | UL/C-UL listed UL 508 |
UL approvals | UL/C-UL Recognized UL 60950-1 |
UL approvals | UL ANSI/ISA-12.12.01 Class I, Division 2, Groups A, B, C, D (Hazardous Location) |
EMC data
EMC requirements for noise emission | EN 61000-6-3 |
EMC requirements for noise emission | EN 61000-6-4 |
EMC requirements for noise immunity | EN 61000-6-1 |
EMC requirements for noise immunity | EN 61000-6-2 |
Electromagnetic compatibility | Conformance with EMC Directive 2014/30/EU |
Electrostatic discharge
Standards/regulations | EN 61000-4-2 |
Contact discharge | 8 kV (Test Level 4) |
Discharge in air | 15 kV (Test Level 4) |
Comments | Criterion A |
Electromagnetic HF field
Standards/regulations | EN 61000-4-3 |
Frequency Range | 80 MHz ... 1 GHz |
Test field strength | 10 V/m (Test Level 3) |
Frequency Range | 1 GHz ... 2 GHz |
Test field strength | 10 V/m (Test Level 3) |
Frequency Range | 2 GHz ... 3 GHz |
Test field strength | 10 V/m (Test Level 3) |
Comments | Criterion A |
Fast transients (burst)
Standards/regulations | EN 61000-4-4 |
Input | 2 kV (Test Level 3 - asymmetrical) |
Output | 2 kV (Test Level 3 - asymmetrical) |
Signal | 2 kV (Test Level 4 - asymmetrical) |
Comments | Criterion A |
Surge voltage load (surge)
Standards/regulations | EN 61000-4-5 |
Input | 0.5 kV (Test Level 1 - symmetrical) |
Input | 0.5 kV (Test Level 1 - asymmetrical) |
Output | 0.5 kV (Test Level 1 - symmetrical) |
Output | 0.5 kV (Test Level 1 - asymmetrical) |
Signal | 1 kV (Test Level 2 - asymmetrical) |
Comments | Criterion B |
Conducted interference
Standards/regulations | EN 61000-4-6 |
I/O/S | asymmetrical |
Frequency Range | 0.15 MHz ... 80 MHz |
Comments | Criterion A |
Voltage | 10 V (Test Level 3) |
Emitted interference
Standards/regulations | EN 61000-6-3 |
Radio interference voltage in acc. with EN 55011 | EN 55011 (EN 55022) Class B, area of application: Industry and residential |
Emitted radio interference in acc. with EN 55011 | EN 55011 (EN 55022) Class B, area of application: Industry and residential |
Criteria
Criterion A | Normal operating behavior within the specified limits. |
Criterion B | Temporary impairment to operational behavior that is corrected by the device itself. |
Accessories
Why Proax for Phoenix Contact 2320092?
Proax is an authorized distributor of Phoenix Contact 2320092 and one of Phoenix Contact's largest distributors in North America. Our highly skilled in-house technical team is ready to assist with any technical needs.
Have a question in mind? to help you get the right product as quickly as possible for your project. We're always here to help!
Short Lead Time
Highly Trained Staff
Live Chat
Technical Support
Local Inventory
60+ Years Experience
Additional Information
Pack Size | 1 |
Recommended