Official Distributor
SKU
MPN
QUINT-PS/1AC/12DC/15
Weight
1.51 kg
Series QUINT-PS
QUINT-PS/1AC/12DC/15 - Power supply unit
Primary-switched power supply unit QUINT POWER, Pluggable screw connection, DIN rail mounting, SFB Technology (Selective Fuse Breaking), input: 1-phase, output: 12 V DC / 15 A
- Reliable starting of difficult loads
- Quick tripping of standard circuit breakers
- Preventive function monitoring
Technical Specifications
Input data
Nominal input voltage range | 100 V AC ... 240 V AC |
Input voltage range | 85 V AC ... 264 V AC |
Input voltage range | 90 V DC ... 350 V DC (UL 508: ≤ 250 V DC) |
Input Voltage Range AC | 85 V AC ... 264 V AC |
Input voltage range DC | 90 V DC ... 350 V DC (UL 508: ≤ 250 V DC) |
Electric strength, max. | 300 V AC |
Voltage type of supply voltage | AC/DC |
Inrush Current | < 15 A (typical) |
Inrush current integral (I2t) | < 1.5 A2s |
AC frequency range | 45 Hz ... 65 Hz |
Frequency range DC | 0 Hz |
Mains buffering time | > 65 ms (120 V AC) |
Mains buffering time | > 65 ms (230 V AC) |
Current consumption | 1.9 A (120 V AC) |
Current consumption | 0.9 A (230 V AC) |
Current consumption | 1.9 A (110 V DC) |
Current consumption | 0.9 A (220 V DC) |
Nominal Power Consumption | 210 VA |
Protective circuit | Transient surge protection; Varistor |
Typical response time | < 0.5 s |
Input fuse | 6.3 A (slow-blow, internal) |
Permissible backup fuse | B10 B16 AC: |
Permissible DC backup fuse | DC: Connect a suitable fuse upstream |
Recommended breaker for input protection | 10 A ... 16 A (AC: Characteristics B, C, D, K) |
Discharge current to PE | < 3.5 mA |
Output data
Efficiency | > 89 % (for 230 V AC and nominal values) |
Output characteristic | U/I |
Nominal Output Voltage | 12 V DC ±1 % |
Setting range of the output voltage (USet) | 5 V DC ... 18 V DC (> 12 V DC, constant capacity restricted) |
Nominal output current (IN) | 15 A (-25 °C ... 60 °C) |
POWER BOOST (IBoost) | 16 A (-25 °C ... 40 °C permanent) |
Selective Fuse Breaking (ISFB) | 60 A (12 ms) |
Magnetic circuit breaker tripping | B2 / B4 / B6 / C2 / C4 |
Derating | 60 °C ... 70 °C (2.5 %/K) |
Feedback voltage resistance | max. 25 V DC |
Protection against overvoltage at the output (OVP) | < 25 V DC |
Control deviation | < 1 % (change in load, static 10 % ... 90 %) |
Control deviation | < 2 % (change in load, dynamic 10 % ... 90 %) |
Control deviation | < 0.1 % (change in input voltage ±10 %) |
Residual ripple | < 10 mVPP (with nominal values) |
Short-circuit-proof | yes |
Output Power | 180 W |
Maximum no-load power dissipation | 5 W |
Power loss nominal load max. | 21 W |
Rise time | < 0.5 ms |
Connection in parallel | yes, for redundancy and increased capacity |
Connection in series | yes |
Signal: DC OK active
Output description | UOUT > 0.9 x UN: High signal |
Switching voltage range | 5 V DC ... 12 V DC |
Output Voltage | 12 V DC |
Maximum Inrush Current | ≤ 20 mA (short-circuit-proof) |
Continuous load current | ≤ 20 mA |
Signal: DC OK floating
Output description | Relay contact, UOUT > 0.9 x UN: Contact closed |
Maximum Switching Voltage | 30 V AC |
Maximum Switching Voltage | 24 V DC |
Maximum Inrush Current | 0.5 A |
Maximum Inrush Current | 1 A |
Continuous load current | 1 A |
Signal: POWER BOOST, active
Output description | IOUT < IN: High signal |
Switching voltage range | 5 V DC ... 12 V DC |
Output Voltage | 12 V DC |
Maximum Inrush Current | ≤ 20 mA (short-circuit-proof) |
Continuous load current | ≤ 20 mA |
Input
Connection Method | Pluggable screw connection |
Conductor cross section, rigid min. | 0.2 mm² |
Conductor cross section, rigid max. | 2.5 mm² |
Conductor cross section flexible min. | 0.2 mm² |
Conductor cross section flexible max. | 2.5 mm² |
Conductor cross section AWG min. | 16 |
Conductor cross section AWG max. | 12 |
Stripping length | 7 mm |
Screw thread | M3 |
Tightening torque, min | 0.5 Nm |
Tightening torque max | 0.6 Nm |
Output
Connection Method | Pluggable screw connection |
Conductor cross section, rigid min. | 0.2 mm² |
Conductor cross section, rigid max. | 2.5 mm² |
Conductor cross section flexible min. | 0.2 mm² |
Conductor cross section flexible max. | 2.5 mm² |
Conductor cross section AWG min. | 16 |
Conductor cross section AWG max. | 12 |
Stripping length | 7 mm |
Screw thread | M3 |
Tightening torque, min | 0.5 Nm |
Tightening torque max | 0.6 Nm |
Signal
Connection Method | Pluggable screw connection |
Conductor cross section, rigid min. | 0.2 mm² |
Conductor cross section, rigid max. | 2.5 mm² |
Conductor cross section flexible min. | 0.2 mm² |
Conductor cross section flexible max. | 2.5 mm² |
Conductor cross section AWG min. | 16 |
Conductor cross section AWG max. | 12 |
Screw thread | M3 |
Tightening torque, min | 0.5 Nm |
Tightening torque max | 0.6 Nm |
Signaling
Types of signaling | LED |
Types of signaling | Active switching output |
Types of signaling | Relay contact |
Signal output: DC OK active
Status display | UOUT > 0.9 x UN: "DC OK" LED green |
Note on status display | UOUT < 0.9 x UN: Flashing "DC OK" LED |
Note on status display | IOUT < IN: LED ON |
Signal output: DC OK floating
Status display | UOUT > 0.9 x UN: "DC OK" LED green |
Note on status display | UOUT < 0.9 x UN: Flashing "DC OK" LED |
Signal output: POWER BOOST, active
Status display | IOUT > IN: LED "BOOST" yellow |
Electrical properties
Number of phases | 1.00 |
Insulation voltage input/output | 4 kV AC (type test) |
Insulation voltage input/output | 2 kV AC (routine test) |
Insulation voltage output / PE | 500 V DC (routine test) |
Insulation voltage input / PE | 3.5 kV AC (type test) |
Insulation voltage input / PE | 2 kV AC (routine test) |
Product properties
Product family | QUINT POWER |
MTBF (IEC 61709, SN 29500) | > 1000000 h (25 °C) |
MTBF (IEC 61709, SN 29500) | > 570000 h (40 °C) |
MTBF (IEC 61709, SN 29500) | > 250000 h (60 °C) |
Insulation characteristics
Protection class | I |
Degree of pollution | 2 |
Dimensions
Width | 60 mm |
Height | 130 mm |
Depth | 125 mm |
Installation dimensions
Installation distance right/left | 5 mm / 5 mm |
Installation distance top/bottom | 50 mm / 50 mm |
Alternative assembly
Width | 122 mm |
Height | 130 mm |
Depth | 63 mm |
Mounting
Mounting Type | DIN rail mounting |
Assembly instructions | alignable: PN ≥50%, 5 mm horizontally, 15 mm next to active components, 50 mm verticallyalignable: PN <50%, 0 mm horizontally, 40 mm vertically top, 20 mm vertically bottom |
Mounting Position | horizontal DIN rail NS 35, EN 60715 |
With protective coating | No |
Material specifications
Housing Material | Metal |
Type of housing | Steel sheet, zinc-plated |
Ambient conditions
Degree of Protection | IP20 |
Ambient Temperature (Operation) | -25 °C ... 70 °C (> 60 °C Derating: 2,5 %/K) |
Ambient temperature (storage/transport) | -40 °C ... 85 °C |
Ambient temperature (start-up type tested) | -40 °C |
Maximum altitude | 5000 m |
Climatic class | 3K3 (in acc. with EN 60721) |
Max. permissible relative humidity (operation) | ≤ 95 % (at 25 °C, non-condensing) |
Shock | 18 ms, 30g, in each space direction (according to IEC 60068-2-27) |
Vibration (Operation) | < 15 Hz, amplitude ±2.5 mm (according to IEC 60068-2-6) |
Vibration (Operation) | 15 Hz ... 150 Hz, 2.3g, 90 min. |
Standards and Regulations
Rail applications | EN 50121-4 |
Rail applications | EN 50121-3-2 |
Standard – Limitation of mains harmonic currents | EN 61000-3-2 |
Standard - Electrical safety | IEC 61010-2-201 (SELV) |
Standard - Equipment safety | GS (tested safety) |
Standard - Approval for medical use | IEC 60601-1, 2 x MOOP |
Standard – Protection against shock currents, basic requirements for protective separation in electrical equipment | EN 50178 |
Standard – Safety extra-low voltage | IEC 61010-1 (SELV) |
Standard – Safety extra-low voltage | IEC 61010-2-201 (PELV) |
Standard - Safe isolation | IEC 61010-2-201 |
Standard - safety for equipment for measurement, control, and laboratory use | IEC 61010-1 |
Overvoltage category
EN 62477-1 | III |
Approvals
CSA | CAN/CSA-C22.2 No. 60950-1-07 |
CSA | CSA-C22.2 No. 107.1-01 |
UL approvals | UL Listed UL 508 |
UL approvals | UL/C-UL Recognized UL 60950-1 |
UL approvals | UL ANSI/ISA-12.12.01 Class I, Division 2, Groups A, B, C, D (Hazardous Location) |
EMC data
Low Voltage Directive | Conformance with Low Voltage Directive 2014/35/EC |
EMC requirements for noise emission | EN 61000-6-3 |
EMC requirements for noise emission | EN 61000-6-4 |
EMC requirements for noise immunity | EN 61000-6-1 |
EMC requirements for noise immunity | EN 61000-6-2 |
Electromagnetic compatibility | Conformance with EMC Directive 2014/30/EU |
Noise emission | EN 55011 (EN 55022) |
Electrostatic discharge
Standards/regulations | EN 61000-4-2 |
Contact discharge | 8 kV (Test Level 4) |
Discharge in air | 15 kV (Test Level 4) |
Comments | Criterion A |
Electromagnetic HF field
Standards/regulations | EN 61000-4-3 |
Frequency Range | 80 MHz ... 1 GHz |
Test field strength | 20 V/m (Test Level 3) |
Frequency Range | 1 GHz ... 2 GHz |
Test field strength | 10 V/m (Test Level 3) |
Frequency Range | 2 GHz ... 3 GHz |
Test field strength | 10 V/m (Test Level 3) |
Comments | Criterion A |
Fast transients (burst)
Standards/regulations | EN 61000-4-4 |
Input | 4 kV (Test Level 4 - asymmetrical) |
Output | 2 kV (Test Level 3 - asymmetrical) |
Signal | 2 kV (Test Level 4 - asymmetrical) |
Comments | Criterion A |
Surge voltage load (surge)
Standards/regulations | EN 61000-4-5 |
Input | 1 kV (Test Level 2 - symmetrical) |
Input | 2 kV (Test Level 3 - asymmetrical) |
Output | 0.5 kV (Test Level 1 - symmetrical) |
Output | 0.5 kV (Test Level 1 - asymmetrical) |
Signal | 1 kV (Test Level 2 - asymmetrical) |
Comments | Criterion B |
Conducted interference
Standards/regulations | EN 61000-4-6 |
I/O/S | asymmetrical |
Frequency Range | 0.15 MHz ... 80 MHz |
Comments | Criterion A |
Voltage | 10 V (Test Level 3) |
Emitted interference
Standards/regulations | EN 61000-6-3 |
Radio interference voltage in acc. with EN 55011 | EN 55011 (EN 55022) Class B, area of application: Industry and residential |
Emitted radio interference in acc. with EN 55011 | EN 55011 (EN 55022) Class B, area of application: Industry and residential |
Criteria
Criterion A | Normal operating behavior within the specified limits. |
Criterion B | Temporary impairment to operational behavior that is corrected by the device itself. |
Why Proax for Phoenix Contact 2866718?
Proax is an authorized distributor of Phoenix Contact 2866718 and one of Phoenix Contact's largest distributors in North America. Our highly skilled in-house technical team is ready to assist with any technical needs.
Have a question in mind? to help you get the right product as quickly as possible for your project. We're always here to help!
Short Lead Time
Highly Trained Staff
Live Chat
Technical Support
Local Inventory
60+ Years Experience
Additional Information
Pack Size | 1 |
Recommended