Official Distributor
SKU
MPN
PTCB E1 24DC/2A NO
Weight
0.044 kg
Series PTCB-E1
PTCB E1 24DC/2A NO - Electronic circuit breaker
1-channel, electronic circuit breaker for protecting loads at 24 V DC against overload and short circuit. Easy potential distribution with components from the CLIPLINE complete terminal block system. With fixed nominal current. For installation on DIN rails.
- Simple application setup due to bridging option to CLIPLINE complete terminal block system
- More space in the control cabinet: narrowest protection on just 6 mm width
- Individual setup for suitable protection, exactly according to your requirements
- Optimum protection for cables and sensors as well as NEC Class 2 circuits by means of an additional internal output fuse
Technical Specifications
General
Note | EN 50121-3-2: Railway applications - Electromagnetic compatibility - Part 3-2: Rolling stock – Apparatus |
Note | Connection for signal line tested in accordance with EN 61000-4-4 with 1 kV; if necessary, customer must provide appropriate protective measures |
Note | Repeated hard short circuits can reduce the melting integral of the integrated backup fuse. |
Product properties
Product family | PTCB |
Type | DIN rail module, one-piece |
Number of Positions | 1 |
No. of channels | 1 |
Insulation characteristics
Protection class | III |
Pollution degree | 2 |
General
Operating Voltage | 18 V DC ... 30 V DC |
Rated voltage | 24 V DC |
Rated current IN | 24 A DC (Total current input) |
Rated current IN | 2 A DC (Rated current output) |
Rated current (pre-adjusted) | 2 A |
Rated surge voltage | 0.5 kV |
Tripping method | E (electronic) |
Feedback resistance | max. 35 V DC |
Required backup fuse | Only required if Imax of the power supply > the short-circuit switching capacity. Integrated failsafe element. |
Short-circuit switching capacity | 300 A |
Dielectric strength | max. 35 V DC (Load circuit) |
Fuse | electronic |
Efficiency | > 99 % |
Closed circuit current I0 | typ. 12 mA |
Power dissipation | typ. 0.3 W (No-load operation) |
Power dissipation | < 0.8 W (Nominal operation) |
Module initialization time | < 0.55 s |
Waiting time after switch off of a channel | 5 s (at overload / short circuit) |
Measuring tolerance I | ± 15 % |
Temperature derating | 21 A (Total current at 60°C) |
Temperature derating | 24 A (Total current at 50°C) |
Temperature derating | 2 A (Channel current at 60°C) |
Temperature derating | 2 A (Channel current at 50°C) |
MTBF (IEC 61709, SN 29500) | 28571428 h (at 25 °C with 21 % load) |
MTBF (IEC 61709, SN 29500) | 14084507 h (at 40°C with 34.25% load) |
MTBF (IEC 61709, SN 29500) | 2053388 h (at 60°C with 100% load) |
Voltage drop | 0.06 V (at 2 A) |
Fail-safe element | 4 A DC |
Load circuit
Shutdown time | ≤ 10 ms (for short circuit > 2.0 x IN) |
Shutdown time | 1 s (1.2 ... 2.0 x IN) |
Undervoltage switch-off | ≤ 17.8 V DC (active) |
Undervoltage switch-off | ≥ 18.8 V DC (inactive) |
Overvoltage switch-off | ≥ 30.5 V DC (active) |
Overvoltage switch-off | ≤ 29.5 V DC (inactive) |
Max. capacitive load | 14000 µF (Depending on the available short-circuit current) |
Indicator/remote signaling
Connection name | Remote indication circuit |
Switching function | N/O contact |
Operating Voltage | 0 V DC ... 30 V DC |
Operating current | 100 mA DC |
Main circuit IN+
Connection Method | Push-in connection |
Stripping length | 8 mm |
Conductor cross section flexible | 0.2 mm² ... 2.5 mm² |
Conductor cross section rigid | 0.2 mm² ... 4 mm² |
Conductor cross section AWG | 24 ... 12 |
Conductor cross section, flexible, with ferrule, with plastic sleeve | 0.2 mm² ... 2.5 mm² |
Conductor cross section flexible, with ferrule without plastic sleeve | 0.2 mm² ... 2.5 mm² |
Main circuit IN-
Connection Method | Push-in connection |
Stripping length | 8 mm |
Conductor cross section flexible | 0.2 mm² ... 2.5 mm² |
Conductor cross section rigid | 0.2 mm² ... 4 mm² |
Conductor cross section AWG | 24 ... 12 |
Conductor cross section, flexible, with ferrule, with plastic sleeve | 0.2 mm² ... 2.5 mm² |
Conductor cross section flexible, with ferrule without plastic sleeve | 0.2 mm² ... 2.5 mm² |
Main circuit OUT
Connection Method | Push-in connection |
Stripping length | 8 mm |
Conductor cross section flexible | 0.2 mm² ... 2.5 mm² |
Conductor cross section rigid | 0.2 mm² ... 4 mm² |
Conductor cross section AWG | 24 ... 12 |
Conductor cross section, flexible, with ferrule, with plastic sleeve | 0.2 mm² ... 2.5 mm² |
Conductor cross section flexible, with ferrule without plastic sleeve | 0.2 mm² ... 2.5 mm² |
Remote indication circuit
Connection Method | Push-in connection |
Stripping length | 10 mm |
Conductor cross section flexible | 0.2 mm² ... 2.5 mm² |
Conductor cross section rigid | 0.2 mm² ... 4 mm² |
Conductor cross section AWG | 24 ... 14 |
Conductor cross section, flexible, with ferrule, with plastic sleeve | 0.2 mm² ... 2.5 mm² |
Conductor cross section flexible, with ferrule without plastic sleeve | 0.2 mm² ... 2.5 mm² |
Signaling
Channel LED off | off (Channel switched off) |
Channel LED yellow | lit (Channel switched on, channel load > 80% ) |
Channel LED yellow | flashing (Programming mode active) |
Channel LED green | lit (Channel switched on) |
Channel LED red | lit (Channel switched off, over- or undervoltage active) |
Channel LED red | ON temporarily (Channel switched off, 5 s cool-down phase, overload or short-circuit release) |
Channel LED red | flashing (Channel switched off, ready to be switched back on, overload or short-circuit release) |
Channel LED red | flashing quickly (Channel switched off, external voltage at the output, possible installation error) |
Dimensions
Width | 6.2 mm |
Height | 105.8 mm |
Depth | 55.6 mm (incl. DIN rail 7.5 mm) |
Material specifications
Color | gray (RAL 7042) |
Material | PBT |
Material | PBT |
Flammability rating according to UL 94 | V-0 |
Ambient conditions
Degree of Protection | IP20 |
Ambient Temperature (Operation) | -30 °C ... 60 °C |
Ambient temperature (storage/transport) | -40 °C ... 70 °C |
Altitude | ≤ 3000 m up to 52 °C (amsl) |
Altitude | ≤ 4000 m up to 46 °C (amsl) |
Humidity test | 96 h, 95 % RH, 40 °C |
Shock (operation) | 30g (IEC 60068-2-27, Test Ea) |
Vibration (Operation) | 10 Hz ... 59.6 Hz (Amplitude ±0.35 mm; in accordance with IEC 60068-2-6, Test Fc) |
Vibration (Operation) | 59.6 Hz … 150 Hz (Acceleration 5g; in accordance with IEC 60068-2-6, Test Fc) |
Vibration (Operation) | 5 Hz … 100 Hz (Resonance search 4g; resonance frequency 4g; 90 min in accordance with DNV GL Class B) |
UL approval
Identification | UL/C-UL Listed UL 508 |
Identification | UL Recognized UL 2367 |
Identification | NEC Class 2 according to UL 1310 |
Identification | UL/C-UL Listed ANSI/UL 121201 Class I, Division 2, Groups A, B, C, D; T4 (Hazardous Location) |
Shipbuilding approval
Identification | DNV GL |
Corrosive gas test
Identification | ISA S71.04.2013 G3 Harsh Group A |
DNV GL data
Temperature | D |
Humidity | B |
Vibration | B |
EMC | B |
Enclosure | A |
Standards and Regulations
Standards/specifications | EN 61000-6-2 |
Note | EMC – Immunity for industrial areas |
Standards/specifications | EN 61000-6-3 |
Note | EMC – Emission for residential, business and commercial properties and small operations |
Standards/specifications | EN 60068-2-78 |
Note | Environmental influences – Moisture and heat, constant |
Standards/specifications | EN 50178 |
Note | Equipping power installations with electronic equipment |
Standards/specifications | EN 60068-2-6 |
Note | Environmental influences – Vibrations (sinusoidal) |
Standards/specifications | EN 60068-2-27 |
Note | Environmental influences – Shocks |
Standards/specifications | EN 60068-2-30 |
Note | Environmental influences – Part 2–30: Tests – Test Db: Damp heat, cyclical |
Standards/specifications | EN 61373 |
Note | Railway applications - Rolling stock equipment - Shock and vibration tests |
Standards/specifications | EN 45545-2 |
Note | Railway applications - Fire protection on railway vehicles - Part 2: Requirements for fire behavior of materials and components |
Mounting
Mounting Type | DIN rail: 35 mm |
Accessories
Why Proax for Phoenix Contact 2909903?
Proax is an authorized distributor of Phoenix Contact 2909903 and one of Phoenix Contact's largest distributors in North America. Our highly skilled in-house technical team is ready to assist with any technical needs.
Have a question in mind? to help you get the right product as quickly as possible for your project. We're always here to help!
Short Lead Time
Highly Trained Staff
Live Chat
Technical Support
Local Inventory
60+ Years Experience
Additional Information
Pack Size | 1 |
Recommended