Official Distributor
SKU
MPN
TTC-6P-T3-24DC-PT-I
Weight
0.049 kg
Series TTC
TTC-6P-T3-24DC-PT-I - Type 3 surge protection device
Type 3 surge protection, consisting of protective plug and base element, with integrated status indicator for 24 V DC power supplies
- Space-saving and cost-saving with a narrow overall width of just 6 mm
- Continuous monitoring of protective devices, plus mechanical status indicator with optional remote signaling
- Finding the right product for all possible requirements in MCR applications is easy, thanks to the complete range of products with customized features
- Easy testing and documentation with CHECKMASTER 2 with pluggable protective modules
- The signal is not influenced during maintenance work, thanks to the impedance-neutral insertion and removal of protective plugs
Technical Specifications
General
Note | CBM: |
Note | 2905743 CBM E4 24DC/0.5-10A NO-R |
Note | 2905744 CBM E8 24DC/0.5-10A NO-R |
Note | CBMC: |
Note | 2906032 CBMC E4 24DC/1-10A NO |
Note | 2908716 CBMC E4 24DC/1-10A NO-C |
Note | 2910411 CBMC E4 24DC/1-10A IOL |
Note | PTCB: |
Note | 2908262 PTCB E1 24DC/1-8A NO |
Note | CB E1: |
Note | 2800907 CB E1 24DC/10A NO P |
Note | 2800914 CB E1 24DC/10A S-R P |
Note | 2800928 CB E1 24DC/10A S-C P |
Note | 2905805 CB E1 24DC/10A SI-R P |
Note | 2905812 CB E1 24DC/10A SI-C P |
Product properties
Product family | TERMITRAB complete |
IEC power supply system | DC |
Type | DIN rail module, two-section, divisible |
Number of Positions | 2 |
Surge protection fault message | optical |
Insulation characteristics
Overvoltage category | III |
Pollution degree | 2 |
IEC test classification | III |
IEC test classification | T3 |
EN type | T3 |
Number of Ports | One |
Connection data
Connection Method | Push-in connection |
Conductor cross section flexible | 0.2 mm² ... 2.5 mm² |
Conductor cross section rigid | 0.2 mm² ... 4 mm² |
Conductor cross section AWG | 24 ... 12 |
Dimensions
Width | 6.2 mm +0.1 mm |
Height | 105.8 mm |
Depth | 100 mm (incl. DIN rail 7.5 mm) |
Material specifications
Color (Base element) | gray (RAL 7042) |
Color (Male connector) | light grey (RAL 7035) |
Flammability rating according to UL 94 | V-0 |
CTI value of material | 600 |
Insulating material | PBT |
Housing Material | PBT |
Power supplies
Direction of action | 1L-N & N-PE |
Nominal voltage UN | 24 V DC |
Maximum continuous voltage UC | 30 V DC |
Rated load current IL | 6 A (30 °C) |
Residual current IPE | ≤ 5 µA |
Nominal discharge current In (8/20) µs | 1 kA |
Combination wave UOC | 2 kV (2 Ω) |
Combination wave UOC | 2 kV (2 Ω) |
Voltage protection level Up (DC+) - (DC-) | ≤ 0.09 kV (Uoc= 2 kV) |
Voltage protection level Up (DC+) - (DC-) | ≤ 0.2 kV (Uoc= 6 kV) |
Voltage protection level Up (DC+/DC-) - PE | ≤ 0.7 kV |
Short-circuit current rating ISCCR | 60 A DC (without additional backup fuse) |
Short-circuit current rating ISCCR | 220 A DC |
Max. backup fuse with branch wiring | 6 A (gG) |
Max. backup fuse with branch wiring | 10 A (see the note: CBM, CBMC, PTCB, CB E1) |
Ambient conditions
Degree of Protection | IP20 |
Ambient Temperature (Operation) | -40 °C ... 80 °C |
Ambient temperature (storage/transport) | -40 °C ... 80 °C |
Altitude | ≤ 6000 m (amsl) |
Permissible humidity (operation) | 5 % ... 95 % |
Shock (operation) | 30g (Half-sine / 11 ms / 3x ±X, ±Y, ±Z) |
Vibration (Operation) | 5g (10 ... 150 Hz/20 cycles/axis/X, Y, Z) |
Conformity/Approvals
UL, USA / Canada | Class I, Div. 2, Groups A, B, C, D T4A |
Standards and Regulations
Standards/specifications | IEC 61643-11 |
Note | 2011 |
EN 61643-11
Standards/specifications | EN 61643-11 |
Note | 2012 |
Mounting
Mounting Type | DIN rail: TH 35 - 7.5 mm |
Accessories
Why Proax for Phoenix Contact 1027586?
Proax is an authorized distributor of Phoenix Contact 1027586 and one of Phoenix Contact's largest distributors in North America. Our highly skilled in-house technical team is ready to assist with any technical needs.
Have a question in mind? to help you get the right product as quickly as possible for your project. We're always here to help!
Short Lead Time
Highly Trained Staff
Live Chat
Technical Support
Local Inventory
60+ Years Experience
Additional Information
Pack Size | 1 |
Recommended
- Parafoudre basse tension avec indicateur d'état intégré et sectionnement par couteau pour un circuit de signalisation à 3 fils à sécurité intrinsèque, avec potentiel de référence commun. Pour applications HF. Mise à la terre indirecte par éclateur à gaz, compatible HART. Adapté à l'utilisation dans un système de bus de terrain (par ex. PROFIBUS PA) selon le concept FISCO, APL ready. Utilisable dans des circuits sécurisés jusqu'à SIL 3.