Proax

Currency
0 Items
proax logo
Cart
Phoenix ContactOfficial Distributor

By Phoenix Contact

SKU
MPN
AXL E PB IOL8 DI4 M12 6M
Weight
0.71 kg

AXL E PB IOL8 DI4 M12 6M - Distributed I/O device

Axioline E, PROFIBUS DP, M12 connector, IO-Link ports Class A: 4, connection method: M12 connector, connection technology: 3-conductor, IO-Link ports Class B: 4, connection method: M12 connector, connection technology: 3-conductor, Digital inputs at pin 2 for class A ports: 4, 24 V DC, connection technology: 3-conductor, Metal housing, degree of protection: IP65/IP67

  • Connection to PROFIBUS DP using M12 connectors (B-coded)
  • Baud rate of up to 12 Mbaud (automatic baud rate detection)
  • Connection of four IO-Link devices with additional digital input
  • Connection of four IO-Link actuators with additional power supply
  • Connection of IO-Link ports using M12connectors (A-coded, 5-pos.)
  • IO-Link specification V1.1.2
  • Diagnostic and status indicators
  • Short-circuit and overload protection of the sensor supply
  • IP65/IP67 degree of protection
Technical Specifications

Dimensions

Width60 mm
Height185 mm
Depth38 mm
Drill hole spacing198.5 mm
Note on dimensionsThe height is 194.5 mm including the mounting panel. With fixing clips pulled out, the height is 212 mm. The depth is 38 mm including the mounting panel (30.5 mm without the mounting panel).

Material specifications

Housing MaterialZinc die-cast

PROFIBUS DP

Number of interfaces2
No. of channels2
Connection MethodM12 connector
Note on the connection methodB-coded
Number of Positions5
Transmission Speed9.6 kbps ... 12 Mbps (Automatic baud rate detection)
Transmission physicsPROFIBUS-DP-compliant copper cable
Address area assignment1 ... 126, adjustable
Equipment typePROFIBUS slave
System-specific protocolsPROFIBUS protocols DP V1

Module

ID code (hex)0E57
Input address areamin. 2 Byte
Input address areamax. 162 Byte (Dependent on configuration)
Output address areamin. 2 Byte
Output address areamax. 162 Byte (Dependent on configuration)

Digital:

Input nameDigital inputs at pin 2 for class A ports
Description of the inputIEC 61131-2 type 1
Number of Inputs4
Connection MethodM12 connector, X01 ... X04 have double occupancy
Connection technology3-conductor
Input voltage range "0" signal-0.3 V DC ... 5 V DC
Input voltage range "1" signal15 V DC ... 30 V DC
Nominal input voltage UIN24 V DC
Nominal input current at UINtyp. 3 mA
Sensor current per channelmax. 200 mA (from L+/L-)
Total sensor currentmax. 1.6 A (from L+/L-)
Input Frequency0.5 kHz
Input filter time< 1000 µs
Protective circuitOverload protection, short-circuit protection of sensor supply

Digital

Description of the inputIO-Link ports in digital input (DI) mode
Number of Inputsmax. 8 (EN 61131-2 type 1)
Connection MethodM12 connector, X01 ... X04 have double occupancy
Connection technology3-conductor
Nominal input voltage UIN24 V DC
Input voltage range "0" signal-0.3 V DC ... 5 V DC
Input voltage range "1" signal15 V DC ... 30 V DC
Nominal input currenttyp. 3 mA
Sensor current per channelmax. 200 mA (from L+/L-)
Total sensor currentmax. 1.6 A (from L+/L-)
Input filter time< 1000 µs
Input Frequency0.5 kHz
Protective circuitOverload protection; yes
Protective circuitShort-circuit protection for the sensor supply; yes

IO-Link

Number of Ports4
Connection MethodM12 connector
Connection technology3-conductor
Port TypeClass A
Cycle Timemin. 2 ms (MasterCycleTime: PDInput* + PDOutput* + OnReqData* < = 17 Bytes, COM3; * see "IO-Link Interface and System Specification V1.1.2")
Number of Ports4
Connection MethodM12 connector
Connection technology3-conductor
Port TypeClass B
Cycle Timemin. 2 ms (MasterCycleTime: PDInput* + PDOutput* + OnReqData* < = 17 Bytes, COM3; * see "IO-Link Interface and System Specification V1.1.2")

Digital

Output descriptionIO-Link ports in digital output (DO) mode
Connection MethodM12 connector, X01 ... X04 have double occupancy
Connection technology3-conductor
Number of Outputsmax. 8
Nominal Output Voltage24 V DC
Maximum Output Current per channel150 mA
Maximum Output Current per module1.2 A
Nominal load, ohmic3.6 W (160 Ω, at nominal load)
Nominal load, inductive3.6 VA (0.8 H, 160 Ω, at nominal load)
Signal delaymax. 150 µs (when switched on)
Signal delaymax. 200 µs (when switched off)
Switching rate1 per second, maximum (at nominal inductive load)
Switching rate5500 per second, maximum (at nominal ohmic load)
Limitation of the voltage induced on circuit interruption-15 V DC
Output voltage when switched offmax. 1 V
Output current when switched offmax. 300 µA
Protective circuitOverload protection; yes
Protective circuitShort-circuit protection; yes
Behavior with overloadShutdown with automatic restart

Product properties

Product familyAxioline E
TypeBlock design
Special PropertiesMetal housing

Potentials

Voltage supply US24 V DC
Power supply at USmax. 4 A
Current consumption from UStyp. 8 mA
Current consumption from USmax. 1.2 A

Supply: IO-Link

Nominal voltage for I/O supply24 V DC
Nominal current for every IO-Link portmax. 150 mA (at C/Q (pin 4), maximum of 1.6 A over all 8 IO-Link C/Q and L+ cables)
Nominal current for every IO-Link portmax. 200 mA (at L+/L- (pin 1 and pin 3), during startup, up to 1.6 A for short periods)
Nominal current for every IO-Link portmax. 2 A (at UA (IO-Link B ports, pin 2 and pin 5))
Permissible cable length< 20 m
Protective circuitOverload protection; yes

Supply: Module electronics and sensors

DesignationSupply of module electronics and sensors (US)
Connection MethodM12 connector (T-coded)
Number of Positions4
Supply Voltage24 V DC
Supply Voltage Range19.5 V DC ... 31.2 V DC (including all tolerances, including ripple)
Current consumptiontyp. 170 mA ±15 % (at 24 V DC)
Current consumptionmax. 12 A

Supply: Actuators

DesignationSupply of actuators (UA)
Connection MethodM12 connector (T-coded)
Number of Positions4
Supply Voltage24 V DC
Supply Voltage Range18 V DC ... 31.2 V DC (including all tolerances, including ripple)
Current consumptiontyp. 30 mA ±15 % (at 24 V DC)
Current consumptionmax. 12 A

Electrical isolation/isolation of the voltage ranges

Test voltage: 24 V supply (communications power and sensor supply, IO-Link ports)/bus connection500 V AC, 50 Hz, 1 min.
Test voltage: 24 V supply (communications power and sensor supply, IO-Link ports)/FE500 V AC, 50 Hz, 1 min.
Test voltage: Bus connection / FE500 V AC, 50 Hz, 1 min.
Test voltage: 24 V supply (actuator supply)/24 V supply (communications power and sensor supply, IO-Link ports)500 V AC, 50 Hz, 1 min.
Test voltage: 24 V supply (actuator supply)/bus connection500 V AC, 50 Hz, 1 min.
Test voltage: 24 V supply (actuator supply)/FE500 V AC, 50 Hz, 1 min.

Connection data

Connection MethodM12 connector

Ambient conditions

Ambient Temperature (Operation)-25 °C ... 60 °C
Degree of ProtectionIP65/IP67
Air pressure (operation)70 kPa ... 106 kPa (up to 3000 m above sea level)
Air pressure (storage/transport)70 kPa ... 106 kPa (up to 3000 m above sea level)
Ambient temperature (storage/transport)-25 °C ... 85 °C
Permissible humidity (operation)5 % ... 95 %
Permissible humidity (storage/transport)5 % ... 95 %

Standards and Regulations

Protection classIII (IEC 61140, EN 61140, VDE 0140-1)

Mounting

Mounting TypeWall mounting or DIN rail mounting; both with mounting panel.
Accessories

Why Proax for Phoenix Contact 2701508?

Proax is an authorized distributor of Phoenix Contact 2701508 and one of Phoenix Contact's largest distributors in North America. Our highly skilled in-house technical team is ready to assist with any technical needs.

Have a question in mind? to help you get the right product as quickly as possible for your project. We're always here to help!

Short Lead Time
Highly Trained Staff
Live Chat
Technical Support
Local Inventory
60+ Years Experience
Additional Information

Pack Size1
Recommended

Available for order

Phoenix Contact Availability