AXL E PB DI16 M12 6M - Distributed I/O device

Axioline E, Digital input device, PROFIBUS-Slave, M12 connector, Digital inputs: 16, 24 V DC, connection technology: 4-conductor, Metal housing, degree of protection: IP65/IP67

  • Connection to PROFIBUS DP using M12 connectors (B-coded)
  • Baud rate of up to 12 Mbaud (automatic baud rate detection)
  • Connection of digital sensors using M12connectors (A-coded)
  • Diagnostic and status indicators
  • Short-circuit and overload protection of the sensor supply
  • IP65/IP67 degree of protection
Technical Specifications

Dimensions

Width60 mm
Height185 mm
Depth38 mm
Drill hole spacing198.5 mm
Note on dimensionsThe height is 194.5 mm including the mounting panel. With fixing clips pulled out, the height is 212 mm. The depth is 38 mm including the mounting panel (30.5 mm without the mounting panel).

Material specifications

Housing MaterialZinc die-cast

PROFIBUS-Slave

Number of interfaces2
No. of channels2
Connection MethodM12 connector
Note on the connection methodB-coded
Number of Positions5
Transmission Speed9.6 kbps ... 12 Mbps (Automatic baud rate detection)
Transmission physicsPROFIBUS-DP-compliant copper cable
Address area assignment1 ... 126, adjustable

PROFIBUS DP

Equipment typePROFIBUS slave
System-specific protocolsPROFIBUS protocols DP V1

Module

ID code (hex)0E5C
Input address area16 bit
Output address area0 bit

Digital:

Input nameDigital inputs
Description of the inputEN 61131-2 types 1 and 3
Number of Inputs16
Cable Lengthmax. 30 m (to the sensor)
Connection MethodM12 connector, double occupancy
Connection technology4-conductor
Input voltage range "0" signal0 V ... 5 V DC
Input voltage range "1" signal11 V DC ... 30 V DC
Nominal input voltage UIN24 V DC
Nominal input current at UINtyp. 3 mA
Sensor current per channeltyp. 75 mA (from US)
Total sensor currentmax. 1.2 A (per device)
Input filter time< 1000 µs
Protective circuitOverload protection, short-circuit protection of sensor supply

Product properties

Product familyAxioline E
TypeBlock design
Special PropertiesMetal housing

Potentials

Voltage supply US24 V DC
Power supply at USmax. 4 A
Current consumption from UStyp. 8 mA
Current consumption from USmax. 1.2 A

Supply: Module electronics and sensors

DesignationSupply of module electronics and sensors (US)
Connection MethodM12 connector (T-coded)
Number of Positions4
Supply Voltage24 V DC
Supply Voltage Range18 V DC ... 31.2 V DC (including all tolerances, including ripple)
Current consumptiontyp. 165 mA ±15 % (at 24 V DC)
Current consumptionmax. 12 A

Supply: Actuators

DesignationSupply of actuators (UA) for additional devices
Connection MethodM12 connector (T-coded)
Number of Positions4
Supply Voltage24 V DC
Supply Voltage Range18 V DC ... 31.2 V DC (including all tolerances, including ripple)
Current consumptiontyp. 3 mA ±15 % (at 24 V DC)
Current consumptionmax. 12 A

Electrical isolation/isolation of the voltage ranges

Test voltage: 24 V supply (communications power and sensor supply, digital inputs)/bus connection500 V AC, 50 Hz, 1 min.
Test voltage: 24 V supply (communications power and sensor supply, digital inputs)/FE500 V AC, 50 Hz, 1 min.
Test voltage: Bus connection / FE500 V AC, 50 Hz, 1 min.
Test voltage: 24 V supply (actuator supply)/24 V supply (communications power and sensor supply, digital inputs)500 V AC, 50 Hz, 1 min.
Test voltage: 24 V supply (actuator supply)/bus connection500 V AC, 50 Hz, 1 min.
Test voltage: 24 V supply (actuator supply)/FE500 V AC, 50 Hz, 1 min.

Connection data

Connection MethodM12 connector

Ambient conditions

Ambient Temperature (Operation)-25 °C ... 60 °C
Degree of ProtectionIP65/IP67
Air pressure (operation)70 kPa ... 106 kPa (up to 3000 m above sea level)
Air pressure (storage/transport)70 kPa ... 106 kPa (up to 3000 m above sea level)
Ambient temperature (storage/transport)-25 °C ... 85 °C
Permissible humidity (operation)5 % ... 95 %
Permissible humidity (storage/transport)5 % ... 95 %

Standards and Regulations

Protection classIII (IEC 61140, EN 61140, VDE 0140-1)

Mounting

Mounting TypeWall mounting or DIN rail mounting; both with mounting panel.
Accessories

Why Proax for Phoenix Contact AXL E PB DI16 M12 6M?

Proax is an authorized distributor of Phoenix Contact AXL E PB DI16 M12 6M and one of Phoenix Contact's largest distributors in North America. Our highly skilled in-house technical team is ready to assist with any technical needs.

Have a question in mind? to help you get the right product as quickly as possible for your project. We're always here to help!

Short Lead Time
Highly Trained Staff
Live Chat
Technical Support
Local Inventory
60+ Years Experience
Additional Information

Alternate NamesAXLEPBDI16M126M
Pack Size1
Recommended

Available for order