Official Distributor
SKU
MPN
PSR-MC34-3NO-1DO-24DC-SC
Weight
0.183 kg
This product is Not Cancellable/Not Returnable
Series PSR-MC
PSR-MC34-3NO-1DO-24DC-SC - Safety relays
Safety relay for emergency stop and safety doors up to SIL 3, Cat. 4, PL e, 1 or 2-channel operation, automatic or manual, monitored start, cross-circuit detection, 3 enabling current paths, US = 24 V DC, plug-in screw terminal block
- Up to Cat. 4/PL e in accordance with EN ISO 13849-1, SIL 3 in accordance with EN IEC 62061
- Low housing width of just 12.5 mm
- 2 channel control
- 3 enabling current paths, 1 digital signal output
- Manually monitored and automatic activation in a single device
- Cross-circuit detection
Technical Specifications
Product properties
Product family | PSRmini |
Application | Emergency stop |
Application | Safety door |
Application | Solenoid switch |
Application | Transponder |
Relay type | Electromechanical relay with force-guided contacts in accordance with IEC/EN 61810-3 |
Times
Typical response time | < 175 ms (automatic start) |
Typical response time | < 175 ms (manual, monitored start) |
Typ. starting time with Us | < 250 ms (when controlled via A1) |
Typical release time | < 20 ms (on demand via A1) |
Typical release time | < 20 ms (on demand via the sensor circuit) |
Restart time | < 1 s (Boot time, after switching on the supply voltage) |
Recovery time | < 500 ms (following demand of the safety function) |
Electrical properties
Maximum power dissipation for nominal condition | 6.1 W (US = 26.4 V, IL² = 72 A², PTotal max = 2.5 W + 3.6 W) |
Nominal operating mode | 100% operating factor |
Air clearances and creepage distances between the power circuits
Rated Insulation Voltage | 250 V AC |
Rated Insulation Voltage | 250 V AC |
Rated surge voltage/insulation | See section “Insulation coordination” |
Supply
Designation | A1/A2 |
Rated control circuit supply voltage US | 20.4 V DC ... 26.4 V DC |
Rated control circuit supply voltage US | 24 V DC -15 % / +10 % |
Rated control supply current IS | typ. 84 mA (at US) |
Power consumption at US | typ. 2 W |
Inrush Current | typ. 5 A (Δt = 200 µs at Us) |
Filter time | 1 ms (in the event of voltage dips at Us) |
Protective circuit | Serial protection against polarity reversal; Suppressor diode |
Digital: Sensor circuit (S12, S22)
Description of the input | safety-related sensor inputs |
Description of the input | NPN (S12), NPN/PNP (S22) |
Number of Inputs | 2 |
Input voltage range "0" signal | < 5 V (S12) |
Input voltage range "0" signal | Input S22 can interpret low-resistance outputs of a PLC as a continuous HIGH signal. |
Input voltage range "1" signal | 20.4 V ... 26.4 V |
Input current range "0" signal | < 2 mA (S12) |
Input current range "0" signal | 0 mA ... 2 mA (S22) |
Inrush Current | < 20 mA (Typically with US at S12) |
Inrush Current | < 5 mA (typically with US at S22/24 V) |
Inrush Current | > -15 mA (typically with US at S22/0 V) |
Filter time | max. 1.5 ms (at S12, S22; test pulse width) |
Filter time | min. 7.5 ms (at S12, S22; test pulse rate) |
Concurrence | ∞ |
Max. permissible overall conductor resistance | 150 Ω |
Protective circuit | Suppressor diode |
Current consumption | < 5 mA (Typically with US at S12) |
Current consumption | < 5 mA (typically with US at S22/24 V) |
Current consumption | > -5 mA (typically with US at S22/0 V) |
Digital: Start circuit (S34)
Description of the input | non-safety-related |
Description of the input | NPN/PNP |
Number of Inputs | 1 |
Input voltage range "1" signal | 20.4 V DC ... 26.4 V DC |
Inrush Current | max. 200 mA (typically with US) |
Max. permissible overall conductor resistance | 150 Ω |
Protective circuit | Suppressor diode |
Current consumption | < 10 mA (at S34/24 V) |
Current consumption | > -5 mA (at S34/0 V) |
Relay: Enabling current paths (13/14, 23/24/34)
Output description | safety-related N/O contacts |
Number of Outputs | 3 (undelayed) |
Contact switching type | 3 enabling current paths |
Contact Material | AgSnO2 |
Switching voltage | min. 12 V |
Switching voltage | max. 250 V AC/DC (Observe the load curve) |
Switching capacity | min. 60 mW |
Inrush Current | min. 3 mA |
Inrush Current | max. 6 A |
Switching capacity in accordance with IEC 60947-5-1 | 5 A (AC15) |
Switching capacity in accordance with IEC 60947-5-1 | 4 A (DC13) |
Limiting Continuous Current | 6 A (For 13/14) |
Limiting Continuous Current | 6 A (For 23/24/34; since the 23/24/34 contact path only has one input path, only a total current of 6 A is permitted here) |
Sq. Total current | 72 A2 (observe derating) |
Switching frequency | 0.5 Hz |
Mechanical service life | 10x 106 cycles |
Output fuse | 6 A gL/gG |
Output fuse | 4 A gL/gG (for low-demand applications) |
Signal: M1
Output description | non-safety-related |
Number of Outputs | 1 (digital, PNP) |
Voltage | 22 V DC (Us - 2 V) |
Current | max. 100 mA |
Maximum Inrush Current | 500 mA (Δt = 1 ms at Us) |
Switching frequency | 0.5 Hz (Resistive, inductive, capacitive) |
Protective circuit | Suppressor diode |
Short-circuit protection | no |
Connection technology
pluggable | yes |
Conductor connection
Connection Method | Screw connection |
Conductor cross section rigid | 0.2 mm² ... 2.5 mm² |
Conductor cross section flexible | 0.2 mm² ... 2.5 mm² |
Conductor cross-section AWG | 24 ... 12 |
Stripping length | 7 mm |
Screw thread | M3 |
Tightening torque | 0.5 Nm ... 0.6 Nm |
Signaling
Status display | 3 x green LED |
Operating voltage display | 1 x green LED |
Dimensions
Width | 12.5 mm |
Height | 112.2 mm |
Depth | 114.5 mm |
Material specifications
Color (Housing) | yellow (RAL 1018) |
Housing Material | Polyamide |
Safety data
Stop category | 0 |
Safety data: EN ISO 13849
Category | 4 |
Performance level (PL) | e (4 A DC13; 5 A AC15; 8760 switching cycles/year) |
Safety data: IEC 61508 - High demand
Safety Integrity Level (SIL) | 3 |
Safety data: IEC 61508 - Low demand
Safety Integrity Level (SIL) | 3 |
Safety data: EN IEC 62061
Safety Integrity Level (SIL) | 3 |
Ambient conditions
Degree of Protection | IP20 |
Min. degree of protection of inst. location | IP54 |
Ambient Temperature (Operation) | -40 °C ... 55 °C (observe derating) |
Ambient temperature (storage/transport) | -40 °C ... 85 °C |
Maximum altitude | ≤ 2000 m (Above sea level) |
Max. permissible humidity (storage/transport) | 75 % (on average, 85% infrequently, non-condensing) |
Max. permissible relative humidity (operation) | 75 % (on average, 85% infrequently, non-condensing) |
Shock | 15g |
Vibration (Operation) | 10 Hz ... 150 Hz, 2g |
CE
Identification | CE-compliant |
Air clearances and creepage distances between the power circuits
Standards/regulations | EN 60947-1 |
Mounting
Mounting Type | DIN rail mounting |
Assembly instructions | See derating curve |
Mounting Position | vertical or horizontal |
Why Proax for Phoenix Contact 2700540?
Proax is an authorized distributor of Phoenix Contact 2700540 and one of Phoenix Contact's largest distributors in North America. Our highly skilled in-house technical team is ready to assist with any technical needs.
Have a question in mind? to help you get the right product as quickly as possible for your project. We're always here to help!
Short Lead Time
Highly Trained Staff
Live Chat
Technical Support
Local Inventory
60+ Years Experience
Additional Information
Pack Size | 1 |
Recommended