PSR-MC37-3NO-1NC-24DC-SP - Safety relays

Safety relay for emergency switching off and safety doors as well as for elevator applications up to SIL 3, Cat. 4, PL e, 1 or 2-channel operation, automatic or manual start, cross-circuit detection, 3 enabling current paths, US = 24 V DC, pluggable Push-in terminal block

  • Low housing width of only 22.5mm
  • 3 enabling current paths, 1 signaling current path, 1 digital signal output
  • Cross-circuit detection
  • Automatic and manual activation
  • Up to Cat. 4/PL e in accordance with EN ISO 13849-1, SIL 3 in accordance with EN IEC 62061
  • Suitable for elevator applications in accordance with EN 81-20
Technical Specifications

Product properties

Product familyPSRmini
ApplicationEmergency stop
ApplicationSafety door
ApplicationSolenoid switch
ApplicationTransponder
Relay typeElectromechanical relay with force-guided contacts in accordance with IEC/EN 61810-3

Times

Typical response time< 100 ms (automatic start)
Typ. starting time with Us< 100 ms (when controlled via A1)
Typical release time< 20 ms (when controlled via A1 or S12)
Restart time< 1 s (Boot time)
Recovery time< 500 ms

Electrical properties

Maximum power dissipation for nominal condition16.65 W (at US = 30 V, IL² = 72 A²)
Nominal operating mode100% operating factor

Air clearances and creepage distances between the power circuits

Rated Insulation Voltage250 V AC
Rated Insulation Voltage250 V AC
Rated surge voltage/insulationBasic insulation 4 kV between all current paths
Rated surge voltage/insulationBasic insulation 4 kV between all current paths and housing

Supply

DesignationA1/A2
Rated control circuit supply voltage US19.2 V DC ... 30 V DC
Rated control circuit supply voltage US24 V DC -20 % / +25 %
Rated control supply current IStyp. 70 mA
Power consumption at UStyp. 1.68 W
Inrush Current2 A (Δt = 300 µs at Us)
Protective circuitSurge protection; Suppressor diode
Protective circuitProtection against polarity reversal for rated control circuit supply voltage

Digital: Sensor circuit (S12, S22)

Description of the inputsafety-related sensor inputs
Input voltage range "0" signal0 V DC ... 5 V DC (for safe Off; at S12 and S22)
Input current range "0" signal0 mA ... 2 mA (for safe Off; at S12 and S22)
Inrush Current< 5 mA (Δt = 500 µs, for Us/Ix at S12)
Inrush Current> -5 mA (Δt = 500 µs, for Us/Ix at S22)
Filter timemax. 3 ms (at S12, S22; test pulse width; blanking pulses/dark test)
Filter time1 s (at S12, S22; test pulse rate; blanking pulses/dark test)
Filter timeWhere test pulse width ≤ 1 ms: test pulse rate = 5 x test pulse width
Filter timemax. 1 ms (at S12, S22; test pulse width; switch-on pulses/light test)
Filter time100 ms (at S12, S22; test pulse rate; switch-on pulses/light test)
Filter timeUnless switch-on pulses/light tests are safety-related, they should be disabled.
Max. permissible overall conductor resistance150 Ω
Current consumption< 4 mA (with Us/Ix to S12/S22)

Digital: Start circuit (S35)

Description of the inputnon-safety-related
Number of Inputs1
Input voltage range "1" signal19.2 V DC ... 30 V DC
Inrush Current< 10 mA (Δt = 500 µs)
Max. permissible overall conductor resistance150 Ω
Protective circuitSuppressor diode
Current consumption< 0.5 mA

Relay: Enabling current path (13/14, 23/24, 33/34)

Output descriptionsafety-related N/O contacts
Number of Outputs3 (undelayed)
Contact switching type3 enabling current paths
Contact MaterialAgSnO2
Switching voltagemin. 5 V AC/DC
Switching voltagemax. 250 V AC/DC (Observe the load curve)
Switching capacitymin. 50 mW
Inrush Currentmin. 10 mA
Inrush Currentmax. 6 A
Switching capacity in accordance with IEC 60947-5-15 A (24 V (DC13))
Switching capacity in accordance with IEC 60947-5-15 A (250 V (AC15))
Limiting Continuous Current6 A (observe derating)
Sq. Total current72 A2 (observe derating)
Switching frequency0.5 Hz
Mechanical service life10x 106 cycles
Interrupting rating (ohmic load) max.1500 VA (250 V AC, τ = 0 ms)
Interrupting rating (ohmic load) max.For additional values, see load curve
Maximum interrupting rating (inductive load)48 W (24 V DC, τ = 40 ms)
Maximum interrupting rating (inductive load)40 W (48 V DC, τ = 40 ms)
Maximum interrupting rating (inductive load)36 W (60 V DC, τ = 40 ms)
Maximum interrupting rating (inductive load)35 W (110 V DC, τ = 40 ms)
Maximum interrupting rating (inductive load)33 W (220 V DC, τ = 40 ms)
Maximum interrupting rating (inductive load)1500 VA (250 V AC, τ = 40 ms)
Output fuse6 A gL/gG (N/O contact)

Relay: Signaling current path (41/42)

Output descriptionnon-safety-related N/C contact
Number of Outputs1 (undelayed)
Contact switching type1 signaling current path
Contact MaterialAgSnO2
Switching voltagemin. 5 V AC/DC
Switching voltagemax. 250 V AC/DC
Switching capacitymin. 50 mW
Inrush Currentmin. 10 mA
Inrush Currentmax. 6 A (Δt = 100 ms)
Limiting Continuous Current1 A
Sq. Total current1 A2
Switching frequency0.5 Hz
Mechanical service life10x 106 cycles
Output fuse1 A gL/gG

Signal: Y32

Output descriptionnon-safety-related
Number of Outputs1 (digital)
Voltage23 V DC (Us - 1 V)
Currentmax. 100 mA
Maximum Inrush Current1 A (Δt = 5 ms at Us)
Short-circuit protectionYes

Connection technology

pluggableyes

Conductor connection

Connection MethodPush-in connection
Conductor cross section rigid0.2 mm² ... 1.5 mm²
Conductor cross section flexible0.2 mm² ... 1.5 mm²
Conductor cross section, flexible, with ferrule, with plastic sleeve0.25 mm² ... 1.5 mm² (only together with CRIMPFOX 6)
Conductor cross section flexible, with ferrule without plastic sleeve0.25 mm² ... 1.5 mm² (only together with CRIMPFOX 6)
Conductor cross-section AWG24 ... 16
Stripping length8 mm

Signaling

Status display3 x green LED
Operating voltage display1 x green LED

Dimensions

Width22.5 mm
Height117.4 mm
Depth114.5 mm

Material specifications

Color (Housing)yellow (RAL 1018)
Housing MaterialPolyamide

Safety data

Stop category0

Safety data: EN ISO 13849

Category4
Performance level (PL)e (5 A DC13; 5 A AC15; 8760 switching cycles/year)

Safety data: IEC 61508 - High demand

Safety Integrity Level (SIL)3

Safety data: IEC 61508 - Low demand

Safety Integrity Level (SIL)3

Safety data: EN IEC 62061

Safety Integrity Level (SIL)3

Ambient conditions

Degree of ProtectionIP20
Min. degree of protection of inst. locationIP54
Ambient Temperature (Operation)-40 °C ... 60 °C (observe derating)
Ambient temperature (storage/transport)-40 °C ... 85 °C
Maximum altitude≤ 2000 m (Above sea level)
Max. permissible humidity (storage/transport)75 % (on average, 85% infrequently, non-condensing)
Max. permissible relative humidity (operation)75 % (on average, 85% infrequently, non-condensing)
Shock15g for Δt = 11 ms (continuous shock: 10g for Δt = 16 ms)
Vibration (Operation)10 Hz ... 150 Hz, 2g

CE

IdentificationCE-compliant

Air clearances and creepage distances between the power circuits

Standards/regulationsDIN EN 60664-1:2008

Mounting

Mounting TypeDIN rail mounting
Assembly instructionsSee derating curve
Mounting Positionvertical or horizontal

Why Proax for Phoenix Contact PSR-MC37-3NO-1NC-24DC-SP?

Proax is an authorized distributor of Phoenix Contact PSR-MC37-3NO-1NC-24DC-SP and one of Phoenix Contact's largest distributors in North America. Our highly skilled in-house technical team is ready to assist with any technical needs.

Have a question in mind? to help you get the right product as quickly as possible for your project. We're always here to help!

Short Lead Time
Highly Trained Staff
Live Chat
Technical Support
Local Inventory
60+ Years Experience
Additional Information

Alternate NamesPSRMC373NO1NC24DCSP
Pack Size1
Recommended

Available for order