MS132-KB with Push-in Spring terminals is a compact and powerful range for motor protection up to 15 kW (400 V) / 32 A in width of 45 mm, complying with the latest railway rolling stock standards and allowing installation in passengers or driver cabins for trains frequently operating tunnels or undergrounds.
They offer a reliable protection for motors in the event of overload or phase failure. The devices have trip class 10.
This type has also a clear and reliable indication of fault in a separate window in the event of short-circuit tripping. Further features are the build-in disconnect function, temperature compensation, trip-free mechanism and a rotary handle with a clear switch position indication. The manual motor starter is suitable for three- and single-phase applications. The handle is lockable to protect against unauthorized changes. Auxiliary contacts, signaling contacts, undervoltage releases, shunt trips and terminal spacers are available as accessory. These are suitable throughout the MS132-B/MS165-B range.
– designed in accordance to the applicable parts of IEC 60077 standard
– shocks and vibration withstand conforming to IEC 61373 (category 1, class B)
– usable according to European fire and smoke safety standard EN 45545-2
Technical Specifications
Dimensions
Product Net Width | 112 mm |
Product Net Height | 45 mm |
Product Net Depth / Length | 87 mm |
Product Net Weight | 0.316 kg |
Technical
Rated Service Short-Circuit Breaking Capacity (Ics) | (230 V AC) 30 kA |
Rated Service Short-Circuit Breaking Capacity (Ics) | (250 V DC) 3 Poles in Series 10 kA |
Rated Service Short-Circuit Breaking Capacity (Ics) | (400 V AC) 30 kA |
Rated Service Short-Circuit Breaking Capacity (Ics) | (440 V AC) 30 kA |
Rated Service Short-Circuit Breaking Capacity (Ics) | (500 V AC) 10 kA |
Rated Service Short-Circuit Breaking Capacity (Ics) | (690 V AC) 3 kA |
Rated Ultimate Short-Circuit Breaking Capacity (Icu) | (230 V AC) 50 kA |
Rated Ultimate Short-Circuit Breaking Capacity (Icu) | (400 V AC) 50 kA |
Rated Ultimate Short-Circuit Breaking Capacity (Icu) | (440 V AC) 30 kA |
Rated Ultimate Short-Circuit Breaking Capacity (Icu) | (500 V AC) 10 kA |
Rated Ultimate Short-Circuit Breaking Capacity (Icu) | (690 V AC) 3 kA |
Rated Instantaneous Short-Circuit Current Setting (Ii) | 480 A |
Setting range | 25 ... 32 A |
Rated Operational Power AC-3 (Pe) | (400 V) Three Phase 15 kW |
Rated Operational Power AC-3e (Pe) | (400 V) Three Phase 15 kW |
Rated Operational Voltage | Main Circuit 690 V AC |
Rated Operational Voltage | Main Circuit 250 V DC |
Rated Operational Current (Ie) | 32 A |
Rated Operational Current AC-3 (Ie) | 32 A |
Rated Operational Current AC-3e (Ie) | 32 A |
Rated Operational Current DC-5 (Ie) | 32 A |
Rated Frequency (f) | Main Circuit 50 Hz |
Rated Frequency (f) | Main Circuit 60 Hz |
Operating Frequency (fsw) | 0 ... 400 Hz |
Rated Impulse Withstand Voltage (Uimp) | Main Circuit 6 kV |
Rated Insulation Voltage (Ui) | 690 V |
Power Loss | at Rated Operating Conditions per Pole 1.9 ... 3.1 W |
Number of Poles | 3 |
Conventional Free-air Thermal Current (Ith) | Main Circuit 32 A |
Degree of Protection | Housing IP20 |
Degree of Protection | Main Circuit Terminals IP20 |
Pollution degree | 3 |
Electrical Durability | 50000 cycle |
Mechanical Durability | 100000 cycle |
Terminal Type | Push-in Spring Terminals |
Connecting Capacity Main Circuit | Flexible with Ferrule 1/2x 0.5 ... 4 mm² |
Connecting Capacity Main Circuit | Flexible with Insulated Ferrule 1x 0.5 ... 4 mm² |
Connecting Capacity Main Circuit | Flexible with Insulated Ferrule 2x 0.5 ... 2.5 mm² |
Connecting Capacity Main Circuit | Flexible 1/2x 0.75 ... 4 mm² |
Connecting Capacity Main Circuit | Solid 1/2x 1 ... 2.5 mm² |
Connecting Capacity Main Circuit | Stranded 1/2x 1 ... 6 mm² |
Wire Stripping Length | Main Circuit 12 mm |
Mounting Position | 1 ... 6 |
Mounting on DIN Rail | TH35-15 (35 x 15 mm Mounting Rail) acc. to IEC 60715 |
Mounting on DIN Rail | TH35-7.5 (35 x 7.5 mm Mounting Rail) acc. to IEC 60715 |
Minimum Mounting Distance | Electrical Conductive Board, Horizontal - Up to 400 V 0 mm |
Minimum Mounting Distance | Electrical Conductive Board, Horizontal - Up to 690 V 1.5 mm |
Minimum Mounting Distance | Electrical Conductive Board, Vertical 75 mm |
Minimum Mounting Distance | Other Device Same Type, Horizontal 0 mm |
Minimum Mounting Distance | Other Device Same Type, Vertical 150 mm |
Actuator Type | Rotary Handle |
Contact Position Indication | ON / OFF / TRIP |
Standards | IEC 60077-1 (applicable parts) |
Standards | IEC 60077-2 (applicable parts) |
Standards | IEC/EN 60947-1 |
Standards | IEC/EN 60947-2 |
Standards | IEC/EN 60947-4-1 |
Remarks | UL508 Self-Protected Combination Motor Controller (Type E) in combination with terminal spacer TS1-M3-K |
Technical UL/CSA
Short-circuit current rating (SCCR) | Manual Self-Protected Combination Controllers (Type E), (480Y / 277 V AC) 30 kA |
Short-circuit current rating (SCCR) | Any UL Listed Fuses or Circuit-Breakers, Group Installations (480 V AC) 35 kA |
Short-circuit current rating (SCCR) | Any UL Listed Fuses or Circuit-Breakers, Group Installations (600 V AC) 35 kA |
Short-circuit current rating (SCCR) | Any UL Listed Fuses or Circuit-Breakers, Motor Disconnect (480 V AC) 30 kA |
Short-circuit current rating (SCCR) | Any UL Listed Fuses or Circuit-Breakers, Motor Disconnect (600 V AC) 18 kA |
Short-circuit current rating (SCCR) | Any UL Listed Fuses or Circuit-Breakers, Tap Conductor Protection in Group Installations (480Y / 277 V AC) 30 kA |
Short-circuit current rating (SCCR) | Any UL Listed Fuses or Circuit-Breakers, Tap Conductor Protection in Group Installations (600Y / 347 V AC) 18 kA |
Maximum Operating Voltage UL/CSA | Main Circuit 600 V AC |
Horsepower Rating UL/CSA | (200 V AC) Three Phase 7.5 Hp |
Horsepower Rating UL/CSA | (208 V AC) Three Phase 10 Hp |
Horsepower Rating UL/CSA | (220 ... 240 V AC) Three Phase 10 Hp |
Horsepower Rating UL/CSA | (440 ... 480 V AC) Three Phase 20 Hp |
Horsepower Rating UL/CSA | (550 ... 600 V AC) Three Phase 25 Hp |
Full Load Amps Motor Use | (200 V AC) Three Phase 25.3 A |
Full Load Amps Motor Use | (208 V AC) Three Phase 30.8 A |
Full Load Amps Motor Use | (220 ... 240 V AC) Three Phase 28 A |
Full Load Amps Motor Use | (440 ... 480 V AC) Three Phase 27 A |
Full Load Amps Motor Use | (550 ... 600 V AC) Three Phase 27 A |
Locked Rotor Amps | (200 V AC) Three Phase 146 A |
Locked Rotor Amps | (208 V AC) Three Phase 179 A |
Locked Rotor Amps | (220 ... 240 V AC) Three Phase 162 A |
Locked Rotor Amps | (440 ... 480 V AC) Three Phase 145 A |
Locked Rotor Amps | (550 ... 600 V AC) Three Phase 146 A |
General Use Rating UL/CSA | (600 V AC) 32 A |
Connecting Capacity Main Circuit UL/CSA | Stranded 1/2x 18-10 AWG |
Connecting Capacity Main Circuit UL/CSA | Stranded 1x 8 AWG |
Why Proax for ABB MS132-32KB?
Proax is an authorized distributor of ABB MS132-32KB and one of ABB's largest distributors in North America. Our highly skilled in-house technical team is ready to assist with any technical needs.
Have a question in mind? to help you get the right product as quickly as possible for your project. We're always here to help!
Short Lead Time
Highly Trained Staff
Live Chat
Technical Support
Local Inventory
60+ Years Experience
Additional Information
Alternate Names | MS13232KB |
Pack Size | 1 |
Recommended