QUINT-PS-100-240AC/48DC/10 - Power supply unit
DIN rail power supply unit, primary-switched mode, 1-phase, output: 48 V DC / 10 A
Technical Specifications
AC operation
Nominal input voltage range | 100 V AC ... 240 V AC |
Input voltage range | 85 V AC ... 264 V AC |
Input voltage range | 90 V DC ... 350 V DC |
Input Voltage Range AC | 85 V AC ... 264 V AC |
Input voltage range DC | 90 V DC ... 350 V DC |
Voltage type of supply voltage | AC/DC |
Inrush Current | < 15 A (3.2 A2s) |
Inrush current integral (I2t) | 3.2 A2s |
AC frequency range | 45 Hz ... 65 Hz |
Frequency range DC | 0 Hz |
Mains buffering time | > 30 ms (120 V AC) |
Mains buffering time | > 35 ms (230 V AC) |
Current consumption | approx. 4.76 A (120 V AC) |
Current consumption | 2.3 A (230 V AC) |
Nominal Power Consumption | 524 W |
Protective circuit | Transient surge protection; Varistor |
Typical response time | < 1 s |
Input fuse | 12 A (slow-blow, internal) |
Permissible backup fuse | B10 B16 |
Recommended breaker for input protection | 10 A ... 16 A (Characteristics B, C, D, K) |
Discharge current to PE | < 3.5 mA |
Output data
Efficiency | > 90 % |
Nominal Output Voltage | 48 V DC ±1 % |
Setting range of the output voltage (USet) | 30 V DC ... 56 V DC |
Nominal output current (IN) | 10 A (up to 60 °C) |
Output current limit | 13 A (approx. IBOOST, for short-circuit) |
POWER BOOST (IBoost) | 13 A |
Derating | 60 °C (2.5 %/K) |
Feedback voltage resistance | 60 V DC |
Protection against overvoltage at the output (OVP) | ≤ 60 V DC |
Max. capacitive load | unlimited |
Control deviation | < 1 % (change in load, static 10 % ... 90 %) |
Control deviation | < 5 % (change in load, dynamic 10 % ... 90 %) |
Control deviation | < 0.1 % (change in input voltage ±10 %) |
Residual ripple | < 20 mVPP (with nominal values) |
Output Power | 480 W |
Peak switching voltages nominal load | < 50 mVPP |
Maximum no-load power dissipation | < 5 W |
Power loss nominal load max. | < 56 W |
Rise time | < 2 ms (UOUT (10 % ... 90 %)) |
Connection in parallel | yes, for redundancy and increased capacity |
Connection in series | yes |
Signal: DC OK active
Output description | UOUT > 0.9 x UN: High signal |
Maximum Switching Voltage | ≤ 24 V |
Output Voltage | + 24 V DC |
Maximum Inrush Current | ≤ 40 mA |
Continuous load current | ≤ 40 mA |
Signal: DC OK floating
Output description | Relay contact, UOUT > 0.9 x UN: Contact closed |
Maximum Switching Voltage | ≤ 30 V AC/DC |
Maximum Inrush Current | ≤ 1 A |
Continuous load current | ≤ 1 A |
Input
Connection Method | Screw connection |
Conductor cross section, rigid min. | 0.2 mm² |
Conductor cross section, rigid max. | 6 mm² |
Conductor cross section flexible min. | 0.2 mm² |
Conductor cross section flexible max. | 4 mm² |
Conductor cross section AWG min. | 24 |
Conductor cross section AWG max. | 10 |
Stripping length | 7 mm |
Screw thread | M3 |
Tightening torque, min | 0.5 Nm |
Tightening torque max | 0.6 Nm |
Output
Connection Method | Screw connection |
Conductor cross section, rigid min. | 0.5 mm² |
Conductor cross section, rigid max. | 16 mm² |
Conductor cross section flexible min. | 0.5 mm² |
Conductor cross section flexible max. | 10 mm² |
Conductor cross section AWG min. | 20 |
Conductor cross section AWG max. | 6 |
Stripping length | 7 mm |
Screw thread | M4 |
Tightening torque, min | 1.2 Nm |
Tightening torque max | 1.5 Nm |
Signal
Conductor cross section, rigid min. | 0.5 mm² |
Conductor cross section, rigid max. | 16 mm² |
Conductor cross section flexible min. | 0.5 mm² |
Conductor cross section flexible max. | 10 mm² |
Conductor cross section AWG min. | 20 |
Conductor cross section AWG max. | 6 |
Screw thread | M4 |
Tightening torque, min | 1.2 Nm |
Tightening torque max | 1.5 Nm |
Signaling
Types of signaling | LED |
Types of signaling | Active switching output |
Types of signaling | Relay contact |
Signal output: DC OK active
Status display | "DC OK" LED green |
Note on status display | UOUT < 0.9 x UN: LED flashing |
Signal output: DC OK floating
Status display | "DC OK" LED green |
Note on status display | UOUT < 0.9 x UN: LED flashing |
Electrical properties
Insulation voltage input/output | 4 kV AC (type test) |
Insulation voltage input/output | 2 kV AC (routine test) |
Insulation voltage output / PE | 500 V DC (routine test) |
Insulation voltage input / PE | 3.5 kV AC (type test) |
Insulation voltage input / PE | 2 kV AC (routine test) |
Product properties
Product family | QUINT POWER |
MTBF (IEC 61709, SN 29500) | > 500000 h |
Insulation characteristics
Protection class | I (with PE connection) |
Degree of pollution | 2 |
Dimensions
Width | 157 mm |
Height | 130 mm |
Depth | 125 mm |
Alternative assembly
Width | 122 mm |
Height | 130 mm |
Depth | 160 mm |
Mounting
Mounting Type | DIN rail mounting |
Assembly instructions | alignable: horizontally 0 mm, vertically 50 mm |
Mounting Position | horizontal DIN rail NS 35, EN 60715 |
Material specifications
Housing Material | Metal |
Type of housing | AluNox (AlMg1) |
Ambient conditions
Degree of Protection | IP20 |
Ambient Temperature (Operation) | -25 °C ... 70 °C (> 60 °C Derating: 2,5 %/K) |
Ambient temperature (storage/transport) | -40 °C ... 85 °C |
Climatic class | 3K3 (in acc. with EN 60721) |
Max. permissible relative humidity (operation) | 95 % (at 25 °C, non-condensing) |
Shock | 18 ms, 30g, in each space direction (according to IEC 60068-2-27) |
Vibration (Operation) | < 15 Hz, amplitude ±2.5 mm (according to IEC 60068-2-6) |
Vibration (Operation) | 15 Hz ... 150 Hz, 2.3g, 90 min. |
Standards and Regulations
Standard – Electronic equipment for use in electrical power installations and their assembly into electrical power installations | EN 50178/VDE 0160 (PELV) |
Standard – Limitation of mains harmonic currents | EN 61000-3-2 |
Standard - Electrical safety | EN 60950-1/VDE 0805 (SELV) |
Standard - Electrical safety | EN 61558-2-17 |
Standard - Equipment safety | GS (tested safety) |
Standard – Protection against shock currents, basic requirements for protective separation in electrical equipment | EN 50178 |
Standard – Safety extra-low voltage | EN 60950-1 (SELV) |
Standard – Safety extra-low voltage | EN 60204 (PELV) |
Standard - Safe isolation | DIN VDE 0100-410 |
Standard - Safety of transformers | EN 61558-2-17 |
Overvoltage category
EN 62477-1 | III |
Approvals
Shipbuilding approval | DNV GL (EMC A), ABS |
UL approvals | UL/C-UL listed UL 508 |
UL approvals | UL/C-UL Recognized UL 60950-1 |
EMC data
Low Voltage Directive | Conformance with Low Voltage Directive 2014/35/EC |
EMC requirements for noise emission | EN 61000-6-3 |
EMC requirements for noise emission | EN 61000-6-4 |
EMC requirements for noise immunity | EN 61000-6-1 |
EMC requirements for noise immunity | EN 61000-6-2 |
Electromagnetic compatibility | Conformance with EMC Directive 2014/30/EU |
Electrostatic discharge
Standards/regulations | EN 61000-4-2 |
Housing | Level 4 |
Contact discharge | 8 kV |
Discharge in air | 15 kV |
Comments | Criterion B |
Electromagnetic HF field
Standards/regulations | EN 61000-4-3 |
Frequency Range | 80 MHz ... 1 GHz |
Test field strength | 10 V/m |
Comments | Criterion A |
Fast transients (burst)
Standards/regulations | EN 61000-4-4 |
Input | 4 kV (level 4 - asymmetrical: conductor to ground) |
Output | 2 kV (level 3 - asymmetrical: conductor to ground) |
Signal | 1 kV (level 1 - asymmetrical: conductor to ground) |
Comments | Criterion B |
Surge voltage load (surge)
Standards/regulations | EN 61000-4-5 |
Input | 4 kV (inst. class 4 - asymmetrical: conductor to ground) |
Input | 2 kV (inst. class 4 -symmetrical: conductor to conductor) |
Output | 0.5 kV (level 1 - asymmetrical: conductor to ground) |
Output | 0.5 kV (level 1 - symmetrical: conductor to conductor) |
Signal | 1 kV (level 2 - asymmetrical: conductor to ground) |
Comments | Criterion B |
Conducted interference
Standards/regulations | EN 61000-4-6 |
I/O/S | Level 3 - asymmetrical |
Frequency Range | 0.15 MHz ... 80 MHz |
Comments | Criterion A |
Voltage | 10 V |
Voltage dips
Standards/regulations | EN 61000-4-11 |
Emitted interference
Standards/regulations | EN 61000-6-3 |
Radio interference voltage in acc. with EN 55011 | EN 55011 (EN 55022) Class B, area of application: Industry and residential |
Emitted radio interference in acc. with EN 55011 | EN 55011 (EN 55022) Class B, area of application: Industry and residential |
Why Proax for Phoenix Contact QUINT-PS-100-240AC/48DC/10?
Proax is an authorized distributor of Phoenix Contact QUINT-PS-100-240AC/48DC/10 and one of Phoenix Contact's largest distributors in North America. Our highly skilled in-house technical team is ready to assist with any technical needs.
Have a question in mind? to help you get the right product as quickly as possible for your project. We're always here to help!
Short Lead Time
Highly Trained Staff
Live Chat
Technical Support
Local Inventory
60+ Years Experience
Additional Information
Alternate Names | QUINTPS100240AC48DC10 |
Pack Size | 1 |
Recommended