SKU
MPN
QUINT-PS-3X400-500AC/48DC/10
Weight
2.3 kg
Series QUINT-PS
QUINT-PS-3X400-500AC/48DC/10 - Power supply unit
DIN rail power supply unit 48 V DC/10 A, primary-switched, 3-phase.Please use the following item in new systems: 2320827
QUINT-PS
The Phoenix Contact QUINT-PS Series is a line of high-performance power supplies designed to ensure maximum system availability in demanding industrial applications. These power supplies are equipped with advanced features such as Selective Fuse Breaking (SFB) Technology, preventive function monitoring, and configurable settings to meet diverse operational requirements.
Key Features:
SFB Technology: The QUINT-PS Series utilizes SFB Technology to deliver up to six times the nominal current for 12 milliseconds, enabling standard circuit breakers to trip selectively. This ensures that only the faulty circuit is disconnected, while critical system components continue to operate without interruption.
Preventive Function Monitoring: These power supplies continuously monitor critical operating parameters and provide early warning signals before faults occur. This proactive approach allows for timely maintenance and reduces the risk of unexpected system downtime.
Power Boost: The QUINT-PS Series offers a static power reserve, known as POWER BOOST, providing up to 125% of the nominal power continuously. This feature facilitates the reliable startup of heavy loads and simplifies system expansion without the need for additional power supplies.
Configurable Settings: Users can customize signaling thresholds and characteristic curves to match specific application needs, enhancing flexibility and adaptability in various industrial environments.
Technical Specifications
AC operation
Nominal input voltage range | 3x 400 V AC ... 500 V AC |
Input voltage range | 3x 320 V AC ... 575 V AC (for all three phases) |
Input voltage range | 450 V DC ... 800 V DC (for all three phases) |
Input Voltage Range AC | 3x 320 V AC ... 575 V AC (for all three phases) |
Input voltage range DC | 450 V DC ... 800 V DC (for all three phases) |
Voltage type of supply voltage | AC/DC |
Inrush Current | < 10 A |
Inrush current integral (I2t) | 1 A2s |
AC frequency range | 45 Hz ... 65 Hz |
Frequency range DC | 0 Hz |
Mains buffering time | > 25 ms (400 V AC) |
Mains buffering time | > 30 ms (480 V AC) |
Current consumption | approx. 3x 1.2 A (400 V AC) |
Current consumption | 1 A (480 V AC) |
Nominal Power Consumption | 517 W |
Protective circuit | Transient surge protection; Varistor |
Typical response time | < 1 s |
Permissible backup fuse | B6 B10 B16 |
Recommended breaker for input protection | 3x 6 A ... 16 A (Characteristics B, C, D, K) |
Output data
Efficiency | > 90 % (for 230 V AC and nominal values) |
Nominal Output Voltage | 48 V DC ±1 % |
Setting range of the output voltage (USet) | 30 V DC ... 56 V DC (> 48 V DC, constant capacity restricted) |
Nominal output current (IN) | 10 A (-25 °C ... 60 °C) |
POWER BOOST (IBoost) | 13 A (-25 °C ... 40 °C permanent) |
Derating | 60 °C ... 70 °C (2.5 %/K) |
Residual ripple | < 20 mVPP |
Output Power | 480 W |
Peak switching voltages nominal load | < 140 mVPP (20 MHz) |
Maximum no-load power dissipation | 10 W |
Power loss nominal load max. | 45 W |
Connection in parallel | yes, for redundancy and increased capacity |
Connection in series | yes |
Signal: DC OK active
Output description | UOUT > 0.9 x UN: High signal |
Maximum Switching Voltage | ≤ 24 V |
Output Voltage | + 24 V DC |
Maximum Inrush Current | ≤ 20 mA |
Continuous load current | ≤ 20 mA |
Signal: DC OK floating
Output description | Relay contact, UOUT > 0.9 x UN: Contact closed |
Maximum Switching Voltage | ≤ 30 V AC/DC |
Maximum Inrush Current | max. 0.5 A |
Continuous load current | ≤ 1 A |
Input
Connection Method | Screw connection |
Conductor cross section, rigid min. | 0.2 mm² |
Conductor cross section, rigid max. | 2.5 mm² |
Conductor cross section flexible min. | 0.2 mm² |
Conductor cross section flexible max. | 2.5 mm² |
Conductor cross section AWG min. | 24 |
Conductor cross section AWG max. | 10 |
Stripping length | 8 mm |
Screw thread | M3 |
Output
Connection Method | Screw connection |
Conductor cross section, rigid min. | 0.5 mm² |
Conductor cross section, rigid max. | 16 mm² |
Conductor cross section flexible min. | 0.5 mm² |
Conductor cross section flexible max. | 10 mm² |
Conductor cross section AWG min. | 20 |
Conductor cross section AWG max. | 6 |
Stripping length | 10 mm |
Screw thread | M4 |
Signal
Conductor cross section, rigid min. | 0.5 mm² |
Conductor cross section, rigid max. | 16 mm² |
Conductor cross section flexible min. | 0.5 mm² |
Conductor cross section flexible max. | 10 mm² |
Conductor cross section AWG min. | 20 |
Conductor cross section AWG max. | 6 |
Screw thread | M4 |
Signaling
Types of signaling | LED |
Types of signaling | Active switching output |
Types of signaling | Relay contact |
Signal output: DC OK active
Status display | "DC OK" LED green |
Note on status display | UOUT < 0.9 x UN: LED flashing |
Signal output: DC OK floating
Status display | "DC OK" LED green |
Note on status display | UOUT < 0.9 x UN: LED flashing |
Electrical properties
Insulation voltage input/output | 3 kV (type test) |
Insulation voltage input/output | 1.5 kV (routine test) |
Product properties
Product family | QUINT POWER |
MTBF (IEC 61709, SN 29500) | > 500000 h |
Insulation characteristics
Protection class | I (with PE connection) |
Dimensions
Width | 160 mm |
Height | 130 mm |
Depth | 125 mm |
Alternative assembly
Width | 122 mm |
Height | 130 mm |
Depth | 163 mm |
Mounting
Assembly instructions | alignable: horizontally 0 mm, vertically 50 mm |
Mounting Position | horizontal DIN rail NS 35, EN 60715 |
Material specifications
Housing Material | Metal |
Type of housing | AluNox (AlMg1) |
Ambient conditions
Degree of Protection | IP20 |
Ambient Temperature (Operation) | -25 °C ... 70 °C (> 60 °C Derating: 2,5 %/K) |
Ambient temperature (storage/transport) | -40 °C ... 85 °C |
Max. permissible relative humidity (operation) | 95 % (at 25 °C, non-condensing) |
Standards and Regulations
Standard – Limitation of mains harmonic currents | EN 61000-3-2 |
Standard - Electrical safety | EN 62368-1 |
Standard - Equipment safety | GS (tested safety) |
Standard – Protection against shock currents, basic requirements for protective separation in electrical equipment | EN 62368-1 |
Standard – Safety extra-low voltage | EN 62368-1 (SELV) |
Standard – Safety extra-low voltage | EN 60204 (PELV) |
Standard - Safe isolation | DIN VDE 0100-410 |
Approvals
UL approvals | UL/C-UL listed UL 508 |
UL approvals | UL/C-UL Recognized UL 60950-1 |
EMC data
Low Voltage Directive | Conformance with Low Voltage Directive 2014/35/EC |
EMC requirements for noise emission | EN 61000-6-3 |
EMC requirements for noise emission | EN 61000-6-4 |
EMC requirements for noise immunity | EN 61000-6-1 |
EMC requirements for noise immunity | EN 61000-6-2 |
Electromagnetic compatibility | Conformance with EMC Directive 2014/30/EU |
Noise emission | EN 55011 (EN 55022) |
Why Proax for Phoenix Contact 2938219?
Proax is an authorized distributor of Phoenix Contact 2938219 and one of Phoenix Contact's largest distributors in North America. Our highly skilled in-house technical team is ready to assist with any technical needs.
Have a question in mind? to help you get the right product as quickly as possible for your project. We're always here to help!
Short Lead Time
Highly Trained Staff
Live Chat
Technical Support
Local Inventory
60+ Years Experience
Additional Information
Pack Size | 1 |