Proax

Currency
0 Items
proax logo
Cart
Phoenix ContactOfficial Distributor

By Phoenix Contact

SKU
MPN
QUINT-PS-100-240AC/48DC/ 5
Weight
1.467 kg
Series QUINT-PS

QUINT-PS-100-240AC/48DC/ 5 - Power supply unit

DIN rail power supply unit, primary-switched mode, 1-phase, output: 48 V DC / 5 A

Technical Specifications

AC operation

Nominal input voltage range100 V AC ... 240 V AC
Input voltage range85 V AC ... 264 V AC
Input voltage range90 V DC ... 350 V DC
Input Voltage Range AC85 V AC ... 264 V AC
Input voltage range DC90 V DC ... 350 V DC
Voltage type of supply voltageAC/DC
Inrush Current< 15 A (typical)
Inrush current integral (I2t)1.5 A2s
AC frequency range45 Hz ... 65 Hz
Frequency range DC0 Hz
Mains buffering time> 50 ms (120 V AC)
Mains buffering time> 50 ms (230 V AC)
Current consumptionapprox. 2.2 A (120 V AC)
Current consumption1.2 A (230 V AC)
Nominal Power Consumption263 W
Protective circuitTransient surge protection; Varistor
Typical response time< 1 s
Input fuse6.3 A (slow-blow, internal)
Permissible backup fuseB10 B16
Recommended breaker for input protection10 A ... 16 A (Characteristics B, C, D, K)

Output data

Efficiency> 91 %
Nominal Output Voltage48 V DC ±1 %
Setting range of the output voltage (USet)40 V DC ... 56 V DC
Nominal output current (IN)5 A (up to 60 °C)
POWER BOOST (IBoost)7.5 A
Max. capacitive loadunlimited
Residual ripple< 30 mVPP
Output Power240 W
Peak switching voltages nominal load< 50 mVPP (20 MHz)
Maximum no-load power dissipation2 W
Power loss nominal load max.24 W
Connection in parallelyes, for redundancy and increased capacity
Connection in seriesyes

Signal: DC OK active

Output descriptionUOUT > 0.9 x UN: High signal
Maximum Switching Voltage≤ 24 V
Output Voltage+ 24 V DC
Maximum Inrush Current≤ 20 mA
Continuous load current≤ 40 mA

Signal: DC OK floating

Output descriptionRelay contact, UOUT > 0.9 x UN: Contact closed
Maximum Switching Voltage≤ 30 V AC/DC
Maximum Inrush Current≤ 1 A
Continuous load current≤ 1 A

Input

Connection MethodPluggable screw connection
Conductor cross section, rigid min.0.2 mm²
Conductor cross section, rigid max.2.5 mm²
Conductor cross section flexible min.0.2 mm²
Conductor cross section flexible max.2.5 mm²
Conductor cross section AWG min.24
Conductor cross section AWG max.12
Stripping length7 mm
Screw threadM3

Output

Connection MethodPluggable screw connection
Conductor cross section, rigid min.0.2 mm²
Conductor cross section, rigid max.2.5 mm²
Conductor cross section flexible min.0.2 mm²
Conductor cross section flexible max.2.5 mm²
Conductor cross section AWG min.24
Conductor cross section AWG max.12
Stripping length7 mm
Screw threadM3
Tightening torque, min0.5 Nm
Tightening torque max0.6 Nm

Signal

Conductor cross section, rigid min.0.2 mm²
Conductor cross section, rigid max.2.5 mm²
Conductor cross section flexible min.0.2 mm²
Conductor cross section flexible max.2.5 mm²
Conductor cross section AWG min.24
Conductor cross section AWG max.12
Screw threadM3
Tightening torque, min0.5 Nm
Tightening torque max0.6 Nm

Signaling

Types of signalingLED
Types of signalingActive switching output
Types of signalingRelay contact
Operating voltage displayGreen LED

Signal output: DC OK active

Status display"DC OK" LED green
Note on status displayUOUT < 0.9 x UN: LED flashing

Signal output: DC OK floating

Status display"DC OK" LED green
Note on status displayUOUT < 0.9 x UN: LED flashing

Electrical properties

Insulation voltage input/output4 kV (type test)
Insulation voltage input/output2 kV (routine test)

Product properties

Product familyQUINT POWER
MTBF (IEC 61709, SN 29500)> 500000 h

Insulation characteristics

Protection classI (with PE connection)

Dimensions

Width85 mm
Height130 mm
Depth125 mm

Alternative assembly

Width122 mm
Height130 mm
Depth88 mm

Mounting

Mounting TypeDIN rail mounting
Assembly instructionsalignable: horizontally 0 mm, vertically 50 mm
Mounting Positionhorizontal DIN rail NS 35, EN 60715

Material specifications

Housing MaterialMetal
Type of housingAluNox (AlMg1)

Ambient conditions

Degree of ProtectionIP20
Ambient Temperature (Operation)-25 °C ... 70 °C (> 60 °C Derating: 2,5 %/K)
Ambient temperature (storage/transport)-40 °C ... 85 °C
Max. permissible relative humidity (operation)95 % (at 25 °C, non-condensing)

Standards and Regulations

Standard – Electronic equipment for use in electrical power installations and their assembly into electrical power installationsEN 50178/VDE 0160 (PELV)
Standard – Limitation of mains harmonic currentsEN 61000-3-2
Standard - Electrical safetyEN 60950-1/VDE 0805 (SELV)
Standard - Electrical safetyEN 61558-2-17
Standard - Equipment safetyGS (tested safety)
Standard - Safe isolationDIN VDE 0100-410
Standard - Safety of transformersEN 61558-2-17

Approvals

UL approvalsUL/C-UL Recognized UL 60950-1
UL approvalsUL/C-UL listed UL 508

EMC data

Low Voltage DirectiveConformance with Low Voltage Directive 2014/35/EC
EMC requirements for noise emissionEN 61000-6-3
EMC requirements for noise emissionEN 61000-6-4
EMC requirements for noise immunityEN 61000-6-1
EMC requirements for noise immunityEN 61000-6-2
Electromagnetic compatibilityConformance with EMC Directive 2014/30/EU
Noise emissionEN 55011 (EN 55022)

Why Proax for Phoenix Contact 2866255?

Proax is an authorized distributor of Phoenix Contact 2866255 and one of Phoenix Contact's largest distributors in North America. Our highly skilled in-house technical team is ready to assist with any technical needs.

Have a question in mind? to help you get the right product as quickly as possible for your project. We're always here to help!

Short Lead Time
Highly Trained Staff
Live Chat
Technical Support
Local Inventory
60+ Years Experience
Additional Information

Pack Size1
Recommended

Available for order

Phoenix Contact Availability