Proax

Currency
0 Items
proax logo
Cart
Phoenix ContactOfficial Distributor

By Phoenix Contact

SKU
MPN
2702192
Weight
0.083 kg
Series PSR-MS

PSR-MS21-1NO-1DO-24DC-SC - Safety relays

Safety relay for failsafe controllers up to SILCL 3, Cat. 4, PL e, 1-channel operation, autostart, 1 enabling current path, US = 24 V DC in accordance with IEC 61131-6, fixed screw terminal block

  • Up to Cat. 4/PL e in accordance with EN ISO 13849-1, SIL 3 in accordance with EN IEC 62061
  • Low housing width of just 6.8 mm
  • 1-channel control
  • 1 enabling current path, 1 digital signal output
  • Couples digital output signals from failsafe controllers to I/O devices (valves, etc.) for electrical isolation and power adaptation
  • Automatic activation
Technical Specifications

Product properties

Product familyPSRmini
ApplicationControllers
Relay typeElectromechanical relay with force-guided contacts in accordance with IEC/EN 61810-3

Times

Typical response time< 150 ms (automatic start)
Typ. starting time with Us< 250 ms (when controlled via A1)
Typical release time< 20 ms (when controlled via A1)
Restart time< 1 s
Recovery time< 500 ms

Electrical properties

Maximum power dissipation for nominal condition3.1 W (at US = 30 V, IL² = 36 A²)
Nominal operating mode100% operating factor

Air clearances and creepage distances between the power circuits

Rated Insulation Voltage250 V AC
Rated Insulation Voltage250 V AC
Rated surge voltage/insulationSafe isolation, reinforced insulation 6 kV between input circuit and enabling current path (13/14)Basic insulation 4 kV between all current paths and housing

Supply

Rated control circuit supply voltage US19.2 V DC ... 30 V DC
Rated control circuit supply voltage US24 V DC -20 % / +25 % (at A1)
Rated control supply current IStyp. 35 mA
Power consumption at UStyp. 840 mW
Inrush Current150 mA (Δt = 25 ms at Us)
Filter time2.5 ms (at A1 in the event of voltage dips at Us)
Filter timemax. 3 ms (at A1; test pulse width; blanking pulses/dark test)
Filter time1 s (at A1; test pulse rate; blanking pulses/dark test)
Filter timeWhere test pulse width ≤ 1 ms: test pulse rate = 5 x test pulse width
Filter timemax. 1 ms (at A1; test pulse width; switch-on pulses/light test)
Filter time100 ms (at A1; test pulse rate; switch-on pulses/light test)
Filter timeUnless switch-on pulses/light tests are safety-related, they should be disabled.
Protective circuitSurge protection; Suppressor diode
Protective circuitProtection against polarity reversal for rated control circuit supply voltage

Digital

Inrush Current< 10 mA (with Us/Ix to S35)
Max. permissible overall conductor resistance150 Ω
Voltage at input/start and feedback circuit24 V DC -20 % / +25 %
Current consumption< 2 mA (with Us/Ix to S35)

Relay: Enabling current path

Output descriptionsafety-related N/O contacts
Number of Outputs1 (undelayed)
Contact switching type1 enabling current path
Contact MaterialAgSnO2
Switching voltagemin. 12 V AC/DC
Switching voltagemax. 250 V AC/DC (Observe the load curve)
Switching capacitymin. 60 mW
Inrush Currentmin. 3 mA
Inrush Currentmax. 6 A
Limiting Continuous Current6 A (observe derating)
Sq. Total current36 A2 (observe derating)
Switching frequencymax. 0.5 Hz
Mechanical service life10x 106 cycles
Output fuse6 A gL/gG (N/O contact)
Output fuse4 A gL/gG (for low-demand applications)

Signal

Output descriptionnon-safety-related
Number of Outputs1 (digital, PNP)
Voltagetyp. 21 V DC (Voltage at terminal block “24V” - 3 V)
Currentmax. 100 mA
Maximum Inrush Current500 mA (Δt = 1 ms at Us)
Short-circuit protectionYes

Connection technology

pluggableno

Conductor connection

Connection MethodScrew connection
Conductor cross section rigid0.2 mm² ... 2.5 mm²
Conductor cross section flexible0.2 mm² ... 2.5 mm²
Conductor cross-section AWG26 ... 12
Stripping length12 mm
Screw threadM3
Tightening torque0.5 Nm ... 0.6 Nm

Signaling

Status display2 x green LEDs
Operating voltage display1 x green LED

Dimensions

Width6.8 mm
Height93.1 mm
Depth102.5 mm

Material specifications

Color (Housing)yellow (RAL 1018)
Housing MaterialPBT

Safety data

Stop category0

Safety data: EN ISO 13849

Category4
Performance level (PL)e (4 A DC13; 5 A AC15; 8760 switching cycles/year)

Safety data: IEC 61508 - High demand

Safety Integrity Level (SIL)3 (4 A DC13; 5 A AC15; 8760 switching cycles/year)

Safety data: IEC 61508 - Low demand

Safety Integrity Level (SIL)3

Safety data: EN IEC 62061

Safety Integrity Level (SIL)3 (4 A DC13; 5 A AC15; 8760 switching cycles/year)

Ambient conditions

Degree of ProtectionIP20
Min. degree of protection of inst. locationIP54
Ambient Temperature (Operation)-40 °C ... 60 °C (observe derating)
Ambient temperature (storage/transport)-40 °C ... 85 °C
Maximum altitude≤ 2000 m (Above sea level)
Max. permissible humidity (storage/transport)75 % (on average, 85% infrequently, non-condensing)
Max. permissible relative humidity (operation)75 % (on average, 85% infrequently, non-condensing)
Shock15g
Vibration (Operation)10 Hz ... 150 Hz, 2g

CE

CertificateCE-compliant

Air clearances and creepage distances between the power circuits

Standards/regulationsDIN EN 50178

Mounting

Mounting TypeDIN rail mounting
Assembly instructionsSee derating curve
Mounting Positionvertical or horizontal
Accessories

Why Proax for Phoenix Contact PSR-MS21-1NO-1DO-24DC-SC?

Proax is an authorized distributor of Phoenix Contact PSR-MS21-1NO-1DO-24DC-SC and one of Phoenix Contact's largest distributors in North America. Our highly skilled in-house technical team is ready to assist with any technical needs.

Have a question in mind? to help you get the right product as quickly as possible for your project. We're always here to help!

Short Lead Time
Highly Trained Staff
Live Chat
Technical Support
Local Inventory
60+ Years Experience
Additional Information

Alternate NamesPSRMS211NO1DO24DCSC
Pack Size1
Recommended

Available for order