Proax

Currency
0 Items
proax logo
Cart
Phoenix ContactOfficial Distributor

By Phoenix Contact

SKU
MPN
2702355
Weight
0.15 kg
Series PSR-MM

PSR-MM25-1NO-2DO-24DC-SC - Safety relay module

Safety relay module for sensor-free zero-speed monitoring for 3- and 1-phase motors up to SIL 3, Cat. 3, PL e, 2-channel evaluation of the residual voltage of AC, three-phase, and DC motors, plug-in screw terminal block, width: 12.5 mm

  • Monitoring of 1 and 3-phase AC or DC motors
  • No additional sensors required
  • Adjustable delay time from 0.5 s ... 20 s
  • Adjustable switching threshold from 50 mV... 500 mV
  • 1 enabling current path, 2 digital signal outputs
  • Low housing width of just 12.5 mm
  • Up to Cat. 3/PL e in accordance with EN ISO 13849-1, SIL 3 in accordance with EN IEC 62061
Technical Specifications

Product properties

ApplicationZero-speed safety relay

Times

Typ. starting time with Us< 1 s
Response timetyp. 20 ms (at 50 Hz input frequency)
Delay time range0.5 s ... 20 s ±1 % (K1, K2 can be parameterized)

Electrical properties

Nominal operating mode100% operating factor
InterfacesWithout sensor

Air clearances and creepage distances between the power circuits

Rated Insulation Voltage250 V AC
Rated Insulation Voltage250 V AC
Rated Insulation Voltage400 V AC with isolation paths between (L1/L2/L3) and the remaining current paths
Rated Insulation Voltage690 V AC (with isolation paths within L1/L2/L3)
Rated surge voltage/insulationBasic insulation 4 kV:between all current paths and housingBasic insulation 8 kV:between L1 and L2between L1 and L3between L2 and L3
Rated surge voltage/insulationSafe isolation, reinforced insulation 6 kV:between A1/A2 and 13/14between MO/FO and 13/14Safe isolation, reinforced insulation 8 kV:between L1/L2/L3 and A1/A2between L1/L2/L3 and MO/FObetween L1/L2/L3 and 13/14

Supply

Rated control circuit supply voltage US20.4 V DC ... 26.4 V DC
Rated control circuit supply voltage US24 V DC -15 % / +10 %
Rated control supply current IStyp. 50 mA
Power consumption at UStyp. 1.2 W
Inrush Current5.6 A (Δt = 400 µs at Us)
Filter time1 ms (at A1 in the event of voltage dips at Us)
Protective circuitSurge protection; Suppressor diode
Protective circuitProtection against polarity reversal for rated control circuit supply voltage

Measurement

Voltage input signalmax. 690 V AC/DC (at L1/L2/L3)
Limit frequencymax. 3 kHz (At voltages > 2 VRMS)
Current consumptionmax. 0.35 mA (at L1/L2/L3)

Relay: Enabling current path

Output descriptionsafety-related N/O contacts
Number of Outputs1 (undelayed)
Contact switching type1 enabling current path
Contact MaterialAgSnO2
Switching voltagemin. 24 V AC/DC
Switching voltagemax. 250 V AC/DC (Observe the load curve)
Switching capacitymin. 72 mW
Inrush Currentmin. 3 mA
Inrush Currentmax. 5 A
Limiting Continuous Current5 A (observe derating)
Sq. Total current25 A2 (observe derating)
Switching frequencymax. 0.5 Hz
Mechanical service life10x 106 cycles
Output fuse5 A gL/gG

Signal

Number of Outputs2 (digital, PNP)
Voltage23 V DC (US - 1 V)
Currentmax. 100 mA
Maximum Inrush Current500 mA
Short-circuit protectionYes

Connection technology

pluggableyes

Conductor connection

Connection MethodScrew connection
Conductor cross section rigid0.2 mm² ... 2.5 mm²
Conductor cross section flexible0.2 mm² ... 2.5 mm²
Conductor cross section, flexible, with ferrule, with plastic sleeve0.2 mm² ... 2.5 mm²
Conductor cross section flexible, with ferrule without plastic sleeve0.2 mm² ... 2.5 mm²
Conductor cross-section AWG24 ... 12
Stripping length7 mm
Screw threadM3

Signaling

Status display4 x LED Bi-Colour

Dimensions

Width12.5 mm
Height112.2 mm
Depth114.5 mm

Material specifications

Color (Housing)yellow (RAL 1018)
Housing MaterialPolyamide

Safety data

Stop category0

Safety data: EN ISO 13849

Category3
Performance level (PL)e (4 A DC13; 5 A AC15; 17520 switching cycles/year)

Safety data: IEC 61508 - High demand

Safety Integrity Level (SIL)3 (4 A DC13; 5 A AC15; 17520 switching cycles/year)

Safety data: EN IEC 62061

Safety Integrity Level (SIL)3 (4 A DC13; 5 A AC15; 17520 switching cycles/year)

Ambient conditions

Degree of ProtectionIP20
Min. degree of protection of inst. locationIP54
Ambient Temperature (Operation)-20 °C ... 55 °C (observe derating)
Ambient temperature (storage/transport)-40 °C ... 85 °C
Maximum altitudemax. 2000 m (Above sea level)
Max. permissible humidity (storage/transport)75 % (on average, 85% infrequently, non-condensing)
Max. permissible relative humidity (operation)75 % (on average, 85% infrequently, non-condensing)
Shock15g
Vibration (Operation)10 Hz ... 150 Hz, 2g

CE

CertificateCE-compliant

Air clearances and creepage distances between the power circuits

Standards/regulationsDIN EN 50178

Mounting

Mounting TypeDIN rail mounting
Assembly instructionsSee derating curve
Mounting Positionvertical or horizontal
Accessories

Why Proax for Phoenix Contact PSR-MM25-1NO-2DO-24DC-SC?

Proax is an authorized distributor of Phoenix Contact PSR-MM25-1NO-2DO-24DC-SC and one of Phoenix Contact's largest distributors in North America. Our highly skilled in-house technical team is ready to assist with any technical needs.

Have a question in mind? to help you get the right product as quickly as possible for your project. We're always here to help!

Short Lead Time
Highly Trained Staff
Live Chat
Technical Support
Local Inventory
60+ Years Experience
Additional Information

Alternate NamesPSRMM251NO2DO24DCSC
Pack Size1
Recommended

Available for order