Official Distributor
SKU
MPN
PSR-MM30-2NO-2DO-24DC-SP
Weight
0.191 kg
This product is Not Cancellable/Not Returnable
Series PSR-MM
PSR-MM30-2NO-2DO-24DC-SP - Safety relay module
2-channel over-speed and zero-speed safety relay up to SIL 3, Cat. 4, PL e, 2 safe relay outputs, suitable for connecting HTL, TTL, or sine/cosine encoders as well as proximity switches, plug-in Push-in terminal block, width: 22.5 mm
- Monitoring of up to three different speeds as well as downtime
- Compatible with a range of motion sensors
- Easy parameterization and online monitoring with the PSRmotion software, which can be downloaded free of charge
- Force-guided relay contacts, parameterizable signal outputs
- Up to Cat. 4/PL e in accordance with EN ISO 13849-1, SIL 3 in accordance with EN IEC 62061, SIL 3 in accordance with IEC 61508
Technical Specifications
Product properties
Application | Zero-speed safety relay |
Application | Over-speed safety relay |
Relay type | Electromechanical relay with force-guided contacts in accordance with IEC/EN 61810-3 |
Times
Typical response time | < 200 ms (For Us autostart) |
Typical response time | < 150 ms (For Us manual, monitored start) |
Delay time range | 0 s ... 10 s ±10 % (Adjustable switch-on delay for downtime contacts 23/24) |
Restart time | < 1 s (Boot time) |
Recovery time | < 1 s |
Electrical properties
Maximum power dissipation for nominal condition | 6.5 W (at US = 26.4 V, UINPUT =30 V, IL² = 72 A²) |
Nominal operating mode | 100% operating factor |
Interfaces | Encoder |
Interfaces | Proximity switches |
Air clearances and creepage distances between the power circuits
Rated Insulation Voltage | 250 V AC |
Rated surge voltage/insulation | Basic insulation 4 kV between all current paths and housing |
Rated surge voltage/insulation | Safe isolation, reinforced insulation 6 kV between input circuit (A1/A2, I1, I2, I3, MI1, MI2, IN1, IN2, S34, MO1, MO2, RJ45, USB) and the enabling current paths (13/14, 23/24) |
Supply
Designation | A1/A2 |
Rated control circuit supply voltage US | 20.4 V DC ... 26.4 V DC |
Rated control circuit supply voltage US | 24 V DC -15 % / +10 % |
Rated control supply current IS | typ. 74 mA |
Power consumption at US | typ. 1.78 W |
Inrush Current | < 18 A (Δt = 500 µs at Us) |
Filter time | 2 ms (at A1 in the event of voltage dips at Us) |
Protective circuit | Serial protection against polarity reversal; 33 V suppressor diode |
Digital: Operating mode and monitoring inputs
Description of the input | NPN, IEC 61131-2, type 1 |
Number of Inputs | 1 (Non-safety-related start input: S34) |
Number of Inputs | 3 (Safety-related operating mode inputs: I1, I2, I3) |
Number of Inputs | 2 (Safety-related monitoring inputs: MI1, MI2) |
Discrepancy time | 2 s (I1, I2, I3) |
Discrepancy time | 2.5 s (MI1, MI2) |
Input voltage range "0" signal | 0 V DC ... 5 V DC |
Input voltage range "1" signal | 15 V DC ... 30 V DC |
Input current range "0" signal | 0 mA ... 1.5 mA |
Inrush Current | < 5 mA |
Filter time | max. 2 ms (Test pulse width; low test pulses for operating mode and monitoring inputs) |
Filter time | Test pulse rate = 5 x Test pulse width |
Max. permissible overall conductor resistance | 150 Ω |
Protective circuit | 33 V suppressor diode |
Current consumption | typ. 4 mA (at US) |
Measurement
Input name | Proximity switch inputs |
Description of the input | NPN, IEC 61131-2, type 1 |
Number of Inputs | 2 (Safety-related proximity switch inputs: IN1 IN2) |
Input voltage range "0" signal | 0 V DC ... 5 V DC |
Input voltage range "1" signal | 15 V DC ... 30 V DC |
Input current range "0" signal | 0 mA ... 1.5 mA |
Inrush Current | < 12 mA |
Precision | ± 2 % (in reference to the parameterized limit value) |
Limit frequency | max. 2 kHz (Minimum pulse duration: 45 µs) |
Max. permissible overall conductor resistance | 150 Ω |
Protective circuit | 33 V suppressor diode |
Current consumption | typ. 10 mA (at US) |
Input name | Encoder input |
Description of the input | TTL, HTL, Sin/Cos |
Number of Inputs | 1 (Safety-related encoder input, RJ45) |
Precision | ± 2 % (in reference to the parameterized limit value) |
Limit frequency | max. 400 kHz |
Limit frequency | max. 250 kHz For active diagnostic safety encoder |
Max. permissible overall conductor resistance | 150 Ω |
HTL Signal form/signal level | 0 V DC ... 3 V DC (Low) |
HTL Signal form/signal level | 12 V DC ... 30 V DC (High) |
TTL Signal form/signal level | 0 V DC ... 0.9 V DC (Low) |
TTL Signal form/signal level | 2.5 V DC ... 5 V DC (High) |
Sine / cosine Signal form/signal level | 2 V DC ... 3 V DC (1 Vpp differential signal) |
Current consumption | < 3 mA (Per track for US) |
Relay: Enabling current path
Output description | 2 NO contacts each in series, without delay, floating |
Number of Outputs | 2 (safety-related N/O contacts: 13/14, 23/24) |
Contact switching type | 2 enabling current paths |
Contact Material | AgSnO2 |
Switching voltage | min. 12 V AC/DC |
Switching voltage | max. 250 V AC/DC (Observe the load curve) |
Switching capacity | min. 60 mW |
Inrush Current | min. 3 mA |
Inrush Current | max. 6 A |
Switching capacity in accordance with IEC 60947-5-1 | 4 A (24 V (DC13)) |
Switching capacity in accordance with IEC 60947-5-1 | 5 A (250 V (AC15)) |
Limiting Continuous Current | 6 A |
Sq. Total current | 72 A2 (observe derating) |
Switching frequency | max. 0.5 Hz |
Mechanical service life | 10x 106 cycles |
Output fuse | 6 A gL/gG |
Signal
Output description | PNP |
Number of Outputs | 2 (Non-safety-related signal outputs: MO1, MO2) |
Voltage | approx. 22 V DC (Us - 2 V) |
Current | max. 100 mA |
Maximum Inrush Current | 500 mA (Δt = 1 ms at Us) |
Protective circuit | 33 V suppressor diode |
Short-circuit protection | no |
Connection technology
pluggable | yes |
Conductor connection
Connection Method | Push-in connection |
Conductor cross section rigid | 0.2 mm² ... 1.5 mm² |
Conductor cross section flexible | 0.2 mm² ... 1.5 mm² |
Conductor cross section, flexible, with ferrule, with plastic sleeve | 0.25 mm² ... 1.5 mm² (only together with CRIMPFOX 6) |
Conductor cross section flexible, with ferrule without plastic sleeve | 0.25 mm² ... 1.5 mm² (only together with CRIMPFOX 6) |
Conductor cross-section AWG | 24 ... 16 |
Stripping length | 8 mm |
Signaling
Status display | 2x LED green (OUT1, OUT2) |
Operating voltage display | 1 x green LED (PWR) |
Dimensions
Width | 22.5 mm |
Height | 117.5 mm |
Depth | 114.5 mm |
Material specifications
Color (Housing) | yellow (RAL 1018) |
Housing Material | Polyamide |
Safety data
Stop category | 0 |
Safety data: EN ISO 13849
Category | 4 |
Performance level (PL) | e (6 A DC1, 17520 switching cycles/year) |
Safety data: IEC 61508 - High demand
Safety Integrity Level (SIL) | 3 |
Safety data: EN IEC 62061
Safety Integrity Level (SIL) | 3 (For applications in SIL 3, the required demand rate for the safety function is once per day.) |
Ambient conditions
Degree of Protection | IP20 |
Min. degree of protection of inst. location | IP54 |
Ambient Temperature (Operation) | -40 °C ... 55 °C (observe derating) |
Ambient temperature (storage/transport) | -40 °C ... 70 °C |
Maximum altitude | ≤ 2000 m (Above sea level) |
Max. permissible humidity (storage/transport) | 75 % (on average, 85% infrequently, non-condensing) |
Max. permissible relative humidity (operation) | 75 % (on average, 85% infrequently, non-condensing) |
Shock | 15g |
Vibration (Operation) | 10 Hz ... 150 Hz, 2g |
CE
Certificate | CE-compliant |
Air clearances and creepage distances between the power circuits
Standards/regulations | DIN EN 50178, EN 60947-5-1 |
Mounting
Mounting Type | DIN rail mounting |
Assembly instructions | See derating curve |
Mounting Position | vertical or horizontal |
Accessories
Why Proax for Phoenix Contact 2702358?
Proax is an authorized distributor of Phoenix Contact 2702358 and one of Phoenix Contact's largest distributors in North America. Our highly skilled in-house technical team is ready to assist with any technical needs.
Have a question in mind? to help you get the right product as quickly as possible for your project. We're always here to help!
Short Lead Time
Highly Trained Staff
Live Chat
Technical Support
Local Inventory
60+ Years Experience
Additional Information
Pack Size | 1 |
Recommended