Proax

Currency
0 Items
proax logo
Cart
Phoenix ContactOfficial Distributor

By Phoenix Contact

SKU
MPN
2866530
Weight
1.957 kg
Series TRIO-PS

TRIO-PS/600DC/24DC/20 - Power supply unit

DIN rail power supply unit, primary-switched, 1-phase, input: 600 V DC, output: 24 V DC/20 A

  • Compact buffer solution
  • Fast tripping of standard circuit breakers
  • Preventive function monitoring
  • Reliable starting of difficult loads and easy system extension
Technical Specifications

DC operation

Nominal input voltage range600 V DC
Input voltage range450 V DC ... 840 V DC (Dielectric strength up to 900 V DC)
Voltage type of supply voltageDC
Inrush Current< 26 A
Inrush current integral (I2t)0.8 A2s
Frequency range DC0 Hz
Mains buffering timetyp. 15 ms (600 V DC)
Current consumption0.9 A (600 V DC)
Nominal Power Consumption527.3 VA
Protective circuitTransient surge protection; Varistor
Power factor (cos phi)1
Typical response time< 1 s
Permissible backup fuse4 A 6 A 1000 V DC
Recommended breaker for input protection4 A ... 6 A (1000 V DC)
Discharge current to PE< 3.5 mA

Output data

Efficiency> 91 % (With 600 V DC and nominal values)
Output characteristicU/I
Nominal Output Voltage24 V DC ±1 %
Setting range of the output voltage (USet)22.5 V DC ... 29.5 V DC (UIN > 475 V DC)
Setting range of the output voltage (USet)22.5 V DC ... 28 V DC (UIN ≤ 475 V DC)
Nominal output current (IN)20 A (-25 °C ... 55 °C)
Derating55 °C ... 70 °C (2.5 %/K)
Feedback voltage resistance35 V DC
Protection against overvoltage at the output (OVP)< 35 V DC
Max. capacitive loadunlimited
Active current limitationApprox. 25 A (for short-circuit)
Control deviation< 1 % (change in load, static 10 % ... 90 %)
Control deviation< 2 % (change in load, dynamic 10 % ... 90 %)
Control deviation< 0.1 % (change in input voltage ±10 %)
Residual ripple< 40 mVPP
Output Power480 W
Peak switching voltages nominal load< 10 mVPP
Maximum no-load power dissipation3.8 W
Power loss nominal load max.45 W
Rise time< 2 ms (UOUT (10 % ... 90 %))
Connection in parallelyes, for redundancy and increased capacity
Connection in seriesyes

Input

Connection MethodScrew connection
Conductor cross section, rigid min.0.2 mm²
Conductor cross section, rigid max.2.5 mm²
Conductor cross section flexible min.0.2 mm²
Conductor cross section flexible max.2.5 mm²
Conductor cross section AWG min.24
Conductor cross section AWG max.14
Stripping length9 mm
Screw threadM2,5
Tightening torque, min0.4 Nm
Tightening torque max0.5 Nm

Output

Connection MethodScrew connection
Conductor cross section, rigid min.0.5 mm²
Conductor cross section, rigid max.6 mm²
Conductor cross section flexible min.0.5 mm²
Conductor cross section flexible max.4 mm²
Conductor cross section AWG min.12
Conductor cross section AWG max.10
Stripping length14 mm
Screw threadM3
Tightening torque, min0.5 Nm
Tightening torque max0.6 Nm

Signaling

Types of signalingLED

Signal output

Status display"DC OK" LED green
Note on status displayUOUT > 21.5 V: LED lights up

Electrical properties

Insulation voltage input/output4 kV AC (type test)
Insulation voltage input/output2 kV AC (routine test)
Insulation voltage output / PE500 V DC (routine test)
Insulation voltage input/output2 kV (routine test)
Insulation voltage input / PE2 kV AC (type test)
Insulation voltage input / PE2 kV AC (routine test)
Insulation voltage input, output / housing4 kV

Product properties

Product familyTRIO POWER
MTBF (IEC 61709, SN 29500)> 701000 h (40 °C)

Insulation characteristics

Protection classI (with PE connection)
Overvoltage categoryIII
Degree of pollution2

Dimensions

Width115 mm
Height130 mm
Depth152.5 mm

Installation dimensions

Installation distance right/left0 mm / 0 mm
Installation distance top/bottom50 mm / 50 mm

Mounting

Mounting TypeDIN rail mounting
Assembly instructionsalignable: horizontally 0 mm, vertically 50 mm
Mounting Positionhorizontal DIN rail NS 35, EN 60715
With protective coatingNo

Material specifications

Housing MaterialMetal
Type of housingSteel sheet, zinc-plated
Side element versionAluminum

Ambient conditions

Degree of ProtectionIP20
Ambient Temperature (Operation)-25 °C ... 70 °C (> 55° C derating : 2.5%/K)
Ambient temperature (storage/transport)-40 °C ... 85 °C
Climatic class3K3 (in acc. with EN 60721)
Max. permissible relative humidity (operation)≤ 95 % (at 25 °C, non-condensing)
Shock18 ms, 30g, in each space direction (according to IEC 60068-2-27)
Vibration (Operation)< 15 Hz, amplitude ±2.5 mm (according to IEC 60068-2-6)
Vibration (Operation)15 Hz ... 150 Hz, 2.3g, 90 min.

Standards and Regulations

Rail applicationsEN 50121-4
Standard – Electronic equipment for use in electrical power installations and their assembly into electrical power installationsEN 50178/VDE 0160 (PELV)
Standard – Limitation of mains harmonic currentsEN 61000-3-2
Standard - Electrical safetyEN 60950-1/VDE 0805 (SELV)
Standard – Protection against shock currents, basic requirements for protective separation in electrical equipmentEN 50178
Standard – Safety extra-low voltageEN 60950-1 (SELV)
Standard – Safety extra-low voltageEN 60204 (PELV)
Standard - Safe isolationDIN VDE 0100-410

Approvals

UL approvalsUL/C-UL listed UL 508
UL approvalsUL/C-UL Recognized UL 60950-1

Conformity/Approvals

SIL in accordance with IEC 615080

EMC data

Low Voltage DirectiveConformance with Low Voltage Directive 2014/35/EC
EMC requirements for noise emissionEN 61000-6-3
EMC requirements for noise emissionEN 61000-6-4
EMC requirements for noise immunityEN 61000-6-1
EMC requirements for noise immunityEN 61000-6-2
Electromagnetic compatibilityConformance with EMC Directive 2014/30/EU

Electrostatic discharge

Standards/regulationsEN 61000-4-2
HousingLevel 3
Contact discharge8 kV (Test Level 4)
Discharge in air15 kV (Test Level 4)
CommentsCriterion B

Electromagnetic HF field

Standards/regulationsEN 61000-4-3
Frequency Range80 MHz ... 1 GHz
Test field strength20 V/m
Frequency Range1 GHz ... 2 GHz
Test field strength10 V/m
Frequency Range2 GHz ... 3 GHz
Test field strength10 V/m
CommentsCriterion A

Fast transients (burst)

Standards/regulationsEN 61000-4-4
Input4 kV (Test Level 4 - asymmetrical)
Output2 kV (Test Level 4 - asymmetrical)
CommentsCriterion B

Surge voltage load (surge)

Standards/regulationsEN 61000-4-5
Input1 kV (Test Level 2 - symmetrical)
Input2 kV (Test Level 3 - asymmetrical)
Output0.5 kV (Test Level 1 - symmetrical)
Output0.5 kV (Test Level 1 - asymmetrical)
CommentsCriterion B

Conducted interference

Standards/regulationsEN 61000-4-6
Frequency Range10 kHz ... 15 kHz
CommentsCriterion A
Voltage10 V (Test Level 3)

Voltage dips

Standards/regulationsEN 61000-4-11

Emitted interference

Standards/regulationsEN 61000-6-3
Radio interference voltage in acc. with EN 55011EN 55011 (EN 55022) Class B, area of application: Industry and residential
Emitted radio interference in acc. with EN 55011EN 55011 (EN 55022) Class B, area of application: Industry and residential
Accessories

Why Proax for Phoenix Contact TRIO-PS/600DC/24DC/20?

Proax is an authorized distributor of Phoenix Contact TRIO-PS/600DC/24DC/20 and one of Phoenix Contact's largest distributors in North America. Our highly skilled in-house technical team is ready to assist with any technical needs.

Have a question in mind? to help you get the right product as quickly as possible for your project. We're always here to help!

Short Lead Time
Highly Trained Staff
Live Chat
Technical Support
Local Inventory
60+ Years Experience
Additional Information

Alternate NamesTRIOPS600DC24DC20
Pack Size1
Recommended

Available for order