SKU
MPN
MACX MCR-RTD-I
Weight
0.174 kg
This product is Not Cancellable/Not Returnable
MACX MCR-RTD-I - Temperature measuring transducer
Temperature transducer, converts signals from resistance temperature detectors and resistors into analog 0/4 - 20 mA signals. Freely programmable, screw connection, SIL, 3-way electrical isolation, standard configuration.
- Power supply possible via DIN rail connector
- Programming possible during operation, when measuring circuit is connected, and also when power is switched off using the IFS-USB-PROG-ADAPTER programming adapter
- Installation in zone 2, protection type "ec" (EN 60079-7) permitted
- 3-way electrical isolation
- Status indicator for supply voltage, cable, sensor, and module errors
- Configuration via software (FDT/DTM): sensor type, connection technology, measuring range, measuring unit, filter, alarm signal, and output range
- Output: 0 mA ... 20 mA or 4 mA ... 20 mA
Technical Specifications
Utilization restriction
EMC note | EMC: class A product, see manufacturer's declaration in the download area |
Product properties
Product family | MACX Analog |
Application | Temperature |
No. of channels | 1 |
Type | Signal conditioners with SIL functional safety |
Configuration | Software |
Insulation characteristics: GB Standard
Overvoltage category | II |
Pollution degree | 2 |
Electrical properties
Alignment span | ± 5 % |
Alignment zero | ± 5 % |
Electrical isolation | 3-way isolation |
Electrical isolation between input and output | yes |
Step response (0–99%) | 1 s |
Step response (0–99%) | ≤ 1.7 s |
Temperature coefficient, typical | 0.01 %/K |
Transmission error, typical | 0.1 % (e.g. for Pt 100, 300 K span, 4 ... 20 mA) |
Electrical isolation Input/output/power supply
Rated Insulation Voltage | 300 Vrms |
Test voltage | 2.5 kV AC (50 Hz, 60 s) |
Insulation | Safe isolation in accordance with IEC/EN 61010-1 |
Electrical isolation Input/output
Electrical isolation | 375 V (Peak value in accordance with IEC/EN 60079-11) |
Electrical isolation Input/power supply
Electrical isolation | 375 V (Peak value in accordance with IEC/EN 60079-11) |
Supply
Nominal Supply Voltage | 24 V DC |
Supply Voltage Range | 19.2 V DC ... 30 V DC (24 V DC, -20 % ... +25 %) |
Power dissipation | ≤ 0.76 W |
Power consumption | ≤ 1 W |
Signal
Number of Inputs | 1 |
Measurement
Sensor types (RTD) that can be used | Pt, Ni, Cu sensors: 2, 3, 4-wire |
Temperature measuring range | -200 °C ... 850 °C (Range depending on the sensor type) |
Linear resistance measuring range | 0 Ω ... 50 kΩ |
Potentiometer resistance range | 0 Ω ... 50 kΩ |
Max. permissible overall conductor resistance | 50 Ω (Per cable) |
Sensor input current | 10 µA ... 210 µA (Up to 2x 210 µA with 3-conductor technology) |
Temperature measuring range | ≥ 50 K |
Signal: Current
Number of Outputs | 1 |
Configurable/programmable | Yes |
Current Output Signal | 0 mA ... 20 mA |
Current Output Signal | 4 mA ... 20 mA (SIL) |
Max. current output signal | ≥ 21 mA |
Load/Output Load Current Output | ≤ 600 Ω |
Output ripple (current) | < 15 µAPP |
Output ripple (current) | < 10 µArms |
Behavior in the event of a sensor error | As per NE 43 or can be freely defined |
Connection data
Connection Method | Screw connection |
Stripping length | 7 mm |
Screw thread | M3 |
Conductor cross section rigid | 0.2 mm² ... 2.5 mm² |
Conductor cross section flexible | 0.2 mm² ... 2.5 mm² |
Conductor cross section AWG | 24 ... 14 |
Tightening torque | 0.5 Nm ... 0.6 Nm |
Test socket
Max. diameter | 2 mm |
Ex data
Ex installation (EPL) | Gc |
Ex installation (EPL) | Div. 2 |
Signaling
Status display | Green LED (supply voltage) |
Status display | Red LED, flashing 2.4 Hz (cable error, sensor error on input or output, ERR) |
Status display | Red LED, flashing 1.2 Hz (service operation, ERR) |
Status display | Red LED, permanently on (module error, ERR) |
Dimensions
Width | 12.5 mm |
Height | 112.5 mm |
Depth | 113.7 mm |
Depth NS 35/7,5 | 114.5 mm (Snapped onto DIN rail NS 35/7,5 in accordance with EN 60715) |
Material specifications
Color | gray (RAL 7042) |
Flammability rating according to UL 94 | V0 (Housing) |
Housing Material | PA 6.6-FR |
Ambient conditions
Degree of Protection | IP20 |
Ambient Temperature (Operation) | -40 °C ... 70 °C (Any mounting position) |
Ambient temperature (storage/transport) | -40 °C ... 80 °C |
Permissible humidity (operation) | 5 % ... 95 % (non-condensing) |
Altitude range (≤ 2000 m)
Altitude | ≤ 2000 m (The technical data refers to altitudes ≤2000 m above mean sea level. For altitudes >2000 m above mean sea level, refer to the data sheet.) |
Ambient Temperature (Operation) | -40 °C ... 70 °C |
Test voltage | 2.5 kV |
Rated Insulation Voltage | 300 Vrms |
Altitude range (≤ 3000 m)
Height Range | > 2000 m ... 3000 m |
Ambient Temperature (Operation) | -40 °C ... 63 °C |
Test voltage | 2.25 kV |
Rated Insulation Voltage | 150 Vrms |
Altitude range (≤ 4000 m)
Height Range | > 3000 m ... 4000 m |
Ambient Temperature (Operation) | -40 °C ... 56 °C |
Test voltage | 2 kV |
Rated Insulation Voltage | 150 Vrms |
Altitude range (≤ 5000 m)
Height Range | > 4000 m ... 5000 m |
Ambient Temperature (Operation) | -40 °C ... 49 °C |
Test voltage | 1.75 kV |
Rated Insulation Voltage | 150 Vrms |
CE
Certificate | CE-compliant |
Note | and EN 61326 |
ATEX
Identification | II 3 G Ex ec ic IIC T4 Gc |
Certificate | PxCIF19ATEX1050192X |
UKCA Ex (UKEX)
Identification | II 3 G Ex ec ic IIC T4 Gc |
Certificate | CML 22UKEX3531X |
IECEx
Identification | Ex ec ic IIC T4 Gc |
Certificate | IECEx IBE 19.0001 X |
CCC / China-Ex
Identification | Ex nA ic IIC T4 Gc |
Certificate | NEPSI GYJ20.1305X |
UL, USA/Canada
Identification | UL 61010 Listed |
Identification | Class I, Div. 2, Groups A, B, C, D T4 |
Identification | Class I, Zone 2, Group IIC T4 |
Shipbuilding approval
Certificate | DNV GL TAA00000AG |
Safety Integrity Level (SIL, IEC 61508)
Identification | 2 |
EAC Ex
Identification | 2Ex ec ic IIC T4 Gc |
Certificate | BY/112 02.01 TP012 103.01 00082 |
DNV GL data
Temperature | B |
Humidity | B |
Vibration | A |
EMC | B |
Enclosure | Required protection according to the Rules shall be provided upon installation on board |
EMC data
Noise immunity | EN 61000-6-2 |
Note | When being exposed to interference, there may be minimal deviations. |
Electromagnetic compatibility | Conformance with EMC directive |
Noise emission | EN 61000-6-4 |
Electromagnetic HF field
Designation | Electromagnetic RF field |
Standards/regulations | EN 61000-4-3 |
Typical deviation from the measuring range final value | 1 % |
Fast transients (burst)
Designation | Fast transients (burst) |
Standards/regulations | EN 61000-4-4 |
Typical deviation from the measuring range final value | 1 % |
Conducted interference
Designation | Conducted interferences |
Standards/regulations | EN 61000-4-6 |
Typical deviation from the measuring range final value | 1 % |
Standards and Regulations
Electrical isolation | 3-way isolation |
GB Standard
Standards/regulations | GB 3836.1 |
Standards/regulations | GB 3836.4 |
Standards/regulations | GB 3836.8 |
Mounting
Mounting Type | DIN rail mounting |
Accessories
Why Proax for Phoenix Contact 1050192?
Proax is an authorized distributor of Phoenix Contact 1050192 and one of Phoenix Contact's largest distributors in North America. Our highly skilled in-house technical team is ready to assist with any technical needs.
Have a question in mind? to help you get the right product as quickly as possible for your project. We're always here to help!
Short Lead Time
Highly Trained Staff
Live Chat
Technical Support
Local Inventory
60+ Years Experience
Additional Information
Pack Size | 1 |
Recommended