MACX MCR-SL-2NAM-R-UP-SP - Isolation amplifier
2-channel NAMUR signal conditioner with wide range power supply for proximity sensors and switches. In terms of signal output, for each channel there is a relay with a changeover contact available. Line fault detection (LFD), 3-way isolation, Push-in connection, SIL 2.
- Installation in zone 2, protection type "n" (EN 60079-15) permitted
- Up to SIL 2 in accordance with EN 61508
- Line fault detection (LFD), can be activated/deactivated, error indicated by flashing red LED with de-excitation of output relay
- Direction of operation can be selected (operating or closed circuit current behavior)
- 3-way electrical isolation
- LED indicators for supply voltage, switching state, and malfunction in accordance with NAMUR NE 44
- Signal output relay (changeover contact)
- 2-channel
- Wide-range power supply of 19.2 ... 253 V AC/DC
- Input for NAMUR proximity sensors (EN 60947-5-6), floating contacts or contacts with resistance circuit
Technical Specifications
Product properties
Product family | MACX Analog |
No. of channels | 2 |
Type | Signal conditioners with SIL functional safety |
Configuration | DIP switches |
Functionality
Configuration | DIP switches |
Electrical properties
Electrical isolation | 3-way isolation |
Electrical isolation between input and output | yes |
Maximum power dissipation for nominal condition | ≤ 1.3 W |
Step response (10-90%) | typ. 6 ms (N/O contact: OFF/ON) |
Step response (10-90%) | typ. 6 ms (N/O contact: ON/OFF) |
Step response (10-90%) | typ. 4 ms (N/C contact: ON/OFF) |
Step response (10-90%) | typ. 10 ms (N/C contact: OFF/ON) |
Electrical isolation
Test voltage | 2.5 kV AC (50 Hz, 60 s) |
Electrical isolation Input/output IEC/EN 60079-11
Standards/regulations | IEC/EN 60079-11 |
Rated Insulation Voltage | 375 VPP |
Overvoltage category | III |
Pollution degree | 2 |
Electrical isolation Input/power supply IEC/EN 60079-11
Standards/regulations | IEC/EN 60079-11 |
Rated Insulation Voltage | 375 VPP |
Overvoltage category | II |
Pollution degree | 2 |
Electrical isolation Input/power supply IEC/EN 61010-1
Standards/regulations | IEC/EN 61010-1 |
Rated Insulation Voltage | 300 Vrms |
Overvoltage category | II |
Pollution degree | 2 |
Insulation | Safe isolation |
Electrical isolation Output 1/output 2/input, power supply IEC/EN 61010-1
Standards/regulations | IEC/EN 61010-1 |
Rated Insulation Voltage | 300 Vrms |
Overvoltage category | III |
Pollution degree | 2 |
Insulation | Safe isolation |
Supply
Nominal supply voltage range | 24 V AC/DC ... 230 V AC/DC -20 % ... +10 % (50/60 Hz) |
Supply Voltage Range | 19.2 V AC/DC ... 253 V AC/DC (50/60 Hz) |
Max. current consumption | < 80 mA |
Max. current consumption | < 42 mA (24 V DC) |
Power dissipation | < 1.1 W |
Power consumption | < 1.1 W |
Signal: NAMUR
Number of Inputs | 2 |
Available Input Sources | NAMUR proximity sensors (IEC/EN 60947-5-6) |
Available Input Sources | Floating switch contacts |
Available Input Sources | Switch contacts with resistance circuit |
Switching threshold "0" signal current | < 1.2 mA (blocking) |
Switching threshold "1" signal, current | > 2.1 mA (conductive) |
Short-circuit current | 8 mA |
Switching hysteresis | < 0.2 mA |
Line fault detection | < 0.05 mA ... 0.35 mA (Line break) |
Line fault detection | < 100 Ω ... 360 Ω (Short circuit) |
Line fault detection | Activated /deactivated via DIP switch |
Non-load voltage | 8 V DC |
Switching: Relay
Contact switching type | 1 changeover contact per channel |
Contact Material | AgSnO2, hard gold-plated |
Maximum Switching Voltage | 250 V AC (2 A, 60 Hz) |
Maximum Switching Voltage | 120 V DC (0.2 A) |
Maximum Switching Voltage | 30 V DC (2 A) |
Maximum switching capacity | 500 VA |
Recommended minimum load | 5 V / 10 mA |
Switching frequency | ≤ 20 Hz (Load-dependent) |
Signal
Number of Outputs | 2 |
Connection data
Connection Method | Push-in connection |
Stripping length | 10 mm |
Conductor cross section rigid | 0.2 mm² ... 2.5 mm² |
Conductor cross section flexible | 0.2 mm² ... 2.5 mm² |
Conductor cross section flexible (2 conductors with same cross section) | 0.25 mm² ... 0.34 mm² (TWIN ferrule without plastic sleeve) |
Conductor cross section flexible (2 conductors with same cross section) | 0.5 mm² ... 1.5 mm² (TWIN ferrule with plastic sleeve) |
Conductor cross section AWG | 24 ... 14 |
Conductor cross section AWG | 24 ... 22 (TWIN ferrule without plastic sleeve) |
Conductor cross section AWG | 20 ... 16 (TWIN ferrule with plastic sleeve) |
Ex data
Ex installation (EPL) | Gc |
Ex installation (EPL) | Div. 2 |
Data
No. of channels | 0 |
Signaling
Status display | Green LED (supply voltage) |
Status display | LED yellow (switching state) |
Status display | Red LED (line errors) |
Dimensions
Width | 17.5 mm |
Height | 107.9 mm |
Depth | 113.7 mm |
Depth NS 35/7,5 | 114.5 mm (Snapped onto DIN rail NS 35/7,5 in accordance with EN 60715) |
Material specifications
Color | gray (RAL 7042) |
Flammability rating according to UL 94 | V0 (Housing) |
Housing Material | PA 6.6-FR |
Safety data
Safety Integrity Level (SIL) | 2 |
Safety Integrity Level (SIL) | 2 |
Ambient conditions
Ambient Temperature (Operation) | -40 °C ... 60 °C (Any mounting position) |
Ambient Temperature (Operation) | -40 °C ... 70 °C (Derating) |
Ambient temperature (storage/transport) | -40 °C ... 85 °C |
Permissible humidity (operation) | 10 % ... 95 % (non-condensing) |
Altitude range (≤ 2000 m)
Altitude | ≤ 2000 m (The technical data refers to altitudes ≤2000 m above mean sea level. For altitudes >2000 m above mean sea level, refer to the data sheet.) |
Ambient Temperature (Operation) | -40 °C ... 60 °C |
Ambient Temperature (Operation) | -40 °C ... 70 °C (Derating) |
Rated Insulation Voltage | 253 V AC (Power supply, input / output) |
Rated Insulation Voltage | 125 V DC (Power supply, input / output) |
Altitude range (≤ 3000 m)
Height Range | > 2000 m ... 3000 m |
Ambient Temperature (Operation) | -40 °C ... 54 °C |
Ambient Temperature (Operation) | -40 °C ... 63 °C (Derating) |
Rated Insulation Voltage | 190 V AC (Power supply, input / output) |
Rated Insulation Voltage | 110 V DC (Power supply, input / output) |
Altitude range (≤ 4000 m)
Height Range | > 3000 m ... 4000 m |
Ambient Temperature (Operation) | -40 °C ... 48 °C |
Ambient Temperature (Operation) | -40 °C ... 56 °C (Derating) |
Rated Insulation Voltage | 60 V AC/DC (Power supply, input / output) |
Altitude range (≤ 5000 m)
Height Range | > 4000 m ... 5000 m |
Ambient Temperature (Operation) | -40 °C ... 42 °C |
Ambient Temperature (Operation) | -40 °C ... 49 °C (Derating) |
Rated Insulation Voltage | 60 V AC/DC (Power supply, input / output) |
CE
Certificate | CE-compliant |
Note | and EN 61326-1 |
ATEX
Identification | II 3G Ex ec nC IIC T4 Gc |
Certificate | IBExU 20 ATEX B011 X |
UKCA Ex (UKEX)
Identification | II 3 G Ex nA nC IIC T4 Gc X |
Certificate | PxCIF21UKEX2865052X |
IECEx
Identification | Ex ec nC IIC T4 Gc |
Certificate | IBE 10.0002 X |
CCC / China-Ex
Identification | Ex ec nC IIC T4 Gc |
Certificate | 2021122304114199 |
UL, USA/Canada
Identification | UL 508 Listed |
Identification | UL 61010 Listed |
Identification | Class I, Div. 2, Groups A, B, C, D T4 |
Identification | Class I, Zone 2, Group IIC T4 |
Shipbuilding approval
Certificate | DNV GL TAA000020C |
Safety Integrity Level (SIL, IEC 61508)
Identification | 2 |
INMETRO
Identification | Ex ec nC IIC T4 Gc |
Certificate | DNV 18.0116 X |
EAC Ex
Identification | 2Ex ec nC IIC T4 Gc |
Certificate | BY/112 02.01 TP012 103.01 00078 |
DNV GL data
Temperature | B |
Humidity | B |
Vibration | A |
EMC | A |
Enclosure | Required protection according to the Rules shall be provided upon installation on board |
EMC data
Noise immunity | EN 61000-6-2 |
Electromagnetic compatibility | Conformance with EMC directive |
Noise emission | EN 61000-6-4 |
Electromagnetic HF field
Designation | Electromagnetic RF field |
Standards/regulations | EN 61000-4-3 |
Evaluation criterion | A |
Fast transients (burst)
Designation | Fast transients (burst) |
Standards/regulations | EN 61000-4-4 |
Evaluation criterion | A |
Conducted interference
Designation | Conducted interferences |
Standards/regulations | EN 61000-4-6 |
Evaluation criterion | A |
Standards and Regulations
Electrical isolation | 3-way isolation |
GB Standard
Standards/regulations | GB/T 3836.1 |
Standards/regulations | GB/T 3836.3 |
Standards/regulations | GB/T 3836.8 |
Mounting
Mounting Type | DIN rail mounting |
Accessories
Why Proax for Phoenix Contact 2924304?
Proax is an authorized distributor of Phoenix Contact 2924304 and one of Phoenix Contact's largest distributors in North America. Our highly skilled in-house technical team is ready to assist with any technical needs.
Have a question in mind? to help you get the right product as quickly as possible for your project. We're always here to help!
Short Lead Time
Highly Trained Staff
Live Chat
Technical Support
Local Inventory
60+ Years Experience
Additional Information
Pack Size | 1 |
Recommended