2904890
SKU
PHX2904890
MPN
PACT RCP-D95
Series PACT-RCP-D
PACT RCP-D95 - Coil
300 mm long Rogowski coil. The measuring coil diameter when installed is 95 mm. The Rogowski coil is used for AC current measurement for busbars and power lines.
Technical Specifications
Insulation characteristics
| Pollution degree | 2 |
Measuring coil
| Conductor structure signal line | 2x 0.22 mm (Signal (tinned)) |
| Conductor structure signal line | 1x 0.22 mm (Shielding (tinned)) |
| Insulation | double insulation |
| Rated Insulation Voltage | 1000 V AC (rms CAT III) |
| Rated Insulation Voltage | 600 V AC (rms CAT IV) |
| Test voltage | 10.45 kV DC (60 s) |
| Basic accuracy | <± 0.2 % |
General
| Converter type | Rogowski coil |
Frequency
| Designation | Measuring coil |
| Frequency measuring range | 40 Hz ... 20000 Hz |
| Position error | <± 0.1 % (typical) |
| Linearity error | < 0.1 % |
Current transformers
| Converter type | Rogowski coil |
Signal
| Designation | Measuring coil |
| Output signal (at 50 Hz) | 100 mV (no load, at 1,000 A) |
| Output voltage (in no-load operation) | VOUT = M * dI/dt |
| Output voltage (sinusoidal, in no-load operation) | 100 mV (VOUT = 2 * π * M * f * I (M = 0.318 μH; example: At 50 Hz; I = 1,000 A)) |
Measuring coil
| Length | 300 mm |
| Diameter | 8.3 mm ±0.2 mm |
Measuring coil when installed
| Diameter | 95 mm |
Signal line
| Length | 3 m |
Material specifications
| Housing Material | PC |
| Coil material | Elastollan |
Ambient conditions
| Measuring coil degree of protection | IP67 (not assessed by UL) |
| Ambient Temperature (Operation) | -30 °C ... 80 °C (Measuring coil) |
| Ambient temperature (storage/transport) | -40 °C ... 80 °C (Measuring coil) |
| Altitude | < 2000 m |
| Permissible humidity (operation) | 5 % ... 95 % (non-condensing) |
UKCA
| Certificate | UKCA-compliant |
CMIM
| Certificate | CMIM-compliant |
UL, USA/Canada
| Identification | UL 61010 Recognized |
| Note | Measuring coil |
Standards and Regulations
| Standards/regulations | IEC 61010-1 |
| Standards/regulations | IEC 61010-2-032 |
Why Proax for Phoenix Contact 2904890?
Proax is an authorized distributor of Phoenix Contact 2904890 and one of Phoenix Contact's largest distributors in North America. Our highly skilled in-house technical team is ready to assist with any technical needs.
Have a question in mind? to help you get the right product as quickly as possible for your project. We're always here to help!
Short Lead Time
Highly Trained Staff
Live Chat
Technical Support
Local Inventory
60+ Years Experience
Additional Information
| Pack Size | 1 |
Recommended
PACT RCP-4000A-UIRO-D140 - Set consisting of a 4-way signal conditioner with screw connection technology and a Rogowski coil 450 mm in length/140 mm in diameter for AC current measurement on busbars and power lines.The signal conditioner outputs 8 different standard signals on the output side and has one switching output.