1145210
SKU
PHX1145210
MPN
FA MCR-HT-1TS-I-OLP
Weight
0.187 kg
FA MCR-HT-1TS-I-OLP - Head-mounted transducer
Output loop-powered head transmitter for transmitting RTD and TC sensor signals, as well as from resistance and voltage sensors via 4 mA ... 20 mA. HART, Standard configuration, Screw connection
Technical Specifications
Product properties
| Product family | Field Analog |
| No. of channels | 1 |
| Configuration | Software |
| Configuration | HART |
Insulation characteristics
| Overvoltage category | II |
| Pollution degree | 2 |
Electrical properties
| Step response (0–99%) | 1 s (TC) |
| Step response (0–99%) | 1 s (RTD) |
Electrical isolation Input/output
| Test voltage | 2 kV AC (50 Hz, 60 s) |
Supply
| Supply Voltage Range | loop-powered, no external supply necessary |
| Supply Voltage Range | 10 V DC ... 36 V DC (Standard) |
Measurement
| Number of Inputs | 1 |
| Input voltage range | -20 mV ... 100 mV (Minimum measuring span: 5 mV) |
| Sensor types (RTD) that can be used | Pt, Ni, Cu sensors: 2, 3, 4-wire |
| Sensor types that can be used (TC) | A, B, C, D, E, J, K, L, N, R, S, T, U |
| Temperature measuring range | -250 °C ... 2500 °C (Range depending on the sensor type) |
| Temperature measuring range | ≥ 10 K (RTD) |
| Temperature measuring range | ≥ 50 K (TC) |
| Linear resistance measuring range | 10 Ω ... 2000 Ω (Minimum measuring span: 10 Ω) |
Signal: Current
| Current Output Signal | 4 mA ... 20 mA (HART) |
| Current Output Signal | 20 mA ... 4 mA (HART) |
| Max. current output signal | 23 mA |
| Load | (UL - 10 V) / 0.023 A |
| HART coding | FSK ± 0.5 mA |
| HART version | 7 |
| Transmission Speed | 1200 Baud |
| Mains frequency filter | 50/60 Hz |
| Communication resistance | ≥ 250 Ω |
| Switch-on delay | 7 s (HART) |
| Switch-on delay | 7 s (Measured value) |
Connection data
| Connection Method | Screw connection |
| Stripping length | 8 mm |
| Screw thread | M3 |
| Conductor cross section rigid | 0.2 mm² ... 2.5 mm² |
| Conductor cross section flexible | 0.2 mm² ... 2.5 mm² |
| Conductor cross section AWG | 24 ... 14 |
| Tightening torque | 0.5 Nm |
Ex data
| Ex installation (EPL) | Gc |
| Ex installation (EPL) | Div. 2 |
Data communication (bypass)
| Protocols Supported | HART |
Ambient conditions
| Degree of Protection | IP00 (upon installation in field housing IP66/67, NEMA 4X) |
| Ambient Temperature (Operation) | -40 °C ... 85 °C |
| Ambient temperature (storage/transport) | -50 °C ... 100 °C |
| Altitude | ≤ 4000 m (Above sea level) |
| Climatic class | C1 |
| Permissible humidity (operation) | 5 % ... 95 % (condensation permitted) |
CE
| Certificate | CE-compliant |
ATEX
| Identification | II 3 G Ex ec IIC T6 |
| Certificate | PxCIF20ATEX1145192U |
CSA
| Identification | Ex ec IIC T6...T4 |
Mounting
| Mounting Type | Installation |
| Mounting Type | DIN rail mounting |
| Assembly instructions | Installation in connecting head B in accordance with DIN EN 50446 |
Why Proax for Phoenix Contact 1145210?
Proax is an authorized distributor of Phoenix Contact 1145210 and one of Phoenix Contact's largest distributors in North America. Our highly skilled in-house technical team is ready to assist with any technical needs.
Have a question in mind? to help you get the right product as quickly as possible for your project. We're always here to help!
Short Lead Time
Highly Trained Staff
Live Chat
Technical Support
Local Inventory
60+ Years Experience
Additional Information
| Pack Size | 1 |