3046485
UT 6-TG - Disconnect terminal block
Disconnect terminal block, Current and voltage are determined by the plug used., nom. voltage: 500 V, nominal current: 20 A, connection method: Screw connection, Rated cross section: 6 mm2, cross section: 0.2 mm2 - 10 mm2, mounting: NS 35/7,5, NS 35/15, color: gray
- Tested for railway applications
UT
The Phoenix Contact UT Series comprises feed-through terminal blocks that utilize screw connection technology, offering reliable and maintenance-free conductor connections for various industrial applications. These terminal blocks are designed to accommodate a wide range of conductor cross-sections, providing flexibility and ease of installation.
Key Features:
- ✅ Screw Connection Technology: The UT Series employs a screw connection method, ensuring secure and durable connections. The Reakdyn principle, a screw locking technique developed by Phoenix Contact, prevents loosening of terminal block screws, eliminating the need for retightening.
- ✅ Versatile Conductor Accommodation: These terminal blocks can connect solid and stranded conductors without ferrules, even above the nominal cross-section, due to their large wiring space. This feature allows for universal application across various conductor types and sizes.
- ✅ Compact Design: The UT Series offers a compact, space-saving design, making it ideal for smaller control cabinets and boxes where space is at a premium.
Notes
| General | Current and voltage are determined by the plug used. |
Product properties
| Area of application | Railway industry |
| Area of application | Machine building |
| Area of application | Plant engineering |
| Number of Connections | 2 |
| Number of rows | 1 |
| Potentials | 1 |
Insulation characteristics
| Overvoltage category | III |
| Degree of pollution | 3 |
Electrical properties
| Rated surge voltage | 6 kV |
| Maximum power dissipation for nominal condition | 1.31 W |
Connection data
| Number of connections per level | 2 |
| Nominal cross section | 6 mm² |
Level 1 above 1 below 1
| Screw thread | M4 |
| Tightening torque | 1.5 ... 1.8 Nm |
| Stripping length | 10 mm |
| Internal cylindrical gage | A5 |
| Connection in acc. with standard | IEC 60947-7-1 |
| Conductor cross section rigid | 0.2 mm² ... 10 mm² |
| Cross section AWG | 24 ... 8 (converted acc. to IEC) |
| Conductor cross section flexible | 0.2 mm² ... 10 mm² |
| Conductor cross section, flexible [AWG] | 24 ... 8 (converted acc. to IEC) |
| Conductor cross-section flexible (ferrule without plastic sleeve) | 0.25 mm² ... 6 mm² |
| Flexible conductor cross section (ferrule with plastic sleeve) | 0.25 mm² ... 6 mm² |
| 2 conductors with same cross section, solid | 0.2 mm² ... 2.5 mm² |
| 2 conductors with same cross section, flexible | 0.2 mm² ... 2.5 mm² |
| 2 conductors with same cross section, flexible, with ferrule without plastic sleeve | 0.25 mm² ... 1.5 mm² |
| 2 conductors with the same cross section, flexible, with TWIN ferrule with plastic sleeve | 0.5 mm² ... 4 mm² |
| Nominal Current | 20 A |
| Maximum Load Current | 20 A (with 10 mm² conductor cross section) |
| Nominal Voltage | 500 V |
| Nominal cross section | 6 mm² |
Dimensions
| Width | 8.2 mm |
| Height | 57.8 mm |
| Depth on NS 35/7,5 | 47.5 mm |
| Depth on NS 35/15 | 55 mm |
Material specifications
| Color | gray |
| Flammability rating according to UL 94 | V0 |
| Insulating material group | I |
| Insulating material | PA |
| Static insulating material application in cold | -60 °C |
| Relative insulation material temperature index (Elec., UL 746 B) | 130 °C |
| Fire protection for rail vehicles (DIN EN 45545-2) R22 | HL 1 - HL 3 |
| Fire protection for rail vehicles (DIN EN 45545-2) R23 | HL 1 - HL 3 |
| Fire protection for rail vehicles (DIN EN 45545-2) R24 | HL 1 - HL 3 |
| Fire protection for rail vehicles (DIN EN 45545-2) R26 | HL 1 - HL 3 |
| Surface flammability NFPA 130 (ASTM E 162) | passed |
| Specific optical density of smoke NFPA 130 (ASTM E 662) | passed |
| Smoke gas toxicity NFPA 130 (SMP 800C) | passed |
Surge voltage test
| Test voltage setpoint | 7.3 kV |
| Result | Test passed |
Temperature-rise test
| Requirement temperature-rise test | Increase in temperature ≤ 45 K |
| Result | Test passed |
| Result | Test passed |
| Short-time withstand current 2.5 mm² | 0.3 kA |
| Result | Test passed |
Mechanical data
| Open side panel | No |
Mechanical strength
| Result | Test passed |
Attachment on the carrier
| DIN rail/fixing support | NS 32/NS 35 |
| Test force setpoint | 5 N |
| Result | Test passed |
Test for conductor damage and slackening
| Rotation speed | 10 (+/- 2) rpm |
| Revolutions | 135 |
| Conductor cross section/weight | 0.2 mm² / 0.2 kg |
| Conductor cross section/weight | 6 mm² / 1.4 kg |
| Conductor cross section/weight | 10 mm² / 2 kg |
| Result | Test passed |
Needle-flame test
| Time of exposure | 30 s |
Oscillation/broadband noise
| Specification | DIN EN 50155 (VDE 0115-200):2018-05 |
| Specification | DIN EN 50155 (VDE 0115-200):2022-06 |
| Spectrum | Service life test category 2, bogie-mounted |
| Spectrum | Service life test category 2, bogie-mounted |
| Frequency | f1 = 5 Hz to f2 = 250 Hz |
| Frequency | f1 = 5 Hz to f2 = 250 Hz |
| ASD level | 6.12 (m/s²)²/Hz |
| ASD level | 6.12 (m/s²)²/Hz |
| Acceleration | 3.12g |
| Acceleration | 3.12g |
| Test duration per axis | 5 h |
| Test duration per axis | 5 h |
| Test directions | X-, Y- and Z-axis |
| Test directions | X-, Y- and Z-axis |
| Result | Test passed |
Shocks
| Specification | DIN EN 50155 (VDE 0115-200):2008-03 |
| Specification | DIN EN 50155 (VDE 0115-200):2022-06 |
| Pulse shape | Semi-sinusoidal |
| Pulse shape | Half-sine |
| Acceleration | 30g |
| Acceleration | 5g |
| Shock duration | 18 ms |
| Shock duration | 30 ms |
| Number of shocks per direction | 3 |
| Number of shocks per direction | 3 |
| Test directions | X-, Y- and Z-axis (pos. and neg.) |
| Test directions | X-, Y- and Z-axis (pos. and neg.) |
| Result | Test passed |
Ambient conditions
| Ambient Temperature (Operation) | -60 °C ... 110 °C (Operating temperature range incl. self-heating; for max. short-term operating temperature, see RTI Elec.) |
| Ambient temperature (storage/transport) | -25 °C ... 60 °C (for a short time, not exceeding 24 h, -60 °C to +70 °C) |
| Ambient temperature (assembly) | -5 °C ... 70 °C |
| Ambient temperature (actuation) | -5 °C ... 70 °C |
| Permissible humidity (operation) | 20 % ... 90 % |
| Permissible humidity (storage/transport) | 30 % ... 70 % |
Standards and Regulations
| Connection in acc. with standard | IEC 60947-7-1 |
Mounting
| Mounting Type | NS 35/7,5 |
| Mounting Type | NS 35/15 |
P-CO XL-UT - Component connector, for installing components that can be individually selected up to a diameter of 10 mm and power dissipation of up to 1 W, nom. voltage: 400 V, nominal current: 10 A, connection method: Plug-in connection, depth: 37.5 mm, width: 12.3 mm, height: 41.2 mm, number of positions: 1, color: gray, mounting type: Pluggable (slot)
P-CO - Component connector, for installing components that can be individually selected, nom. voltage: 250 V, nominal current: 6 A, connection method: Plug-in connection, pitch: 5.2 mm, depth: 33.2 mm, width: 5.1 mm, height: 24.2 mm, number of positions: 1, color: gray, mounting type: Pluggable (slot)
P-CO XL - Component connector, for installing components that can be individually selected up to a diameter of 10 mm and power dissipation of up to 1 W, nom. voltage: 400 V, nominal current: 10 A, connection method: Plug-in connection, depth: 37.5 mm, width: 12.3 mm, height: 41.2 mm, number of positions: 1, color: gray, mounting type: Pluggable (slot)
Why Proax for Phoenix Contact 3046485?
Proax is an authorized distributor of Phoenix Contact 3046485 and one of Phoenix Contact's largest distributors in North America. Our highly skilled in-house technical team is ready to assist with any technical needs.
Have a question in mind? to help you get the right product as quickly as possible for your project. We're always here to help!
| Pack Size | 50 |
UT 6-TG P/P - Disconnect terminal block, Current and voltage are determined by the plug used., With test socket screws for insertion of test plugs, nom. voltage: 500 V, nominal current: 20 A, connection method: Screw connection, Rated cross section: 6 mm2, cross section: 0.2 mm2 - 10 mm2, mounting: NS 35/7,5, NS 35/15, color: gray
UT 6-TG P/P-EX - Disconnect terminal block, Current and voltage are determined by the plug used., With test socket screws for insertion of test plugs, nom. voltage: 500 V, nominal current: 20 A, connection method: Screw connection, Rated cross section: 2.5 mm2, cross section: 0.2 mm2 - 10 mm2, mounting: NS 35/7,5, NS 35/15, color: gray
UT 6-TG P/P BU - Disconnect terminal block, Current and voltage are determined by the plug used., With test socket screws for insertion of test plugs, nom. voltage: 500 V, nominal current: 20 A, connection method: Screw connection, Rated cross section: 2.5 mm2, cross section: 0.2 mm2 - 10 mm2, mounting: NS 35/7,5, NS 35/15, color: blue