MPN
ST 1,5-TWIN
Weight
0.006 kg
This product is Not Cancellable/Not Returnable

ST 1,5-TWIN - Feed-through terminal block

Feed-through terminal block, nom. voltage: 500 V, nominal current: 17.5 A, number of connections: 3, connection method: Spring-cage connection, Rated cross section: 1.5 mm2, cross section: 0.08 mm2 - 1.5 mm2, mounting type: NS 35/7,5, NS 35/15, color: gray

  • The consistent double function shaft offers every opportunity for time-saving potential distribution and accommodating test accessories
  • User-friendly implementation of all potential branching tasks
  • Tested for railway applications
  • Space-saving and practical multi-conductor connection without additional bridges
Technical Specifications

General

Number of rows1
Number of Connections3
Potentials1
Nominal cross section1.5 mm²
Colorgray
Insulating materialPA
Flammability rating according to UL 94V0
Area of applicationRailway industry
Area of applicationMachine building
Area of applicationPlant engineering
Area of applicationProcess industry
Mounting TypeNS 35/7,5
Rated surge voltage6 kV
Degree of pollution3
Overvoltage categoryIII
Insulating material groupI
Maximum power dissipation for nominal condition0.56 W
Maximum Load Current17.5 A (in case of a 1.5 mm² conductor cross section, the maximum load current must not be exceeded by the total current of all connected conductors.)
Nominal current IN17.5 A (with 1.5 mm² conductor cross section)
Nominal voltage UN500 V
Open side panelYes
General informationWhen establishing a connection on the open housing side of a feed-through modular terminal block of the same series and size, the block must be provided with a cover if the expected insulation voltage is >320 V. The max. load current must not be exceeded by the total current of all connected conductors.
Shock protection test specificationDIN EN 50274 (VDE 0660-514):2002-11
Back of the hand protectionguaranteed
Finger protectionguaranteed
Result of surge voltage testTest passed
Surge voltage test setpoint7.3 kV
Result of power-frequency withstand voltage testTest passed
Power frequency withstand voltage setpoint1.89 kV
Result of the test for mechanical stability of terminal points (5 x conductor connection)Test passed
Result of flexion and pull-out testTest passed
Bending test rotation speed10 (+/- 2) rpm
Bending test turns135
Bending test conductor cross section/weight0.14 mm² / 0.2 kg
Bending test conductor cross section/weight0.2 mm² / 0.2 kg
Bending test conductor cross section/weight1.5 mm² / 0.4 kg
Tensile test resultTest passed
Conductor cross section tensile test0.14 mm²
Tractive force setpoint10 N
Conductor cross section tensile test0.2 mm²
Tractive force setpoint10 N
Conductor cross section tensile test1.5 mm²
Tractive force setpoint40 N
Result of tight fit on supportTest passed
Tight fit on carrierNS 32/NS 35
Setpoint1 N
Result of voltage-drop testTest passed
Requirements, voltage dropU1 ≤ 3.2 mV; U2 ≤ 1.5 x U1
Result of temperature-rise testTest passed
Requirement temperature-rise testIncrease in temperature ≤ 45 K
Short circuit stability resultTest passed
Conductor cross section short circuit testing1.5 mm²
Short-time current0.18 kA
Result of thermal testTest passed
Proof of thermal characteristics (needle flame) effective duration30 s
Result of aging testTest passed
Ageing test for screwless modular terminal block temperature cycles192
Oscillation, broadband noise test resultTest passed
Test specification, oscillation, broadband noiseDIN EN 50155 (VDE 0115-200):2018-05
Test spectrumService life test category 2, bogie-mounted
Test frequencyf1 = 5 Hz to f2 = 250 Hz
ASD level6.12 (m/s²)²/Hz
Acceleration3.12g
Test duration per axis5 h
Test directionsX-, Y- and Z-axis
Shock test resultTest passed
Test specification, shock testDIN EN 50155 (VDE 0115-200):2008-03
Shock formHalf-sine
Acceleration5g
Shock duration30
Number of shocks per direction3
Test directionsX-, Y- and Z-axis (pos. and neg.)
Relative insulation material temperature index (Elec., UL 746 B)130 °C
Temperature index of insulation material (DIN EN 60216-1 (VDE 0304-21))125 °C
Static insulating material application in cold-60 °C
Surface flammability NFPA 130 (ASTM E 162)passed
Specific optical density of smoke NFPA 130 (ASTM E 662)passed
Calorimetric heat release NFPA 130 (ASTM E 1354)27,5 MJ/kg
Smoke gas toxicity NFPA 130 (SMP 800C)passed
Fire protection for rail vehicles (DIN EN 45545-2) R22HL 1 - HL 3
Fire protection for rail vehicles (DIN EN 45545-2) R23HL 1 - HL 3
Fire protection for rail vehicles (DIN EN 45545-2) R24HL 1 - HL 3
Fire protection for rail vehicles (DIN EN 45545-2) R26HL 1 - HL 3

Dimensions

Width4.2 mm
End cover width2.2 mm
Length60.5 mm
Height NS 35/7,536.5 mm
Height NS 35/1544 mm

Connection data

Connection MethodSpring-cage connection
Stripping length8 mm ... 10 mm
Connection in acc. with standardIEC 60947-7-1
Conductor cross section solid min.0.08 mm²
Conductor cross section solid max.1.5 mm²
Conductor cross section AWG min.28
Conductor cross section AWG max.16
Conductor cross section flexible min.0.08 mm²
Conductor cross section flexible max.1.5 mm²
Min. AWG conductor cross section, flexible28
Max. AWG conductor cross section, flexible16
Conductor cross section flexible, with ferrule without plastic sleeve min.0.14 mm²
Conductor cross section flexible, with ferrule without plastic sleeve max.1.5 mm²
Conductor cross section flexible, with ferrule with plastic sleeve min.0.14 mm²
Conductor cross section flexible, with ferrule with plastic sleeve max.1.5 mm²
Two conductors with the same cross section, flexible, with TWIN ferrules, with plastic sleeve, maximum0.5 mm²
Internal cylindrical gageA1

Ambient conditions

Operating Temperature-60 °C ... 105 °C (max. short-term operating temperature RTI Elec.)
Ambient temperature (storage/transport)-25 °C ... 60 °C (for a short time, not exceeding 24 h, -60 °C to +70 °C)
Permissible humidity (storage/transport)30 % ... 70 %
Ambient temperature (assembly)-5 °C ... 70 °C
Ambient temperature (actuation)-5 °C ... 70 °C

Standards and Regulations

Connection in acc. with standardIEC 60947-7-1

Environmental Product Compliance

China RoHSEnvironmentally friendly use period: unlimited = EFUP-e
China RoHSNo hazardous substances above threshold values
Accessories

Why Proax for Phoenix Contact 3031128?

Proax is an authorized distributor of Phoenix Contact 3031128 and one of Phoenix Contact's largest distributors in North America. Our highly skilled in-house technical team is ready to assist with any technical needs.

Have a question in mind? to help you get the right product as quickly as possible for your project. We're always here to help!

Short Lead Time
Highly Trained Staff
Live Chat
Technical Support
Local Inventory
60+ Years Experience
Additional Information

Pack Size50
Recommended
Sold in quantities of 50

Not in stock

Request lead time or order—we'll ensure quick delivery

Phoenix Contact Availability