PT 2X2-24DC-ST - Surge protection plug
PT protective connector with protective circuit for two 2-wire floating signal circuits. 24 V DC nominal voltage. HART-compatible.
- Easy testing and documentation with CHECKMASTER 2 with pluggable protective modules
- Maximum ease of maintenance, thanks to the 2-piece design
- Easy selection for all possible demands in MCR applications with a complete product portfolio
- The signal is not influenced during maintenance work, thanks to the impedance-neutral insertion and removal of protective plugs
PT
The Phoenix Contact PT Series comprises feed-through terminal blocks that utilize Push-in connection technology, offering efficient and reliable wiring solutions for various industrial applications. These terminal blocks are designed for straightforward conductor insertion, enhancing installation speed and ensuring secure connections.
Key Features:
- ✅ Push-in Connection Technology: The PT Series employs a direct plug-in method, allowing solid conductors or conductors with ferrules to be inserted easily without the need for tools. This design facilitates quick and reliable wiring.
- ✅ Compact Design: The terminal blocks feature a space-saving form factor, making them suitable for applications where installation space is limited.
- ✅ High Electrical Ratings: Depending on the specific model, the PT Series terminal blocks can handle nominal voltages up to 800 V and nominal currents up to 32 A, accommodating a wide range of electrical requirements.
- ✅ Versatile Conductor Compatibility: These terminal blocks support various conductor types and sizes, providing flexibility in wiring configurations.
- ✅ Integration with CLIPLINE Complete System: The PT Series is compatible with Phoenix Contact's CLIPLINE complete system, allowing for standardized bridging, marking, and testing accessories, which simplifies inventory management and enhances system modularity.
General
Note | Technical data is valid in association with the following specified base elements: |
Note | PT 2X2+F-BE 2839224 |
Note | PT 2X2-BE 2839208 |
Product properties
Product family | PLUGTRAB PT |
IEC test classification | C1 |
IEC test classification | C2 |
IEC test classification | C3 |
IEC test classification | D1 |
Type | Male |
Surge protection fault message | none |
Arrester can be tested with CHECKMASTER from software version: | From SW rev. 1.00 |
Wire pairs per module | 2 |
Insulation characteristics
Overvoltage category | III |
Pollution degree | 2 |
Electrical properties
Nominal voltage UN | 24 V DC |
Connection data
Connection Method | Screw connection (in connection with the base element) |
Screw thread | M3 |
Tightening torque | 0.5 Nm |
Conductor cross section flexible | 0.2 mm² ... 2.5 mm² |
Conductor cross section rigid | 0.2 mm² ... 4 mm² |
Conductor cross section AWG | 24 ... 12 |
Dimensions
Width | 17.5 mm |
Height | 44.8 mm |
Depth | 51.7 mm |
Horizontal pitch | 1 Div. |
Complete module width | 17.7 mm |
Complete module height | 90 mm |
Complete module depth | 65.5 mm |
Material specifications
Color | black (RAL 9005) |
Color | Copper |
Flammability rating according to UL 94 | V-0 |
Housing Material | PA 6.6 |
Mechanical data
Open side panel | No |
Protective circuit
Direction of action | Line-Line & Line-Signal Ground/Shield & optional Signal Ground/Shield-Earth Ground |
Maximum continuous voltage UC | 28 V DC |
Maximum continuous voltage UC | 20 V AC |
Rated current | 450 mA (45 °C) |
Operating effective current IC at UC | ≤ 5 µA |
Residual current IPE | ≤ 1 µA (with PT 2X2+F-BE) |
Residual current IPE | ≤ 4 µA (with PT 2X2-BE) |
Nominal discharge current In (8/20) µs (line-line) | 10 kA |
Nominal discharge current In (8/20) µs (line-ground) | 10 kA |
Pulse discharge current Iimp (10/350) µs | 2.5 kA |
Total discharge current Itotal (8/20) µs | 20 kA |
Max. discharge current Imax (8/20) µs maximum (line-line) | 10 kA |
Max. discharge current Imax (8/20) µs maximum (line-earth) | 10 kA |
Nominal pulse current Ian (10/1000) µs (line-line) | 25 A |
Output voltage limitation at 1 kV/µs (line-line) spike | ≤ 45 V |
Output voltage limitation at 1 kV/µs (line-earth) spike | ≤ 450 V (with PT 2X2-BE) |
Output voltage limitation at 1 kV/µs (line-earth) spike | ≤ 1 kV (with PT 2X2+F-BE) |
Output voltage limitation at 1 kV/µs (line-line) static | ≤ 40 V |
Output voltage limitation at 1 kV/µs (line-earth) static | ≤ 25 V (with PT 2X2-BE) |
Output voltage limitation at 1 kV/µs (line-earth) static | ≤ 50 V (with PT 2X2+F-BE) |
Residual voltage at In (conductor-conductor) | ≤ 40 V |
Residual voltage at In (line-signalground) | ≤ 450 V |
Residual voltage with Ian (10/1000) µs (line-line) | ≤ 50 V |
Voltage protection level Up (line-line) | ≤ 70 V (C1 - 1 kV / 500 A) |
Voltage protection level Up (line-line) | ≤ 60 V (C2 - 6 kV / 3 kA) |
Voltage protection level Up (line-line) | ≤ 70 V (C2 - 10 kV / 5 kA) |
Voltage protection level Up (line-line) | ≤ 50 V (C3 - 25 A) |
Voltage protection level Up (line-earth) | ≤ 450 V (C1 - 1 kV / 500 A with PT 2X2-BE) |
Voltage protection level Up (line-earth) | ≤ 500 V (C2 - 6 kV / 3 kA with PT 2X2-BE) |
Voltage protection level Up (line-earth) | ≤ 550 V (C2 - 10 kV / 5 kA with PT 2X2-BE) |
Voltage protection level Up (line-earth) | ≤ 1000 V (C2 - 10 kV / 5 kA with PT 2X2+F-BE) |
Voltage protection level Up static (line-line) | ≤ 40 V (C2 - 10 kV / 5 kA) |
Voltage protection level Up static (line-earth) | ≤ 50 V (C2 - 10 kV / 5 kA with PT 2X2-BE) |
Voltage protection level Up static (line-earth) | ≤ 100 V (C2 - 10 kV / 5 kA with PT 2X2+F-BE) |
Response time tA (line-line) | ≤ 1 ns |
Response time tA (line-earth) | ≤ 100 ns |
Input attenuation aE, sym. | typ. 0.5 dB (≤ 1 MHz / 50 Ω) |
Input attenuation aE, sym. | typ. 0.3 dB (≤ 400 kHz / 150 Ω) |
Input attenuation aE, sym. | typ. 0.1 dB (≤ 70 kHz / 600 Ω) |
Cut-off frequency fg (3 dB), sym. in 50 Ω system | typ. 4.5 MHz |
Cut-off frequency fg (3 dB), sym. in 150 Ω system | typ. 1.5 MHz |
Cut-off frequency fg (3 dB), sym. in 600 Ω system | typ. 600 kHz |
Capacity (core-core) | typ. 1.4 nF |
Capacity (core-earth) | typ. 8 pF (with PT 2X2-BE) |
Capacity (core-earth) | typ. 2 pF (with PT 2X2+F-BE) |
Resistance per path | 2.2 Ω ±10 % |
Surge protection fault message | none |
Max. required back-up fuse | 500 mA (T) |
Impulse durability (line-line) | C1 - 1 kV / 500 A |
Impulse durability (line-line) | C2 - 6 kV / 3 kA |
Impulse durability (line-line) | C2 - 10 kV / 5 kA |
Impulse durability (line-line) | C3 - 25 A |
Impulse durability (line-earth) | C1 - 1 kV / 500 A |
Impulse durability (line-earth) | C2 - 6 kV / 3 kA |
Impulse durability (line-earth) | C2 - 10 kV / 5 kA |
Impulse durability (line-earth) | D1 - 2.5 kA |
Ambient conditions
Degree of Protection | IP20 |
Ambient Temperature (Operation) | -40 °C ... 85 °C |
Ambient temperature (storage/transport) | -40 °C ... 85 °C |
Altitude | ≤ 2000 m (amsl) |
Standards and Regulations
Standards/specifications | IEC 61643-21 |
Note | 2000 + corrigendum 2001 + A1:2008, modified + A2:2012 |
Standards/specifications | EN 61643-21 |
Note | 2001 + A1:2009 + A2:2013 |
Mounting
Mounting Type | on base element |
Why Proax for Phoenix Contact 2838228?
Proax is an authorized distributor of Phoenix Contact 2838228 and one of Phoenix Contact's largest distributors in North America. Our highly skilled in-house technical team is ready to assist with any technical needs.
Have a question in mind? to help you get the right product as quickly as possible for your project. We're always here to help!
Pack Size | 1 |
- PT 2X10/9X4 - Potential collective terminal, nom. voltage: 1000 V, nominal current: 57 A, Line contact, connection method: Push-in connection, Rated cross section: 10 mm2, cross section: 0.5 mm2 - 16 mm2, Load contact, connection method: Push-in connection, Rated cross section: 4 mm2, cross section: 0.5 mm2 - 6 mm2, mounting: NS 35/7,5, color: gray