PT 2X2-HF-24 DC-ST - Surge protection plug
Protective plug PT with HF protective circuit for two 2-core floating signal circuits. Nominal voltage: 24 V DC
- Easy testing and documentation with CHECKMASTER 2 with pluggable protective modules
- Maximum ease of maintenance, thanks to the 2-piece design
- Easy selection for all possible demands in MCR applications with a complete product portfolio
- The signal is not influenced during maintenance work, thanks to the impedance-neutral insertion and removal of protective plugs
PT
The Phoenix Contact PT Series comprises feed-through terminal blocks that utilize Push-in connection technology, offering efficient and reliable wiring solutions for various industrial applications. These terminal blocks are designed for straightforward conductor insertion, enhancing installation speed and ensuring secure connections.
Key Features:
- ✅ Push-in Connection Technology: The PT Series employs a direct plug-in method, allowing solid conductors or conductors with ferrules to be inserted easily without the need for tools. This design facilitates quick and reliable wiring.
- ✅ Compact Design: The terminal blocks feature a space-saving form factor, making them suitable for applications where installation space is limited.
- ✅ High Electrical Ratings: Depending on the specific model, the PT Series terminal blocks can handle nominal voltages up to 800 V and nominal currents up to 32 A, accommodating a wide range of electrical requirements.
- ✅ Versatile Conductor Compatibility: These terminal blocks support various conductor types and sizes, providing flexibility in wiring configurations.
- ✅ Integration with CLIPLINE Complete System: The PT Series is compatible with Phoenix Contact's CLIPLINE complete system, allowing for standardized bridging, marking, and testing accessories, which simplifies inventory management and enhances system modularity.
Product properties
Product family | PLUGTRAB PT |
IEC test classification | C1 |
IEC test classification | C2 |
IEC test classification | C3 |
IEC test classification | D1 |
VDE requirement class | C1 |
VDE requirement class | C2 |
VDE requirement class | C3 |
VDE requirement class | D1 |
Type | Male |
Number of Positions | 5 |
Arrester can be tested with CHECKMASTER from software version: | From SW rev. 1.00 |
Wire pairs per module | 2 |
Insulation characteristics
Overvoltage category | III |
Pollution degree | 2 |
Electrical properties
Nominal voltage UN | 24 V DC |
Connection data
Connection Method | Screw connection (in connection with the base element) |
Conductor cross section flexible | 0.2 mm² ... 2.5 mm² |
Conductor cross section rigid | 0.2 mm² ... 4 mm² |
Conductor cross section AWG | 24 ... 12 |
Dimensions
Width | 17.7 mm |
Height | 45 mm |
Depth | 52 mm |
Horizontal pitch | 1 Div. |
Material specifications
Color | black (RAL 9005) |
Color | Copper |
Flammability rating according to UL 94 | V-0 |
Housing Material | PA |
Mechanical data
Open side panel | No |
Protective circuit
Direction of action | Line-Line & Line-Signal Ground/Shield & optional Signal Ground/Shield-Earth Ground |
Maximum continuous voltage UC | 28 V DC |
Maximum continuous voltage UC | 19.8 V AC |
Rated current | 450 mA (45 °C) |
Operating effective current IC at UC | ≤ 5 µA |
Residual current IPE | ≤ 4 µA (with PT 2X2-BE) |
Residual current IPE | ≤ 1 µA (with PT 2X2+F-BE) |
Nominal discharge current In (8/20) µs (line-line) | 10 kA |
Nominal discharge current In (8/20) µs (line-ground) | 10 kA |
Pulse discharge current Iimp (10/350) µs | 2.5 kA |
Total discharge current Itotal (8/20) µs | 20 kA |
Max. discharge current Imax (8/20) µs maximum (line-line) | 10 kA |
Max. discharge current Imax (8/20) µs maximum (line-earth) | 10 kA |
Nominal pulse current Ian (10/1000) µs (line-line) | 30 A |
Output voltage limitation at 1 kV/µs (line-line) spike | ≤ 120 V |
Output voltage limitation at 1 kV/µs (line-earth) spike | ≤ 450 V |
Output voltage limitation at 1 kV/µs (line-earth) spike | ≤ 1 kV (with PT 2X2+F-BE) |
Output voltage limitation at 1 kV/µs (line-line) static | ≤ 45 V |
Output voltage limitation at 1 kV/µs (line-signalground) static | ≤ 450 V |
Residual voltage at In (conductor-conductor) | ≤ 40 V |
Residual voltage with Ian (10/1000) µs (line-line) | ≤ 50 V |
Voltage protection level Up (line-line) | ≤ 120 V (C2 - 10 kV / 5 kA) |
Voltage protection level Up (line-earth) | ≤ 450 V (C2 - 10 kV / 5 kA) |
Response time tA (line-line) | ≤ 500 ns |
Response time tA (line-earth) | ≤ 500 ns |
Input attenuation aE, sym. | 0.2 dB (≤ 5 MHz) |
Cut-off frequency fg (3 dB), sym. in 100 Ω system | typ. 70 MHz |
Capacity (core-core) | typ. 30 pF |
Resistance per path | 2.2 Ω |
Surge protection fault message | none |
Max. required back-up fuse | 500 mA (T) |
Impulse durability (line-line) | C2 - 10 kV / 5 kA |
Impulse durability (line-earth) | C2 - 10 kV / 5 kA |
Impulse durability (line-earth) | D1 - 2.5 kA |
Ambient conditions
Degree of Protection | IP20 |
Ambient Temperature (Operation) | -40 °C ... 85 °C |
Standards and Regulations
VDE requirement class | C1 |
VDE requirement class | C2 |
VDE requirement class | C3 |
VDE requirement class | D1 |
Air clearances and creepage distances
Standards/regulations | DIN VDE 0110-1 / IEC 60664-1 |
Standards Information technology specification
Standards/regulations | IEC 61643-21 |
Standards/regulations | IEC 61643-21 |
Standards/specifications | IEC 61643-21 |
Note | 2000 |