2839729
PT 2X2-HF-24 DC-ST - Surge protection plug
Protective plug PT with HF protective circuit for two 2-core floating signal circuits. Nominal voltage: 24 V DC
- Easy testing and documentation with CHECKMASTER 2 with pluggable protective modules
- Maximum ease of maintenance, thanks to the 2-piece design
- Easy selection for all possible demands in MCR applications with a complete product portfolio
- The signal is not influenced during maintenance work, thanks to the impedance-neutral insertion and removal of protective plugs
PT
The Phoenix Contact PT Series comprises feed-through terminal blocks that utilize Push-in connection technology, offering efficient and reliable wiring solutions for various industrial applications. These terminal blocks are designed for straightforward conductor insertion, enhancing installation speed and ensuring secure connections.
- Push-in Connection Technology: The PT Series employs a direct plug-in method, allowing solid conductors or conductors with ferrules to be inserted easily without the need for tools. This design facilitates quick and reliable wiring.
- Compact Design: The terminal blocks feature a space-saving form factor, making them suitable for applications where installation space is limited.
- High Electrical Ratings: Depending on the specific model, the PT Series terminal blocks can handle nominal voltages up to 800 V and nominal currents up to 32 A, accommodating a wide range of electrical requirements.
- Versatile Conductor Compatibility: These terminal blocks support various conductor types and sizes, providing flexibility in wiring configurations.
- Integration with CLIPLINE Complete System: The PT Series is compatible with Phoenix Contact's CLIPLINE complete system, allowing for standardized bridging, marking, and testing accessories, which simplifies inventory management and enhances system modularity.
Product properties
| Product family | PLUGTRAB PT |
| IEC test classification | C1 |
| IEC test classification | C2 |
| IEC test classification | C3 |
| IEC test classification | D1 |
| VDE requirement class | C1 |
| VDE requirement class | C2 |
| VDE requirement class | C3 |
| VDE requirement class | D1 |
| Type | Male |
| Number of Positions | 5 |
| Arrester can be tested with CHECKMASTER from software version: | From SW rev. 1.00 |
| Wire pairs per module | 2 |
Insulation characteristics
| Overvoltage category | III |
| Pollution degree | 2 |
Electrical properties
| Nominal voltage UN | 24 V DC |
Connection data
| Connection Method | Screw connection (in connection with the base element) |
| Conductor cross section flexible | 0.2 mm² ... 2.5 mm² |
| Conductor cross section rigid | 0.2 mm² ... 4 mm² |
| Conductor cross section AWG | 24 ... 12 |
Dimensions
| Width | 17.7 mm |
| Height | 45 mm |
| Depth | 52 mm |
| Horizontal pitch | 1 Div. |
Material specifications
| Color | black (RAL 9005) |
| Color | Copper |
| Flammability rating according to UL 94 | V-0 |
| Housing Material | PA |
Mechanical data
| Open side panel | No |
Protective circuit
| Direction of action | Line-Line & Line-Signal Ground/Shield & optional Signal Ground/Shield-Earth Ground |
| Maximum continuous voltage UC | 28 V DC |
| Maximum continuous voltage UC | 19.8 V AC |
| Rated current | 450 mA (45 °C) |
| Operating effective current IC at UC | ≤ 5 µA |
| Residual current IPE | ≤ 4 µA (with PT 2X2-BE) |
| Residual current IPE | ≤ 1 µA (with PT 2X2+F-BE) |
| Nominal discharge current In (8/20) µs (line-line) | 10 kA |
| Nominal discharge current In (8/20) µs (line-ground) | 10 kA |
| Pulse discharge current Iimp (10/350) µs | 2.5 kA |
| Total discharge current Itotal (8/20) µs | 20 kA |
| Max. discharge current Imax (8/20) µs maximum (line-line) | 10 kA |
| Max. discharge current Imax (8/20) µs maximum (line-earth) | 10 kA |
| Nominal pulse current Ian (10/1000) µs (line-line) | 30 A |
| Output voltage limitation at 1 kV/µs (line-line) spike | ≤ 120 V |
| Output voltage limitation at 1 kV/µs (line-earth) spike | ≤ 450 V |
| Output voltage limitation at 1 kV/µs (line-earth) spike | ≤ 1 kV (with PT 2X2+F-BE) |
| Output voltage limitation at 1 kV/µs (line-line) static | ≤ 45 V |
| Output voltage limitation at 1 kV/µs (line-signalground) static | ≤ 450 V |
| Residual voltage at In (conductor-conductor) | ≤ 40 V |
| Residual voltage with Ian (10/1000) µs (line-line) | ≤ 50 V |
| Voltage protection level Up (line-line) | ≤ 120 V (C2 - 10 kV / 5 kA) |
| Voltage protection level Up (line-earth) | ≤ 450 V (C2 - 10 kV / 5 kA) |
| Response time tA (line-line) | ≤ 500 ns |
| Response time tA (line-earth) | ≤ 500 ns |
| Input attenuation aE, sym. | 0.2 dB (≤ 5 MHz) |
| Cut-off frequency fg (3 dB), sym. in 100 Ω system | typ. 70 MHz |
| Capacity (core-core) | typ. 30 pF |
| Resistance per path | 2.2 Ω |
| Surge protection fault message | none |
| Max. required back-up fuse | 500 mA (T) |
| Impulse durability (line-line) | C2 - 10 kV / 5 kA |
| Impulse durability (line-earth) | C2 - 10 kV / 5 kA |
| Impulse durability (line-earth) | D1 - 2.5 kA |
Ambient conditions
| Degree of Protection | IP20 |
| Ambient Temperature (Operation) | -40 °C ... 85 °C |
Standards and Regulations
| VDE requirement class | C1 |
| VDE requirement class | C2 |
| VDE requirement class | C3 |
| VDE requirement class | D1 |
Air clearances and creepage distances
| Standards/regulations | DIN VDE 0110-1 / IEC 60664-1 |
Standards Information technology specification
| Standards/regulations | IEC 61643-21 |
| Standards/regulations | IEC 61643-21 |
| Standards/specifications | IEC 61643-21 |
| Note | 2000 |
Mounting
| Mounting Type | on base element |
Why Proax for Phoenix Contact 2839729?
Proax is an authorized distributor of Phoenix Contact 2839729 and one of Phoenix Contact's largest distributors in North America. Our highly skilled in-house technical team is ready to assist with any technical needs.
Have a question in mind? to help you get the right product as quickly as possible for your project. We're always here to help!
| Pack Size | 1 |