2856090
PT 2X1-12AC-ST - Surge protection plug
Surge protection plug for the base element, coarse and fine protection for two signal wires with common reference potential, common mode voltage coarse protection to ground. Design: 12 V AC
PT
The Phoenix Contact PT Series comprises feed-through terminal blocks that utilize Push-in connection technology, offering efficient and reliable wiring solutions for various industrial applications. These terminal blocks are designed for straightforward conductor insertion, enhancing installation speed and ensuring secure connections.
- Push-in Connection Technology: The PT Series employs a direct plug-in method, allowing solid conductors or conductors with ferrules to be inserted easily without the need for tools. This design facilitates quick and reliable wiring.
- Compact Design: The terminal blocks feature a space-saving form factor, making them suitable for applications where installation space is limited.
- High Electrical Ratings: Depending on the specific model, the PT Series terminal blocks can handle nominal voltages up to 800 V and nominal currents up to 32 A, accommodating a wide range of electrical requirements.
- Versatile Conductor Compatibility: These terminal blocks support various conductor types and sizes, providing flexibility in wiring configurations.
- Integration with CLIPLINE Complete System: The PT Series is compatible with Phoenix Contact's CLIPLINE complete system, allowing for standardized bridging, marking, and testing accessories, which simplifies inventory management and enhances system modularity.
Product properties
| Product family | PLUGTRAB PT |
| IEC test classification | C1 |
| IEC test classification | C2 |
| IEC test classification | C3 |
| IEC test classification | D1 |
| VDE requirement class | C1 |
| VDE requirement class | C2 |
| VDE requirement class | C3 |
| VDE requirement class | D1 |
| Type | Male |
| Surge protection fault message | none |
| Arrester can be tested with CHECKMASTER from software version: | From SW rev. 1.00 |
Insulation characteristics
| Overvoltage category | III |
| Pollution degree | 2 |
Electrical properties
| Nominal voltage UN | 12 V AC |
Connection data
| Connection Method | Screw connection (in connection with the base element) |
| Screw thread | M3 |
| Tightening torque | 0.8 Nm |
| Conductor cross section flexible | 0.2 mm² ... 2.5 mm² |
| Conductor cross section rigid | 0.2 mm² ... 4 mm² |
| Conductor cross section AWG | 24 ... 12 |
Dimensions
| Width | 17.7 mm |
| Height | 45 mm |
| Depth | 52 mm |
| Horizontal pitch | 1 Div. |
| Complete module width | 17.7 mm |
| Complete module height | 90 mm |
| Complete module depth | 65.5 mm |
Material specifications
| Flammability rating according to UL 94 | V-0 |
| Housing Material | PA 6.6 |
Mechanical data
| Open side panel | No |
Protective circuit
| Direction of action | Line-Line & Line-Signal Ground/Shield & optional Signal Ground/Shield-Earth Ground |
| Maximum continuous voltage UC | 18 V DC |
| Maximum continuous voltage UC | 13 V AC |
| Rated current | 300 mA (45 °C) |
| Operating effective current IC at UC | ≤ 5 µA |
| Residual current IPE | ≤ 1 µA (with PT 2X1+F-BE) |
| Residual current IPE | ≤ 10 µA (Directly grounded) |
| Nominal discharge current In (8/20) µs (line-ground) | 10 kA |
| Pulse discharge current Iimp (10/350) µs | 2.5 kA (per path) |
| Total discharge current Itotal (8/20) µs | 20 kA |
| Max. discharge current Imax (8/20) µs maximum (line-earth) | 10 kA |
| Nominal pulse current Ian (10/1000) µs (line-earth) | 49 A |
| Output voltage limitation at 1 kV/µs (line-earth) spike | ≤ 30 V |
| Output voltage limitation at 1 kV/µs (line-earth) static | ≤ 25 V |
| Residual voltage at In (conductor-ground) | ≤ 31 V |
| Voltage protection level Up (line-earth) | ≤ 70 V (C2 - 10 kV / 5 kA) |
| Response time tA (line-earth) | ≤ 1 ns |
| Input attenuation aE, asym. | 0.5 dB (≤ 700 kHz) |
| Cut-off frequency fg (3 dB), asym. (PE) in 50 Ω system | typ. 4 MHz |
| Capacity (core-earth) | 1.3 nF |
| Resistance per path | 4.7 Ω (1-2/5-6/7-8/11-12) |
| Surge protection fault message | none |
| Max. required back-up fuse | 315 mA (T) |
| Impulse durability (line-earth) | C2 - 10 kV / 5 kA |
| Impulse durability (line-earth) | D1 - 2.5 kA |
Ambient conditions
| Degree of Protection | IP20 |
| Ambient Temperature (Operation) | -40 °C ... 85 °C |
Standards and Regulations
| VDE requirement class | C1 |
| VDE requirement class | C2 |
| VDE requirement class | C3 |
| VDE requirement class | D1 |
Air clearances and creepage distances
| Standards/regulations | VDE 0110-1 / IEC 60664-1 |
Standards Information technology specification
| Standards/regulations | IEC 61643-21 |
| Standards/regulations | DIN EN 61643-21 |
| Standards/regulations | UL 497B |
| Standards/regulations | IEC 61643-21 |
| Standards/regulations | DIN EN 61643-21 |
| Standards/regulations | UL 497B |
| Standards/specifications | IEC 61643-21 |
| Note | 2000 |
Mounting
| Mounting Type | on base element |
Why Proax for Phoenix Contact 2856090?
Proax is an authorized distributor of Phoenix Contact 2856090 and one of Phoenix Contact's largest distributors in North America. Our highly skilled in-house technical team is ready to assist with any technical needs.
Have a question in mind? to help you get the right product as quickly as possible for your project. We're always here to help!
| Pack Size | 1 |
PT 2X10/9X4 - Potential collective terminal, nom. voltage: 1000 V, nominal current: 57 A, Line contact, connection method: Push-in connection, Rated cross section: 10 mm2, cross section: 0.5 mm2 - 16 mm2, Load contact, connection method: Push-in connection, Rated cross section: 4 mm2, cross section: 0.5 mm2 - 6 mm2, mounting: NS 35/7,5, color: gray