Official Distributor
SKU
MPN
2692351
Weight
0.159 kg
Series IB-IL-SGI
IB IL SGI 2/P - Inline terminal
Inline analog strain gauge input terminal, two precise inputs, 4, 6-conductor connection method
Technical Specifications
Product properties
Type | modular |
Operating mode | Process data operation with 3 words, PCP with 1 word |
Module
ID code (dec.) | 223 |
ID code (hex) | DF |
Length code (hex) | 03 |
Length code (dec) | 03 |
Process data channel | 48 bit |
Input address area | 48 bit |
Output address area | 48 bit |
Register length | 32 bit |
Required parameter data | 23 Byte |
Required configuration data | 5 Byte |
Potentials
Power consumption | typ. 1.2 W (Device in nominal operation) |
Power consumption | max. 3.2 W (Device with maximum load) |
Potentials: Communications power (UL)
Supply Voltage | 7.5 V DC (via voltage jumper) |
Current draw | max. 100 mA |
Current draw | typ. 85 mA |
Potentials: Supply of analog modules (UANA)
Supply Voltage | 24 V DC (via voltage jumper) |
Supply Voltage Range | 19.2 V DC ... 30 V DC (including all tolerances, including ripple) |
Current draw | max. 100 mA |
Current draw | typ. 25 mA (in case of typical load of 350 Ohm per channel) |
Current draw | 80 mA (for a maximum load of 55 Ω and display) |
Current draw | 7 mA (for no-load operation without strain gauge or display) |
Electrical isolation/isolation of the voltage ranges
Test voltage: Logic/analog I/O (digital isolator) | 500 V AC, 50 Hz, 1 min. |
Test voltage: RS-485/analog I/O (isolating distance) | 500 V AC, 50 Hz, 1 min. |
Test voltage: N/O contact Ka1 - Kb1 / analog I/O (isolating distance) | 500 V AC, 50 Hz, 1 min. |
Test voltage: N/O contact Ka2 - Kb2 / analog I/O (isolating distance) | 500 V AC, 50 Hz, 1 min. |
Test voltage: Functional ground/analog I/O (isolating distance) | 500 V AC, 50 Hz, 1 min. |
Test voltage: Logic/RS-485 (digital isolator) | 500 V AC, 50 Hz, 1 min. |
Test voltage: N/O contact Ka1 - Kb1 / RS-485 (isolating distance) | 500 V AC, 50 Hz, 1 min. |
Test voltage: N/O contact Ka2 - Kb2 / RS-485 (isolating distance) | 500 V AC, 50 Hz, 1 min. |
Test voltage: Functional ground/RS-485 (isolating distance) | 500 V AC, 50 Hz, 1 min. |
Test voltage: Logic / N/O contact Ka1 - Kb1 (optocoupler) | 500 V AC, 50 Hz, 1 min. |
Test voltage: N/O contact Ka2 - Kb2/N/O contact Ka1 - Kb1 (isolating distance) | 500 V AC, 50 Hz, 1 min. |
Test voltage: Functional ground/N/O contact Ka1 - Kb1 (isolating distance) | 500 V AC, 50 Hz, 1 min. |
Test voltage: Logic / N/O contact Ka2 - Kb2 (optocoupler) | 500 V AC, 50 Hz, 1 min. |
Test voltage: Functional ground/N/O contact Ka2 - Kb2 (isolating distance) | 500 V AC, 50 Hz, 1 min. |
Test voltage: Logic/functional ground (isolating distance) | 500 V AC, 50 Hz, 1 min. |
Analog
Description of the input | Input channels for strain gauge |
Number of Inputs | 2 |
Connection technology | 6 or 4-wire, twisted pair shielded cable |
Bridge difference Ud | Measuring range specified by selecting the characteristic |
Bridge voltage U0 | 5 V |
Measured value representation | 15 bit + sign bit |
Process data update | typ. 100 ms (12.5 ms, depends on the configuration) |
Characteristics | ±1 mV/V, ±2 mV/V, ±3 mV/V, ±3.33 mV/V, ±4 mV/V, ±5 mV/V |
Contacts
Description | Floating N/O contact |
Quantity | 2 (Ka1-Kb1, Ka2-Kb2) |
Contact resistance | < 1 Ω (typical) |
Contact resistance | 5 Ω (maximum) |
Typical response time | 100 ms (typical) |
Analog:
Protective circuit | Short-circuit protection of the voltage outputs; Yes, at least 1 minute through temperature monitoring |
Analog
Output description | Voltage output |
Number of Outputs | 2 |
Impedance | > 55 Ω (minimum) |
Output Voltage | typ. 5 V |
Output Current | max. 90 mA (with UV = 5 V) |
Maximum output current | max. 90 mA (with UV = 5 V) |
Inline connector
Connection Method | Spring-cage connection |
Conductor cross section, rigid | 0.08 mm² ... 1.5 mm² |
Conductor cross section, flexible | 0.08 mm² ... 1.5 mm² |
Conductor cross section AWG | 28 ... 16 |
Inline local bus
Connection Method | Inline data jumper |
Transmission Speed | 500 kbps |
Transmission physics | Copper |
Serial
Designation | V.24 (RS-485) serial interface |
Network | Yes |
Addressing | Address 1 = Measured gross/net value |
Addressing | Address 2 = Measured tare value |
Termination resistor | 120 Ω |
Transmission protocol | STX/ETX |
Dimensions
Width | 48.8 mm |
Height | 136 mm |
Depth | 71.5 mm |
Material specifications
Color | green |
Ambient conditions
Ambient Temperature (Operation) | -25 °C ... 55 °C |
Degree of Protection | IP20 |
Air pressure (operation) | 70 kPa ... 106 kPa (up to 3000 m above sea level) |
Air pressure (storage/transport) | 70 kPa ... 106 kPa (up to 3000 m above sea level) |
Ambient temperature (storage/transport) | -25 °C ... 85 °C |
Permissible humidity (operation) | 10 % ... 95 % (according to DIN EN 61131-2) |
Permissible humidity (storage/transport) | 10 % ... 95 % (according to DIN EN 61131-2) |
Standards and Regulations
Protection class | III (IEC 61140, EN 61140, VDE 0140-1) |
Mounting
Mounting Type | DIN rail mounting |
Why Proax for Phoenix Contact IB IL SGI 2/P?
Proax is an authorized distributor of Phoenix Contact IB IL SGI 2/P and one of Phoenix Contact's largest distributors in North America. Our highly skilled in-house technical team is ready to assist with any technical needs.
Have a question in mind? to help you get the right product as quickly as possible for your project. We're always here to help!
Short Lead Time
Highly Trained Staff
Live Chat
Technical Support
Local Inventory
60+ Years Experience
Additional Information
Alternate Names | IBILSGI2P |
Pack Size | 1 |