Proax

Currency
0 Items
proax logo
Cart
Phoenix ContactOfficial Distributor

By Phoenix Contact

SKU
MPN
2878735
Weight
0.226 kg
This product is Not Cancellable/Not Returnable
Series IB-IL-SGI

IB IL SGI 2/F-2MBD-PAC - Analog module

Inline, Strain gauge measurement terminal, transmission speed in the local bus: 2 Mbps, 2 fast inputs, 4-, 6-conductor connection technology, degree of protection: IP20, including Inline connectors and marking fields

  • 2 fast inputs for strain gauge
  • Connection of strain gauges in 6- and 4-conductor technology
  • Sensor supply voltage provided by the terminal, no external power supply required
  • Communication either via process data or parameter channel (PCP)
  • The channels are parameterized independently of one another via the bus system
  • Bus-synchronous process data update
  • Diagnostic and status indicators
Technical Specifications

Dimensions

Width48.8 mm
Height136 mm
Depth71.5 mm

Inline local bus

Number of interfaces2
Connection MethodInline data jumper
Transmission Speed2 Mbps
Transmission physicsCopper

Module

ID code (dec.)223
ID code (hex)DF
Length code (hex)03
Length code (dec)03
Process data channel48 bit
Input address area6 Byte
Output address area6 Byte
Register length32 bit
Required parameter data 15 Byte
Required configuration data 5 Byte

Analog

Description of the inputInput channels for strain gauge
Number of Inputs2
Connection technology6 or 4-wire, twisted pair shielded cable
Bridge difference UdMeasuring range specified by selecting the characteristic and the bridge voltage
Bridge voltage U03.3 V
Bridge voltage U05 V
Measured value representation15 bit + sign bit
Characteristics±1 mV/V, ±2 mV/V, ±3 mV/V, ±4 mV/V
Characteristics+1 mV/V, +2 mV/V, +3 mV/V, +4 mV/V
Output descriptionVoltage output
Number of Outputs2
Impedance> 58.3 Ω (typical; permissible total resistance of the strain gauge)
Output Voltage5 V
Output Voltage3.3 V
Output Currenttyp. 55 mA (with UV = 3.3 V)
Output Currenttyp. 85 mA (with UV = 5 V)

Product properties

Product familyInline
Typemodular
Scope of deliveryincluding Inline connectors and marking fields
Operating modeProcess data operation with 3 words, PCP with 1 word
Special Properties2 fast inputs
Special Properties4-, 6-conductor connection technology
Diagnostics messagesFailure of the power supply at UANA Error message in the process data
Diagnostics messagesFailure of or insufficient communications power UL I/O error message sent to the bus coupler
Diagnostics messagesI/O error Error message in the process data

Potentials

Power consumptiontyp. 0.94 W (Device in nominal operation)

Potentials: Communications power (UL)

Supply Voltage7.5 V DC (via voltage jumper)
Current drawmax. 110 mA
Current drawtyp. 100 mA

Potentials: Supply of analog modules (UANA)

Supply Voltage24 V DC (via voltage jumper)
Supply Voltage Range19.2 V DC ... 30 V DC (including all tolerances, including ripple)
Current drawtyp. 32 mA (with maximum load of 58.3 Ω when UV = 5 V)
Current drawtyp. 8 mA (without strain gauge)

Electrical isolation/isolation of the voltage ranges

Test voltage: Logic/analog I/O (digital isolator)500 V AC, 50 Hz, 1 min.
Test voltage: Functional ground/analog I/O (isolating distance)500 V AC, 50 Hz, 1 min.
Test voltage: Logic/functional ground (isolating distance)500 V AC, 50 Hz, 1 min.

Connection technology

Connection nameInline connector

Conductor connection

Connection MethodSpring-cage connection
Conductor cross section rigid0.08 mm² ... 1.5 mm²
Conductor cross section flexible0.08 mm² ... 1.5 mm²
Conductor cross section AWG28 ... 16
Stripping length8 mm

Inline connector

Connection MethodSpring-cage connection
Conductor cross section, rigid0.08 mm² ... 1.5 mm²
Conductor cross section, flexible0.08 mm² ... 1.5 mm²
Conductor cross section AWG28 ... 16
Stripping length8 mm

Ambient conditions

Ambient Temperature (Operation)-25 °C ... 55 °C
Degree of ProtectionIP20
Air pressure (operation)70 kPa ... 106 kPa (up to 3000 m above sea level)
Air pressure (storage/transport)70 kPa ... 106 kPa (up to 3000 m above sea level)
Ambient temperature (storage/transport)-25 °C ... 85 °C
Permissible humidity (operation)10 % ... 95 % (non-condensing)
Permissible humidity (storage/transport)10 % ... 95 % (non-condensing)

Standards and Regulations

Protection classIII (IEC 61140, EN 61140, VDE 0140-1)

Mounting

Mounting TypeDIN rail mounting
Accessories

Why Proax for Phoenix Contact IB IL SGI 2/F-2MBD-PAC?

Proax is an authorized distributor of Phoenix Contact IB IL SGI 2/F-2MBD-PAC and one of Phoenix Contact's largest distributors in North America. Our highly skilled in-house technical team is ready to assist with any technical needs.