Official Distributor
SKU
MPN
MINI MCR-2-I-I-ILP-PT
Weight
0.109 kg
Series MINI-MCR
MINI MCR-2-I-I-ILP-PT - Loop-powered isolators
1-channel input loop-powered 2-way isolator with plug-in connection technology for the electrical isolation of analog signals. Input signal = output signal: 0(4) mA ... 20 mA. Push-in connection technology.
Technical Specifications
Utilization restriction
EMC note | EMC: class A product, see manufacturer's declaration in the download area |
Product properties
Product family | MINI Analog Pro |
No. of channels | 1 |
Type | Signal conditioner |
Insulation characteristics: GB Standard
Overvoltage category | II |
Pollution degree | 2 |
Electrical properties
Electrical isolation | 2-way isolation |
Electrical isolation between input and output | yes |
Limit frequency (3 dB) | 100 Hz |
Signal transmission behavior | In = Out |
Maximum temperature coefficient | ≤ 0.002 %/K (of measured value / 100 Ω load) |
Maximum transmission error | ≤ 0.1 % (of final value) |
Additional error, load-dependent | < 0.075 % (of measured value / 100 Ω load) |
Electrical isolation Input/output
Rated Insulation Voltage | 300 Vrms |
Test voltage | 3 kV AC (50 Hz, 60 s) |
Insulation | Reinforced insulation according to IEC/EN 61010-1 |
Supply
Supply Voltage Range | 9.6 V DC ... 30 V DC (loop-powered, no external supply necessary) |
Power consumption | 600 mW |
Signal: Current
Number of Inputs | 1 |
Configurable/programmable | no |
Current Input Signal | 0 mA ... 20 mA |
Current Input Signal | 4 mA ... 20 mA |
Response current | approx. 200 µA |
Input voltage limitation | 30 V |
Voltage dissipation | 3.1 V (I = 20 mA) |
Number of Outputs | 1 |
Configurable/programmable | no |
Current Output Signal | 0 mA ... 20 mA |
Current Output Signal | 4 mA ... 20 mA |
Load/Output Load Current Output | < 600 Ω (at I = 20 mA output signal) |
Connection data
Connection Method | Push-in connection |
Stripping length | 10 mm |
Conductor cross section rigid | 0.2 mm² ... 2.5 mm² (with ferrule) |
Conductor cross section rigid | 0.14 mm² ... 2.5 mm² (without ferrule) |
Conductor cross section flexible | 0.14 mm² ... 2.5 mm² |
Conductor cross section AWG | 24 ... 12 (flexible) |
Ex data
Ex installation (EPL) | Gc |
Ex installation (EPL) | Div. 2 |
Dimensions
Width | 6.2 mm |
Height | 109.81 mm |
Depth | 119.2 mm |
Material specifications
Color | gray (RAL 7042) |
Housing Material | PBT |
Fire protection for rail vehicles (DIN EN 45545-2) R22 | HL 1 - HL 2 |
Fire protection for rail vehicles (DIN EN 45545-2) R23 | HL 1 - HL 2 |
Fire protection for rail vehicles (DIN EN 45545-2) R24 | HL 1 - HL 2 |
Ambient conditions
Degree of Protection | IP20 (not assessed by UL) |
Ambient Temperature (Operation) | -40 °C ... 70 °C |
Ambient temperature (storage/transport) | -40 °C ... 85 °C |
Altitude | < 2000 m |
Permissible humidity (operation) | 5 % ... 95 % (non-condensing) |
CE
Certificate | CE-compliant |
ATEX
Identification | II 3 G Ex ec IIC T4 Gc |
Certificate | BVS 19 ATEX E 079 X |
UKCA Ex (UKEX)
Identification | II 3 G Ex ec IIC T4 Gc |
Certificate | PxCIF21UKEX2901994X |
IECEx
Identification | Ex ec IIC T4 Gc |
Certificate | IECEx BVS 19.0068X |
CCC / China-Ex
Identification | Ex nA IIC T4 Gc |
UL, USA/Canada
Identification | UL 508 Listed |
Identification | Class I, Div. 2, Groups A, B, C, D T6 |
Identification | Class I, Zone 2, Group IIC T6 |
EAC Ex
Identification | 2Ex ec IIC T4 Gc |
Certificate | BY/112 02.01 TP012 103.01 00079 |
EMC data
Noise immunity | EN 61000-6-2 |
Note | When being exposed to interference, there may be minimal deviations. |
Electromagnetic compatibility | Conformance with EMC directive |
Noise emission | EN 61000-6-4 |
Standards and Regulations
Electrical isolation | 2-way isolation |
GB Standard
Standards/regulations | GB 3836.1 |
Standards/regulations | GB 3836.8 |
Mounting
Mounting Type | DIN rail mounting |
Mounting Position | any |
Accessories
Why Proax for Phoenix Contact 2901995?
Proax is an authorized distributor of Phoenix Contact 2901995 and one of Phoenix Contact's largest distributors in North America. Our highly skilled in-house technical team is ready to assist with any technical needs.
Have a question in mind? to help you get the right product as quickly as possible for your project. We're always here to help!
Short Lead Time
Highly Trained Staff
Live Chat
Technical Support
Local Inventory
60+ Years Experience
Additional Information
Pack Size | 1 |
Recommended
- Convertisseur de fréquence à configuration universelle, pour la conversion des signaux de fréquence (Hz/rpm) et de modulation d'impulsions en largeur, en signaux normalisés. Tensions de capteur supérieure à 8,2 V DC, en relation avec MINI MCR-2-SPS-PT 1033201 possible. Technologie de raccordement Push-in.