Proax

Currency
0 Items
proax logo
Cart
Phoenix ContactOfficial Distributor

By Phoenix Contact

SKU
MPN
VAL-MS-T1/T2 175/12.5 ST
Weight
0.08 kg
This product is Not Cancellable/Not Returnable
Series VAL-MS-T1

VAL-MS-T1/T2 175/12.5 ST - Type 1/2 surge protection plug

L-N replacement plug for VAL-MS-T1/T2 175/12.5 plug-in lighting/surge arrester.

  • Quality proven millions of times over in the widest range of applications
  • Rapid installation with bridges, thanks to industry-standard overall width of 1 HP
  • Easy testing and insulation measurement, thanks to pluggable protection modules
Technical Specifications

Product properties

Product familyVALVETRAB MS
IEC test classificationI / II
IEC test classificationI
IEC test classificationT1 / T2
EN typeT1 / T2
IEC power supply systemTN-C
IEC power supply systemTN-S
IEC power supply systemTT
TypeMale
Surge protection fault messageoptical

Insulation characteristics

Overvoltage categoryIII
Pollution degree2

Electrical properties

Nominal frequency fN50 Hz (60 Hz)
Nominal voltage UN120 V AC

Connection data

Connection Methodpluggable

Dimensions

Width17.5 mm
Height47 mm
Depth67.3 mm
Horizontal pitch1 Div.

Material specifications

Colorblack (RAL 9005)
Colorblack (RAL 9005)
Flammability rating according to UL 94V-0
CTI value of material600
Insulating materialPA 6.6/PBT
Material groupI
Housing MaterialPA 6.6
Housing MaterialPBT

Protective circuit

Mode of protectionL-N
Mode of protectionL-PEN
Direction of actionL-N / L-PEN
Nominal voltage UN120/208 V AC (TN-C, TN-S)
Nominal voltage UN120/208 V AC (TT)
Nominal frequency fN50 Hz (60 Hz)
Maximum continuous voltage UC175 V AC
Residual current IPE≤ 800 µA
Standby power consumption PC≤ 140.00 mVA
Nominal discharge current In (8/20) µs12.5 kA
Maximum discharge current Imax (8/20) µs50 kA
Impulse discharge current (10/350) µs, charge6.25 As
Impulse discharge current (10/350) µs, specific energy39 kJ/Ω
Impulse discharge current (10/350) µs, peak value limp12.5 kA
Short-circuit current rating ISCCR25 kA
Voltage protection level Up≤ 0.8 kV
Residual voltage Ures≤ 0.8 kV (at In)
Residual voltage Ures≤ 0.7 kV (at 10 kA)
Residual voltage Ures≤ 0.6 kV (at 5 kA)
Residual voltage Ures≤ 0.5 kV (at 3 kA)
TOV behavior at UT208 V AC (5 s / withstand mode)
TOV behavior at UT229 V AC (120 min / withstand mode)
Response time tA≤ 25 ns
Max. backup fuse with branch wiring160 A (gG)

Ambient conditions

Degree of ProtectionIP20
Ambient Temperature (Operation)-40 °C ... 80 °C
Ambient temperature (storage/transport)-40 °C ... 80 °C
Altitude≤ 2000 m (amsl)
Permissible humidity (operation)5 % ... 95 %
Shock (operation)30g (Half-sine / 11 ms / 3x ±X, ±Y, ±Z)
Vibration (Operation)7.5g (10 ... 500 Hz / 2.5 h / X, Y, Z)

UL specifications

Maximum continuous operating voltage MCOV (L-N)175 V AC
Nominal discharge current In (L-N)20 kA
Mode of protectionL-N
Nominal Voltage120 V AC
Power distribution systemSingle phase
Nominal frequency50/60 Hz
Measured limiting voltage MLV (L-N)2200 V
SPD Type4CA

Standards and Regulations

Standards/specificationsIEC 61643-11
Note2011
Standards/specificationsEN 61643-11
Note2012

Mounting

Mounting Typeon base element
Accessories

Why Proax for Phoenix Contact 2800676?

Proax is an authorized distributor of Phoenix Contact 2800676 and one of Phoenix Contact's largest distributors in North America. Our highly skilled in-house technical team is ready to assist with any technical needs.

Have a question in mind? to help you get the right product as quickly as possible for your project. We're always here to help!

Short Lead Time
Highly Trained Staff
Live Chat
Technical Support
Local Inventory
60+ Years Experience
Additional Information

Pack Size10
Recommended
Sold in quantities of 10

Not in stock

Request lead time or order—we'll ensure quick delivery

Phoenix Contact Availability