Series VAL-MS-T1

VAL-MS-T1/T2 175/12.5/3+0-FM - Lightning/surge arrester type 1/2

Universal varistor-based plug-in lightning/surge arrester for 3-phase power supply networks with common N and PE (4-conductor system: L1, L2, L3, PEN), with remote indication contact.

Technical Specifications

General

NoteNominal voltage UN = 120 V AC/240 V AC split-phase (separate GND)

Product properties

Product familyVALVETRAB MS
IEC test classificationI / II
IEC test classificationT1 / T2
EN typeT1 / T2
IEC power supply systemTN-C
TypeDIN rail module, two-section, divisible
Surge protection fault messageOptical, remote indicator contact

Insulation characteristics

Overvoltage categoryIII
Pollution degree2

Electrical properties

Nominal frequency fN50 Hz (60 Hz)

Indicator/remote signaling

Connection nameRemote fault indicator contact
Switching functionChangeover contact
Operating Voltage5 V AC ... 250 V AC
Operating Voltage30 V DC
Operating current5 mA AC ... 1.5 A AC
Operating current1 A DC

Connection data

Connection MethodScrew connection
Screw threadM5
Tightening torque3 Nm (1.5 mm² ... 16 mm²)
Tightening torque4.5 Nm (25 mm² ... 35 mm²)
Stripping length16 mm
Conductor cross section flexible1.5 mm² ... 25 mm²
Conductor cross section rigid1.5 mm² ... 35 mm²
Conductor cross section AWG15 ... 2
Connection MethodFork-type cable lug
Conductor cross section flexible1.5 mm² ... 16 mm²

Remote fault indicator contact

Connection MethodPlug-in/screw connection via COMBICON
Screw threadM2
Tightening torque0.25 Nm
Stripping length7 mm
Conductor cross section flexible0.14 mm² ... 1.5 mm²
Conductor cross section rigid0.14 mm² ... 1.5 mm²
Conductor cross section AWG28 ... 16

Dimensions

Width53.4 mm
Height98.7 mm
Depth77.5 mm (incl. DIN rail 7.5 mm)
Horizontal pitch3 Div.

Material specifications

Flammability rating according to UL 94V-0
CTI value of material600
Insulating materialPA 6.6/PBT
Material groupI
Housing MaterialPA 6.6
Housing MaterialPBT

Mechanical data

Open side panelNo

Protective circuit

Mode of protectionL-PEN
Direction of action3L-PEN
Nominal voltage UN120/208 V AC (TN-C)
Nominal frequency fN50 Hz (60 Hz)
Maximum continuous voltage UC175 V AC
Rated load current IL80 A
Residual current IPE≤ 2400 µA
Standby power consumption PC≤ 420.00 mVA
Nominal discharge current In (8/20) µs12.5 kA
Maximum discharge current Imax (8/20) µs50 kA
Impulse discharge current (10/350) µs, charge6.25 As
Impulse discharge current (10/350) µs, specific energy39 kJ/Ω
Impulse discharge current (10/350) µs, peak value limp12.5 kA
Total discharge current Itotal (8/20) µs150 kA
Total discharge current Itotal (10/350) µs37.5 kA
Short-circuit current rating ISCCR25 kA
Voltage protection level Up≤ 0.8 kV
Residual voltage Ures≤ 0.8 kV (at In)
Residual voltage Ures≤ 0.7 kV (at 10 kA)
Residual voltage Ures≤ 0.6 kV (at 5 kA)
Residual voltage Ures≤ 0.55 kV (at 3 kA)
TOV behavior at UT208 V AC (5 s / withstand mode)
TOV behavior at UT229 V AC (120 min / withstand mode)
Response time tA≤ 25 ns
Max. backup fuse with V-type through wiring80 A (gG - 16 mm²)
Max. backup fuse with branch wiring160 A (gG)

Ambient conditions

Degree of ProtectionIP20 (only when all terminal points are used)
Ambient Temperature (Operation)-40 °C ... 80 °C
Ambient temperature (storage/transport)-40 °C ... 80 °C
Altitude≤ 2000 m (amsl)
Permissible humidity (operation)5 % ... 95 %
Shock (operation)30g (Half-sine / 11 ms / 3x ±X, ±Y, ±Z)
Vibration (Operation)7.5g (10 ... 500 Hz / 2.5 h / X, Y, Z)

UL specifications

Maximum continuous operating voltage MCOV (L-L)350 V AC
Maximum continuous operating voltage MCOV (L-G)175 V AC
Nominal discharge current In (L-L)20 kA
Nominal discharge current In (L-G)20 kA
Mode of protectionL-L
Mode of protectionL-G
Nominal Voltage208/120 V AC
Power distribution systemWye
Nominal frequency50/60 Hz
Measured limiting voltage MLV (L-L)2800 V
Measured limiting voltage MLV (L-G)2200 V
SPD Type4CA

UL indicator/remote signaling

Operating Voltage125 V AC
AC operating current1 A AC

UL connection data

Tightening torque30 lbf-in.
Conductor cross section AWG10 ... 2

Standards and Regulations

Standards/specificationsIEC 61643-11
Note2011
Standards/specificationsEN 61643-11
Note2012

Mounting

Mounting TypeDIN rail: 35 mm
Accessories

Why Proax for Phoenix Contact VAL-MS-T1/T2 175/12.5/3+0-FM?

Proax is an authorized distributor of Phoenix Contact VAL-MS-T1/T2 175/12.5/3+0-FM and one of Phoenix Contact's largest distributors in North America. Our highly skilled in-house technical team is ready to assist with any technical needs.

Have a question in mind? to help you get the right product as quickly as possible for your project. We're always here to help!

Short Lead Time
Highly Trained Staff
Live Chat
Technical Support
Local Inventory
60+ Years Experience
Additional Information

Alternate NamesVALMST1T217512530FM
Pack Size1
Recommended

Available for order