Official Distributor
SKU
MPN
PSR-MC50-3NO-1DO-24DC-SP
Weight
0.175 kg
This product is Not Cancellable/Not Returnable
Series PSR-MC
PSR-MC50-3NO-1DO-24DC-SP - Safety relays
Safety relay for monitoring non-equivalent signal generators up to SIL 3, Cat. 4, PL e, 2-channel, non-equivalent operation, automatic or manual, monitored start, 3 enabling current paths, US = 24 V DC, pluggable Push-in terminal block
- Up to Cat. 4/PL e in accordance with EN ISO 13849-1, SIL 3 in accordance with EN IEC 62061
- Low housing width of just 12.5 mm
- Two-channel non-equivalent control
- 3 enabling current paths, 1 digital signal output
- Manually monitored and automatic activation in a single device
Technical Specifications
Product properties
Product family | PSRmini |
Application | Antivalent signal generator |
Application | Safety door |
Application | Solenoid switch |
Relay type | Electromechanical relay with force-guided contacts in accordance with IEC/EN 61810-3 |
Times
Typical response time | < 175 ms (automatic start) |
Typical response time | < 175 ms (manual, monitored start) |
Typ. starting time with Us | < 250 ms (when controlled via A1) |
Typical release time | < 20 ms (when controlled via A1 or S12 and S13.) |
Recovery time | < 500 ms |
Electrical properties
Maximum power dissipation for nominal condition | 4.8 W (US = 26.4 V, IL² = 48 A², PTotal max = 2.4 W + 2.4 W) |
Nominal operating mode | 100% operating factor |
Air clearances and creepage distances between the power circuits
Rated Insulation Voltage | 250 V AC |
Rated Insulation Voltage | 250 V AC |
Rated surge voltage/insulation | Safe isolation, reinforced insulation 6 kV between input circuit and enabling current path (13/14) and enabling current path (23/24) and enabling current path (33/34)Basic insulation 4 kV between all current paths and housing |
Supply
Designation | A1/A2 |
Rated control circuit supply voltage US | 20.4 V DC ... 26.4 V DC |
Rated control circuit supply voltage US | 24 V DC -15 % / +10 % |
Rated control supply current IS | typ. 80 mA |
Power consumption at US | typ. 1.92 W |
Inrush Current | 5 A (Δt = 200 µs at Us) |
Filter time | 1 ms (at A1 in the event of voltage dips at Us) |
Protective circuit | Surge protection; Suppressor diode |
Protective circuit | Protection against polarity reversal for rated control circuit supply voltage |
Digital: Sensor circuit (S12, S13)
Description of the input | safety-related sensor inputs |
Input voltage range "0" signal | 0 V DC ... 5 V DC (for safe Off; at S12) |
Input current range "0" signal | 0 mA ... 2 mA (for safe Off; at S12) |
Inrush Current | < 20 mA (with Us/Ix to S12) |
Inrush Current | < 5 mA (with Us/Ix to S13) |
Filter time | max. 1.5 ms (at S12, S13; test pulse width) |
Filter time | min. 7.5 ms (at S12, S13; test pulse rate) |
Filter time | Test pulse rate = 5 x Test pulse width |
Max. permissible overall conductor resistance | 150 Ω |
Current consumption | < 5 mA (with Us/Ix to S12) |
Current consumption | < 5 mA (with Us/Ix to S13) |
Digital: Start circuit (S34)
Description of the input | non-safety-related |
Number of Inputs | 1 |
Input voltage range "1" signal | 20.4 V DC ... 26.4 V DC |
Inrush Current | typ. 200 mA |
Max. permissible overall conductor resistance | 150 Ω |
Protective circuit | Suppressor diode |
Current consumption | < 10 mA (at S34/24 V) |
Current consumption | > -5 mA (at S34/0 V) |
Relay: Enabling current paths (13/14, 23/24, 33/34)
Output description | safety-related N/O contacts |
Number of Outputs | 3 (undelayed) |
Contact switching type | 3 enabling current paths |
Contact Material | AgSnO2 |
Switching voltage | min. 12 V AC/DC |
Switching voltage | max. 250 V AC/DC (Observe the load curve) |
Switching capacity | min. 60 mW |
Inrush Current | min. 3 mA |
Inrush Current | max. 6 A |
Limiting Continuous Current | 6 A (observe derating) |
Sq. Total current | 48 A2 (observe derating) |
Switching frequency | 0.5 Hz |
Mechanical service life | 10x 106 cycles |
Output fuse | 6 A gL/gG (N/O contact) |
Output fuse | 4 A gL/gG (for low-demand applications) |
Signal: M1
Output description | non-safety-related |
Number of Outputs | 1 (digital, PNP) |
Voltage | 22 V DC (Us - 2 V) |
Current | max. 100 mA |
Maximum Inrush Current | 500 mA (Δt = 1 ms at Us) |
Short-circuit protection | no |
Connection technology
pluggable | yes |
Conductor connection
Connection Method | Push-in connection |
Conductor cross section rigid | 0.2 mm² ... 1.5 mm² |
Conductor cross section flexible | 0.2 mm² ... 1.5 mm² |
Conductor cross section, flexible, with ferrule, with plastic sleeve | 0.25 mm² ... 1.5 mm² (only together with CRIMPFOX 6) |
Conductor cross section flexible, with ferrule without plastic sleeve | 0.25 mm² ... 1.5 mm² (only together with CRIMPFOX 6) |
Conductor cross-section AWG | 24 ... 16 |
Stripping length | 8 mm |
Signaling
Status display | 3 x green LED |
Operating voltage display | 1 x green LED |
Dimensions
Width | 12.5 mm |
Height | 116.6 mm |
Depth | 114.5 mm |
Material specifications
Color (Housing) | yellow (RAL 1018) |
Housing Material | Polyamide |
Safety data
Stop category | 0 |
Safety data: EN ISO 13849
Category | 4 |
Performance level (PL) | e (4 A DC13; 5 A AC15; 8760 switching cycles/year) |
Safety data: IEC 61508 - High demand
Safety Integrity Level (SIL) | 3 |
Safety data: IEC 61508 - Low demand
Safety Integrity Level (SIL) | 3 |
Safety data: EN IEC 62061
Safety Integrity Level (SIL) | 3 |
Ambient conditions
Degree of Protection | IP20 |
Min. degree of protection of inst. location | IP54 |
Ambient Temperature (Operation) | -40 °C ... 55 °C (observe derating) |
Ambient temperature (storage/transport) | -40 °C ... 85 °C |
Maximum altitude | ≤ 2000 m (Above sea level) |
Max. permissible humidity (storage/transport) | 75 % (on average, 85% infrequently, non-condensing) |
Max. permissible relative humidity (operation) | 75 % (on average, 85% infrequently, non-condensing) |
Shock | 15g |
Vibration (Operation) | 10 Hz ... 150 Hz, 2g |
CE
Identification | CE-compliant |
Air clearances and creepage distances between the power circuits
Standards/regulations | EN 60947-1 |
Mounting
Mounting Type | DIN rail mounting |
Assembly instructions | See derating curve |
Mounting Position | vertical or horizontal |
Why Proax for Phoenix Contact 2700564?
Proax is an authorized distributor of Phoenix Contact 2700564 and one of Phoenix Contact's largest distributors in North America. Our highly skilled in-house technical team is ready to assist with any technical needs.
Have a question in mind? to help you get the right product as quickly as possible for your project. We're always here to help!
Short Lead Time
Highly Trained Staff
Live Chat
Technical Support
Local Inventory
60+ Years Experience
Additional Information
Pack Size | 1 |
Recommended