Proax

Currency
0 Items
proax logo
Cart
Phoenix ContactOfficial Distributor

By Phoenix Contact

SKU
MPN
TRIO-PS67/1AC/24DC/3.75/IPD
Series TRIO-PS

TRIO-PS67/1AC/24DC/3.75/IPD - Power supply unit

Primary-switched power supply unit TRIO POWER, IPD panel feed-through with Push-in spring connection, Wall mounting, input: 1-phase, output: 24 V DC / 3.75 A

Technical Specifications

AC operation

Supply system configurationStar network (TN, TT, IT (PE))
Nominal input voltage range100 V AC ... 277 V AC
Input voltage range100 V AC ... 277 V AC -15 % ... +10 %
Input voltage range115 V AC ... 277 V AC ±10 % (UL)
Derating< 100 V AC ... 85 V AC (1 %/V)
Switch-on voltage≥ 80 V AC
Shut-down voltage< 75 V AC
Typical national grid voltage120 V AC
Typical national grid voltage230 V AC
Voltage type of supply voltageAC/DC
Inrush Current≤ 35 A (typical, 277 V AC)
Inrush Current17 A (typical, 120 V AC)
Inrush current integral (I2t)< 0.45 A2s
AC frequency range50 Hz ... 60 Hz ±10 %
Frequency range (fN)50 Hz ... 60 Hz ±10 %
Mains buffering time> 25 ms (120 V AC)
Mains buffering time> 25 ms (230 V AC)
Current consumption1 A (100 V AC)
Current consumption0.4 A (277 V AC)
Protective circuitTransient surge protection; Varistor
Power factor (cos phi)> 0.92
Switch-on time< 0.2 s
Input fuse4 A (internal (device protection))
Recommended breaker for input protection6 A ... 16 A (Characteristic B, C, D, K or comparable)
Discharge current to PE< 0.5 mA

DC operation

Nominal input voltage range110 V DC ... 250 V DC
Input voltage range110 V DC ... 250 V DC -20 % ... +10 %
Input voltage range120 V DC ... 250 V DC ±10 % (UL)
Derating< 110 V DC ... 88 V DC (1 %/V)
Switch-on voltage≥ 75 V DC
Shut-down voltage< 70 V DC
Voltage type of supply voltageAC/DC
Current consumption0.88 A (110 V DC)
Current consumption0.38 A (250 V DC)

Output data

Efficiencytyp. 93 % (120 V AC)
Efficiencytyp. 94 % (230 V AC)
Nominal Output Voltage24 V DC ±2 %
Nominal output current (IN)3.75 A (Class 2 Output)
Derating> 60 °C ... 70 °C (2.0 %/K)
Feedback voltage resistance≤ 35 V DC
Protection against overvoltage at the output (OVP)≤ 35 V DC
Control deviation< 1 % (change in load, static 10 % ... 90 %)
Control deviation< 3 % (Dynamic load change 10 % ... 90 %, 10 Hz)
Control deviation< 0.1 % (change in input voltage ±10 %)
Residual ripple≤ 10 mVPP
Short-circuit-proofyes
No-load proofyes
Output Power90 W
Peak switching voltages nominal load< 100 mV
Maximum no-load power dissipation< 0.25 W (120 V AC)
Maximum no-load power dissipation< 0.28 W (230 V AC)
Power loss nominal load max.< 7.4 W (120 V AC)
Power loss nominal load max.< 6 W (230 V AC)
Rise timetyp. 100 ms (UOUT (10 % ... 90 %))
Connection in parallelyes, for increasing power and redundancy with diode
Connection in seriesyes, for increased output voltage

Signal: DC OK

Continuous load current100 mA

Input

Connection MethodIPD panel feed-through with Push-in spring connection
Conductor cross section, rigid min.0.5 mm²
Conductor cross section, rigid max.2.5 mm²
Conductor cross section flexible min.0.5 mm²
Conductor cross section flexible max.2.5 mm²
Single conductor/terminal point, stranded, with ferrule, min.0.5 mm²
Single conductor/terminal point, stranded, with ferrule, max.2.5 mm²
Conductor cross section AWG max.14
Color-codedgray
Type of lockingClip locking
Number of Positions3

Output

Connection MethodIPD panel feed-through with Push-in spring connection
Conductor cross section, rigid min.0.5 mm²
Conductor cross section, rigid max.2.5 mm²
Conductor cross section flexible min.0.5 mm²
Conductor cross section flexible max.2.5 mm²
Single conductor/terminal point, stranded, with ferrule, min.0.5 mm²
Single conductor/terminal point, stranded, with ferrule, max.2.5 mm²
Conductor cross section AWG max.14
Color-codedblack
Type of lockingClip locking
Number of Positions3

Signaling

Types of signalingLED
Status display2 x green LEDs

Signal output: LED status indicator

Signalization designationAC OK
Status displayLED
Colorgreen
AC OKACIn > 0.76 x ACN (ACN = 100 V AC)
Signalization designationDC OK
Status displayLED
Colorgreen
DC OKUOUT > 0.9 x UN (UN = 24 V DC)

Electrical properties

Number of phases1.00
Insulation voltage input/output4 kV AC (type test)
Insulation voltage input/output3 kV AC (routine test)

Product properties

Product familyTRIO POWER
MTBF (IEC 61709, SN 29500)> 1475000 h (25 °C)
MTBF (IEC 61709, SN 29500)> 1000000 h (40 °C)
MTBF (IEC 61709, SN 29500)> 500000 h (60 °C)

Insulation characteristics

Protection classI
Pollution degree2 (IEC 61010-1)

Item dimensions

Width100 mm
Height222 mm
Depth53 mm

Drill hole

Diameter4.2 mm

Installation dimensions

Installation distance right/left20 mm / 20 mm
Installation distance top/bottom50 mm / 100 mm

Mounting

Mounting TypeWall mounting
Assembly instructionsAlignable: 20 mm horizontally, 20 mm vertically above, 20 mm vertically below
With protective coatingNo

Material specifications

Flammability rating according to UL 94 (housing / terminal blocks)V0
Housing MaterialMetal
Type of housingAluminum (AlMg3)

Ambient conditions

Degree of ProtectionIP67
Ambient Temperature (Operation)-25 °C ... 70 °C (Derating > 60 °C: 2 %/K)
Ambient temperature (storage/transport)-40 °C ... 85 °C
Maximum altitude≤ 4000 m (> 2000 m, Derating: 10 %/1000 m)
Climatic class4K26 (EN 60721-3-4)
Max. permissible relative humidity (operation)≤ 100 % (at 25 °C, non-condensing)
Permissible humidity (operation)≤ 100 % (at 25 °C, non-condensing)
Shock18 ms, 30g, in each space direction (according to IEC 60068-2-27)
Vibration (Operation)10 Hz ... 59.6 Hz, amplitude ±0.35 mm (in accordance with IEC 60068-2-6)
Vibration (Operation)59.6 Hz ... 150 Hz, 5g, 20 cycles

Overvoltage category

EN 61010-1II (≤ 4000 m)
EN 62477-1III (≤ 2000 m)

Electrical safety

Standard designationElectrical safety
Standards/specificationsIEC 61010-1 (SELV)

Protective extra-low voltage

Standard designationProtective extra-low voltage
Standards/specificationsIEC 61010-1 (SELV)
Standards/specificationsIEC 61010-2-201 (PELV)

Low-voltage power supplies, DC output

Standard designationLow-voltage power supplies, DC output
Standards/specificationsEN 61204-3

Safety requirements for electrical equipment for measurement, control, and laboratory use

Standard designationSafety requirements for electrical equipment for measurement, control, and laboratory use
Standards/specificationsIEC 61010-1

Limit values for harmonic currents

Standard designationLimit values for harmonic currents
Standards/specificationsEN 61000-3-2

Degrees of protection provided by enclosures (IP code)

Standard designationDegrees of protection provided by enclosures (IP code)
Standards/specificationsEN/IEC 60529

Mains variation/undervoltage

Standard designationMains variation/undervoltage
Standards/specificationsSEMI F47 - 0706

UL

IdentificationNEC Class 2 according to UL 1310
IdentificationUL/C-UL Listed UL 61010-1
IdentificationUL/C-UL Listed UL 61010-2-201

EMC data

Low Voltage DirectiveConformance with Low Voltage Directive 2014/35/EC
Interference emissionInterference emission in accordance with EN 61000-6-3 (residential and commercial) and EN 61000-6-4 (industrial)
Noise immunityImmunity in accordance with EN 61000-6-1 (residential), EN 61000-6-2 (industrial)
Electromagnetic compatibilityConformance with EMC Directive 2014/30/EU
Conducted noise emissionEN 55016
Conducted noise emissionEN 61000-6-3 (Class B)
Noise emissionEN 55011 (EN 55022)
Noise emissionEN 55016
Noise emissionEN 61000-6-3 (Class B)

Harmonic currents

Standards/regulationsEN 61000-3-2
Standards/regulationsEN 61000-3-2 (Class A)

Electrostatic discharge

Standards/regulationsEN 61000-4-2
Contact discharge6 kV (Test Level 3)
CommentsCriterion A

Electromagnetic HF field

Standards/regulationsEN 61000-4-3
Frequency Range80 MHz ... 1 GHz
Test field strength10 V/m (Test Level 3)
Frequency Range1 GHz ... 2 GHz
Test field strength10 V/m (Test Level 3)
Frequency Range2 GHz ... 6 GHz
Test field strength10 V/m (Test Level 3)
CommentsCriterion A

Fast transients (burst)

Standards/regulationsEN 61000-4-4
Input4 kV (Test Level 3 - asymmetrical)
Output2 kV (Test Level 3 - asymmetrical)
CommentsCriterion A

Surge voltage load (surge)

Standards/regulationsEN 61000-4-5
Input1 kV (Test Level 1 - symmetrical)
Input2 kV (Test Level 1 - asymmetrical)
Output0.5 kV (Test Level 1 - symmetrical)
Output0.5 kV (Test Level 1 - asymmetrical)
CommentsCriterion B

Conducted interference

Standards/regulationsEN 61000-4-6
Input/Outputasymmetrical
Frequency Range0.15 MHz ... 80 MHz
CommentsCriterion A
Voltage10 V (Test Level 3)

Voltage dips

Standards/regulationsEN 61000-4-11
Voltage230 V AC
Frequency50 Hz
Voltage dip70 %
Number of periods25 periods
CommentsCriterion A
Voltage dip40 %
Number of periods10 periods
CommentsCriterion B
Voltage dip0 %
Number of periods1 period
CommentsCriterion A

Emitted interference

Standards/regulationsEN 61000-6-3
Radio interference voltage in acc. with EN 55011EN 55011 (EN 55022) Class B, area of application: Industry and residential
Emitted radio interference in acc. with EN 55011EN 55011 (EN 55022) Class B, area of application: Industry and residential

Criteria

Criterion ANormal operating behavior within the specified limits.
Criterion BTemporary impairment to operational behavior that is corrected by the device itself.
Criterion CTemporary adverse effects on the operating behavior, which the device corrects automatically or which can be restored by actuating the operating elements.

Why Proax for Phoenix Contact 1278301?

Proax is an authorized distributor of Phoenix Contact 1278301 and one of Phoenix Contact's largest distributors in North America. Our highly skilled in-house technical team is ready to assist with any technical needs.

Have a question in mind? to help you get the right product as quickly as possible for your project. We're always here to help!

Short Lead Time
Highly Trained Staff
Live Chat
Technical Support
Local Inventory
60+ Years Experience
Additional Information

Pack Size1
Recommended

Not in stock

Request lead time or order—we'll ensure quick delivery

Phoenix Contact Availability