Official Distributor
SKU
MPN
TRIO-PS67/1AC/24DC/3.75/M12
Weight
0.933 kg
Series TRIO-PS
TRIO-PS67/1AC/24DC/3.75/M12 - Power supply unit
Primary-switched power supply unit TRIO POWER, M12 circular connector, Wall mounting, input: 1-phase, output: 24 V DC / 3.75 A
Technical Specifications
AC operation
Supply system configuration | Star network (TN, TT, IT (PE)) |
Nominal input voltage range | 100 V AC ... 277 V AC |
Input voltage range | 100 V AC ... 277 V AC -15 % ... +10 % |
Input voltage range | 115 V AC ... 277 V AC ±10 % (UL) |
Derating | < 100 V AC ... 85 V AC (1 %/V) |
Switch-on voltage | ≥ 80 V AC |
Shut-down voltage | < 75 V AC |
Typical national grid voltage | 120 V AC |
Typical national grid voltage | 230 V AC |
Voltage type of supply voltage | AC/DC |
Inrush Current | ≤ 35 A (typical, 277 V AC) |
Inrush Current | 17 A (typical, 120 V AC) |
Inrush current integral (I2t) | < 0.45 A2s |
AC frequency range | 50 Hz ... 60 Hz ±10 % |
Frequency range (fN) | 50 Hz ... 60 Hz ±10 % |
Mains buffering time | > 25 ms (120 V AC) |
Mains buffering time | > 25 ms (230 V AC) |
Current consumption | 1 A (100 V AC) |
Current consumption | 0.4 A (277 V AC) |
Protective circuit | Transient surge protection; Varistor |
Power factor (cos phi) | > 0.92 |
Switch-on time | < 0.2 s |
Input fuse | 4 A (internal (device protection)) |
Recommended breaker for input protection | 6 A ... 16 A (Characteristic B, C, D, K or comparable) |
Discharge current to PE | < 0.5 mA |
DC operation
Nominal input voltage range | 110 V DC ... 250 V DC |
Input voltage range | 110 V DC ... 250 V DC -20 % ... +10 % |
Input voltage range | 120 V DC ... 250 V DC ±10 % (UL) |
Derating | < 110 V DC ... 88 V DC (1 %/V) |
Switch-on voltage | ≥ 75 V DC |
Shut-down voltage | < 70 V DC |
Voltage type of supply voltage | AC/DC |
Current consumption | 0.88 A (110 V DC) |
Current consumption | 0.38 A (250 V DC) |
Output data
Efficiency | typ. 93 % (120 V AC) |
Efficiency | typ. 94 % (230 V AC) |
Nominal Output Voltage | 24 V DC ±2 % |
Nominal output current (IN) | 3.75 A (Class 2 Output) |
Derating | > 60 °C ... 70 °C (2.0 %/K) |
Feedback voltage resistance | ≤ 35 V DC |
Protection against overvoltage at the output (OVP) | ≤ 35 V DC |
Control deviation | < 1 % (change in load, static 10 % ... 90 %) |
Control deviation | < 3 % (Dynamic load change 10 % ... 90 %, 10 Hz) |
Control deviation | < 0.1 % (change in input voltage ±10 %) |
Residual ripple | ≤ 10 mVPP |
Short-circuit-proof | yes |
No-load proof | yes |
Output Power | 90 W |
Peak switching voltages nominal load | < 100 mV |
Maximum no-load power dissipation | < 0.25 W (120 V AC) |
Maximum no-load power dissipation | < 0.28 W (230 V AC) |
Power loss nominal load max. | < 7.4 W (120 V AC) |
Power loss nominal load max. | < 6 W (230 V AC) |
Rise time | typ. 100 ms (UOUT (10 % ... 90 %)) |
Connection in parallel | yes, for increasing power and redundancy with diode |
Connection in series | yes, for increased output voltage |
Signal: DC OK
Continuous load current | 100 mA |
Input
Connection Method | M12 circular connector |
Coding | S |
Type of locking | M12 screw locking |
Number of Positions | 3 |
Output
Connection Method | M12 circular connector |
Coding | L |
Type of locking | M12 screw locking |
Number of Positions | 5 |
Signaling
Types of signaling | LED |
Status display | 2 x green LEDs |
Signal output: LED status indicator
Signalization designation | AC OK |
Status display | LED |
Color | green |
AC OK | ACIn > 0.76 x ACN (ACN = 100 V AC) |
Signalization designation | DC OK |
Status display | LED |
Color | green |
DC OK | UOUT > 0.9 x UN (UN = 24 V DC) |
Electrical properties
Number of phases | 1.00 |
Insulation voltage input/output | 4 kV AC (type test) |
Insulation voltage input/output | 3 kV AC (routine test) |
Product properties
Product family | TRIO POWER |
MTBF (IEC 61709, SN 29500) | > 1475000 h (25 °C) |
MTBF (IEC 61709, SN 29500) | > 1000000 h (40 °C) |
MTBF (IEC 61709, SN 29500) | > 500000 h (60 °C) |
Insulation characteristics
Protection class | I |
Pollution degree | 2 (IEC 61010-1) |
Item dimensions
Width | 100 mm |
Height | 164 mm |
Depth | 53 mm |
Drill hole
Diameter | 4.2 mm |
Installation dimensions
Installation distance right/left | 20 mm / 20 mm |
Installation distance top/bottom | 20 mm / 20 mm |
Mounting
Mounting Type | Wall mounting |
Assembly instructions | Alignable: 20 mm horizontally, 20 mm vertically above, 20 mm vertically below |
With protective coating | No |
Material specifications
Flammability rating according to UL 94 (housing / terminal blocks) | V0 |
Housing Material | Metal |
Type of housing | Aluminum (AlMg3) |
Ambient conditions
Degree of Protection | IP67 |
Ambient Temperature (Operation) | -25 °C ... 70 °C (Derating > 60 °C: 2 %/K) |
Ambient temperature (storage/transport) | -40 °C ... 85 °C |
Maximum altitude | ≤ 4000 m (> 2000 m, Derating: 10 %/1000 m) |
Climatic class | 4K26 (EN 60721-3-4) |
Max. permissible relative humidity (operation) | ≤ 100 % (at 25 °C, non-condensing) |
Permissible humidity (operation) | ≤ 100 % (at 25 °C, non-condensing) |
Shock | 18 ms, 30g, in each space direction (according to IEC 60068-2-27) |
Vibration (Operation) | 10 Hz ... 59.6 Hz, amplitude ±0.35 mm (in accordance with IEC 60068-2-6) |
Vibration (Operation) | 59.6 Hz ... 150 Hz, 5g, 20 cycles |
Overvoltage category
EN 61010-1 | II (≤ 4000 m) |
EN 62477-1 | III (≤ 2000 m) |
Electrical safety
Standard designation | Electrical safety |
Standards/specifications | IEC 61010-1 |
Protective extra-low voltage
Standard designation | Protective extra-low voltage |
Standards/specifications | IEC 61010-1 (SELV) |
Standards/specifications | IEC 61010-2-201 (PELV) |
Low-voltage power supplies, DC output
Standard designation | Low-voltage power supplies, DC output |
Standards/specifications | EN 61204-3 |
Safety requirements for electrical equipment for measurement, control, and laboratory use
Standard designation | Safety requirements for electrical equipment for measurement, control, and laboratory use |
Standards/specifications | IEC 61010-1 |
Limit values for harmonic currents
Standard designation | Limit values for harmonic currents |
Standards/specifications | EN 61000-3-2 |
Degrees of protection provided by enclosures (IP code)
Standard designation | Degrees of protection provided by enclosures (IP code) |
Standards/specifications | EN/IEC 60529 |
Mains variation/undervoltage
Standard designation | Mains variation/undervoltage |
Standards/specifications | SEMI F47 - 0706 |
UL
Identification | NEC Class 2 according to UL 1310 |
Identification | UL/C-UL Listed UL 61010-1 |
Identification | UL/C-UL Listed UL 61010-2-201 |
EMC data
Low Voltage Directive | Conformance with Low Voltage Directive 2014/35/EC |
Interference emission | Interference emission in accordance with EN 61000-6-3 (residential and commercial) and EN 61000-6-4 (industrial) |
Noise immunity | Immunity in accordance with EN 61000-6-1 (residential), EN 61000-6-2 (industrial) |
Electromagnetic compatibility | Conformance with EMC Directive 2014/30/EU |
Conducted noise emission | EN 55016 |
Conducted noise emission | EN 61000-6-3 (Class B) |
Noise emission | EN 55011 (EN 55022) |
Noise emission | EN 55016 |
Noise emission | EN 61000-6-3 (Class B) |
Harmonic currents
Standards/regulations | EN 61000-3-2 |
Standards/regulations | EN 61000-3-2 (Class A) |
Electrostatic discharge
Standards/regulations | EN 61000-4-2 |
Contact discharge | 6 kV (Test Level 3) |
Comments | Criterion A |
Electromagnetic HF field
Standards/regulations | EN 61000-4-3 |
Frequency Range | 80 MHz ... 1 GHz |
Test field strength | 10 V/m (Test Level 3) |
Frequency Range | 1 GHz ... 2 GHz |
Test field strength | 10 V/m (Test Level 3) |
Frequency Range | 2 GHz ... 6 GHz |
Test field strength | 10 V/m (Test Level 3) |
Comments | Criterion A |
Fast transients (burst)
Standards/regulations | EN 61000-4-4 |
Input | 4 kV (Test Level 3 - asymmetrical) |
Output | 2 kV (Test Level 3 - asymmetrical) |
Comments | Criterion A |
Surge voltage load (surge)
Standards/regulations | EN 61000-4-5 |
Input | 1 kV (Test Level 1 - symmetrical) |
Input | 2 kV (Test Level 1 - asymmetrical) |
Output | 0.5 kV (Test Level 1 - symmetrical) |
Output | 0.5 kV (Test Level 1 - asymmetrical) |
Comments | Criterion B |
Conducted interference
Standards/regulations | EN 61000-4-6 |
Input/Output | asymmetrical |
Frequency Range | 0.15 MHz ... 80 MHz |
Comments | Criterion A |
Voltage | 10 V (Test Level 3) |
Voltage dips
Standards/regulations | EN 61000-4-11 |
Voltage | 230 V AC |
Frequency | 50 Hz |
Voltage dip | 70 % |
Number of periods | 25 periods |
Comments | Criterion A |
Voltage dip | 40 % |
Number of periods | 10 periods |
Comments | Criterion B |
Voltage dip | 0 % |
Number of periods | 1 period |
Comments | Criterion A |
Emitted interference
Standards/regulations | EN 61000-6-3 |
Radio interference voltage in acc. with EN 55011 | EN 55011 (EN 55022) Class B, area of application: Industry and residential |
Emitted radio interference in acc. with EN 55011 | EN 55011 (EN 55022) Class B, area of application: Industry and residential |
Criteria
Criterion A | Normal operating behavior within the specified limits. |
Criterion B | Temporary impairment to operational behavior that is corrected by the device itself. |
Criterion C | Temporary adverse effects on the operating behavior, which the device corrects automatically or which can be restored by actuating the operating elements. |
Why Proax for Phoenix Contact 1278165?
Proax is an authorized distributor of Phoenix Contact 1278165 and one of Phoenix Contact's largest distributors in North America. Our highly skilled in-house technical team is ready to assist with any technical needs.
Have a question in mind? to help you get the right product as quickly as possible for your project. We're always here to help!
Short Lead Time
Highly Trained Staff
Live Chat
Technical Support
Local Inventory
60+ Years Experience
Additional Information
Pack Size | 1 |
Recommended
- TRIO-PS/3AC/24DC/40, TRIO POWER power supplies with standard functionalityTRIO POWER is particularly suited to standard machine production, thanks to 1- and 3-phase versions up to 960 W. The wide-range input and the international approval package enable worldwide use.The robust metal housing, the high electric strength, and the wide temperature range ensure a high level of power supply reliability.
- TRIO-PS/1AC/48DC/ 5, TRIO POWER power supplies with standard functionalityTRIO POWER is particularly suited to standard machine production, thanks to 1- and 3-phase versions up to 960 W. The wide-range input and the international approval package enable worldwide use.The robust metal housing, the high electric strength, and the wide temperature range ensure a high level of power supply reliability.
- TRIO-PS/1AC/5DC/10, TRIO POWER power supplies with standard functionalityTRIO POWER is particularly suited to standard machine production, thanks to 1- and 3-phase versions up to 960 W. The wide-range input and the international approval package enable worldwide use.The robust metal housing, the high electric strength, and the wide temperature range ensure a high level of power supply reliability.
- TRIO-PS/1AC/12DC/10, TRIO POWER power supplies with standard functionalityTRIO POWER is particularly suited to standard machine production, thanks to 1- and 3-phase versions up to 960 W. The wide-range input and the international approval package enable worldwide use.The robust metal housing, the high electric strength, and the wide temperature range ensure a high level of power supply reliability.