CAPAROC PM IOL - Feed-in module
Power module with IO-Link interface for supplying the CAPAROC circuit breaker system with 12 or 24 V DC for up to 20 channels. For DIN rail installation via the CAPAROC current rails.
- The benchmark that you can customize by selecting single signals and resets all the way to IO-Link and PROFINET communication
- Particularly easy operation for everyone with tool-free assembly, direct feed-in to the busbar, and clear operating states
- Exceptionally easy design-in with the comprehensive digital data packet
Documents
Technical Specifications
Product properties
Product family | CAPAROC |
Number of slots | 2 |
Insulation characteristics
Protection class | III |
Pollution degree | 2 |
General
Operating Voltage | 10 V DC ... 30 V DC |
Rated voltage | 12 V DC |
Rated voltage | 24 V DC |
Rated current IN | 45 A DC (Total current input) |
Tripping method | E (electronic) |
Feedback resistance | max. 35 V DC |
Dielectric strength | 35 V DC (Load circuit) |
Efficiency | > 99 % |
Closed circuit current I0 | typ. 12 mA (no load at 24 V) |
Power dissipation | typ. 0.27 W (no load at 24 V) |
Power dissipation | < 1.5 W (in nominal operation at 24 V and 45 A) |
Temperature derating | 45 A (Total current at 40°C) |
Temperature derating | 30 A (Total current at 65 °C) |
MTBF (IEC 61709, SN 29500) | 13826266.85 h (at 25 °C with 21 % load) |
MTBF (IEC 61709, SN 29500) | 5534344.72 h (at 40°C with 34.25% load) |
MTBF (IEC 61709, SN 29500) | 687502.35 h (at 65°C with 100% load) |
Voltage drop | 5 mV (at 10 A) |
Load circuit
Undervoltage switch-off | ≤ 9.2 V DC (active) |
Undervoltage switch-off | ≥ 10.2 V DC (inactive) |
Overvoltage switch-off | ≥ 30.5 V DC (active) |
Overvoltage switch-off | ≤ 29.5 V DC (inactive) |
Reset
Current consumption | typ. 0.5 mA (at 24 V DC) |
Pulse length | ≥ 50 ms |
Main circuit IN+
Connection Method | Push-in connection |
Stripping length | 18 mm |
Conductor cross section rigid | 0.5 mm² ... 16 mm² |
Conductor cross section AWG | 20 ... 8 |
Conductor cross section, flexible, with ferrule, with plastic sleeve | 0.5 mm² ... 16 mm² |
Conductor cross section flexible, with ferrule without plastic sleeve | 0.5 mm² ... 16 mm² |
Main circuit IN-
Connection Method | Push-in connection |
Stripping length | 18 mm |
Conductor cross section rigid | 0.5 mm² ... 16 mm² |
Conductor cross section AWG | 20 ... 8 |
Conductor cross section, flexible, with ferrule, with plastic sleeve | 0.5 mm² ... 16 mm² |
Conductor cross section flexible, with ferrule without plastic sleeve | 0.5 mm² ... 16 mm² |
IO-Link
Connection Method | Push-in connection |
Stripping length | 8 mm |
Conductor cross section rigid | 0.2 mm² ... 1.5 mm² |
Conductor cross section AWG | 24 ... 16 |
Conductor cross section, flexible, with ferrule, with plastic sleeve | 0.2 mm² ... 0.75 mm² |
Conductor cross section flexible, with ferrule without plastic sleeve | 0.2 mm² ... 1.5 mm² |
Interface type | IO-Link |
Specification | V1.1 |
Reverse polarity protection | yes |
Transmission Speed | 230.4 kbps (COM3) |
Cycle Time | min. 20 ms |
Amount of Process Data | 8 Byte (Input data) |
Amount of Process Data | 3 Byte (Output data) |
Nominal voltage for I/O supply | 24 V DC |
Current consumption | typ. 30 mA (IO-Link L+) |
IO-Link Vendor ID | 176dec, 00 B0hex |
Maximum system extension | ≤ 20 (Channels) |
Signaling
IO-Link LED off | off (No communication) |
IO-Link LED green | flashing (IO-Link connection exists) |
Power (PWR) LED green | lit (Supply voltage OK) |
Power (PWR) LED red | lit (Supply voltage outside the nominal range) |
Power (PWR) LED red | flashing (System topology changed) |
Dimensions
Width | 12.4 mm |
Height | 132.4 mm |
Depth | 111.3 mm (incl. DIN rail 7.5 mm) |
Material specifications
Color | light gray (RAL 7035) |
Material | PA 6 |
Material | PA 6 |
Material | PA 6 |
Material | PC |
Flammability rating according to UL 94 | V-0 |
Ambient conditions
Degree of Protection | IP20 |
Ambient Temperature (Operation) | -30 °C ... 65 °C |
Ambient temperature (storage/transport) | -40 °C ... 70 °C |
Altitude | ≤ 4000 m (amsl) |
Humidity test | 96 h, 95 % RH, 40 °C |
Shock (operation) | 30g (11 ms period, half-sine shock pulse, according to IEC 60068-2-27) |
Shock (operation) | 25g (6 ms duration, half-sine shock pulse in accordance with IEC 60068-2-27, continuous shock) |
Vibration (Operation) | 5g (10 ... 150 Hz / 10 cycles / axis / X, Y, Z) |
UL approval
Identification | UL/C-UL Listed UL 508 |
Corrosive gas test
Identification | ISA S71.04.2013 G3 Harsh Group A |
Standards and Regulations
Standards/specifications | EN 61000-6-2 |
Note | EMC – Immunity for industrial areas |
Standards/specifications | EN 61000-6-3 |
Note | EMC – Emission for residential, business and commercial properties and small operations |
Standards/specifications | EN 60068-2-78 |
Note | Environmental influences – Moisture and heat, constant |
Standards/specifications | EN 50178 |
Note | Equipping power installations with electronic equipment |
Mounting
Mounting Type | pluggable onto CAPAROC CR… current rail |
Why Proax for Phoenix Contact 1115670?
Proax is an authorized distributor of Phoenix Contact 1115670 and one of Phoenix Contact's largest distributors in North America. Our highly skilled in-house technical team is ready to assist with any technical needs.
Have a question in mind? to help you get the right product as quickly as possible for your project. We're always here to help!
Short Lead Time
Highly Trained Staff
Live Chat
Technical Support
Local Inventory
60+ Years Experience
Additional Information
Pack Size | 1 |
Recommended