SKU
MPN
FLT-SEC-T1+T2-2IT-350/25-FM
Weight
0.634 kg
Series FLT-SEC-T
FLT-SEC-T1+T2-2IT-350/25-FM - Type 1+2 special combined lightning current and surge arrester
Plug-in lightning and surge protective device combination, in accordance with Type 1+2 / Class I+II, for 2-phase power supply networks in isolated operation (L1, L2, PE).
Technical Specifications
General
Note | Only usable in IT Systems between L-PE, if the exposed-conductive-parts (bodies) of the equipment of the low-voltage installation is connected to the earthing arrangement of the transformer substation (interconnected earthing arrangement of the HV-transformer substation with the bodies of the LV-installation. RE = RA accordance to IEC 60364-4-442 / VDE 0100-442 Fig. 44D / Example a). |
Product properties
Product family | SEC Family |
IEC test classification | I + II |
IEC test classification | T1 + T2 |
EN type | T1 + T2 |
IEC power supply system | IT |
Type | DIN rail module, two-section, divisible |
Surge protection fault message | Optical, remote indicator contact |
Insulation characteristics
Overvoltage category | III |
Pollution degree | 2 |
Electrical properties
Nominal frequency fN | 50 Hz (60 Hz) |
Indicator/remote signaling
Connection name | Remote fault indicator contact |
Switching function | Changeover contact |
Operating Voltage | 12 V AC ... 250 V AC |
Operating Voltage | 125 V DC (200 mA DC) |
Operating current | 10 mA AC ... 1 A AC |
Operating current | 1 A DC (30 V DC) |
Connection data
Connection Method | Screw terminal blocks |
Screw thread | M5 |
Tightening torque | 4.5 Nm |
Stripping length | 18 mm |
Conductor cross section flexible | 2.5 mm² ... 35 mm² |
Conductor cross section rigid | 2.5 mm² ... 35 mm² |
Conductor cross section AWG | 13 ... 2 |
Connection Method | Fork-type cable lug |
Conductor cross section flexible | 1.5 mm² ... 16 mm² |
Remote fault indicator contact
Connection Method | Plug-in/screw connection via COMBICON |
Screw thread | M2 |
Tightening torque | 0.25 Nm |
Stripping length | 7 mm |
Conductor cross section flexible | 0.14 mm² ... 1.5 mm² |
Conductor cross section rigid | 0.14 mm² ... 1.5 mm² |
Conductor cross section AWG | 28 ... 16 |
Dimensions
Width | 71.2 mm |
Height | 95.2 mm |
Depth | 74.5 mm |
Horizontal pitch | 4 Div. |
Material specifications
Color (Male connector) | light grey (RAL 7035) |
Color (Base element) | gray (RAL 7042) |
Flammability rating according to UL 94 | V-0 |
CTI value of material | 600 |
Insulating material | PA6.6-FR 20% GF |
Insulating material | PBT-FR |
Material group | I |
Housing Material | PA 6.6-FR 20 % GF |
Housing Material | PBT-FR |
Mechanical data
Open side panel | No |
Protective circuit
Mode of protection | L-PE |
Mode of protection | L-L |
Direction of action | 2L-PE |
Nominal voltage UN | 240 V AC (IT) |
Nominal frequency fN | 50 Hz (60 Hz) |
Maximum continuous operating voltage UC (L-PE) | 350 V AC |
Rated load current IL | 125 A (< 55 °C) |
Residual current IPE | ≤ 0.5 mA |
Nominal discharge current In (8/20) µs | 25 kA |
Impulse discharge current (10/350) µs, charge | 12.5 As |
Impulse discharge current (10/350) µs, specific energy | 160 kJ/Ω |
Impulse discharge current (10/350) µs, peak value limp | 25 kA |
Follow current interrupt rating Ifi (L-PE) | 25 kA (264 V AC) |
Follow current interrupt rating Ifi (L-PE) | 3 kA (350 V AC) |
Short-circuit current rating ISCCR | 25 kA (264 V AC) |
Short-circuit current rating ISCCR | 3 kA (350 V AC) |
Voltage protection level Up (L-L) | ≤ 1.5 kV (L1-L2) |
Voltage protection level Up (L-PE) | ≤ 2.8 kV (L1-PE) |
Voltage protection level Up (L-PE) | ≤ 1.5 kV (L2-PE) |
Residual voltage Ures (L-L) | ≤ 1.5 kV (at In / L1-L2) |
Residual voltage Ures (L-L) | ≤ 1.2 kV (at 10 kA / L1-L2) |
Residual voltage Ures (L-L) | ≤ 1 kV (at 5 kA / L1-L2) |
Residual voltage Ures (L-L) | ≤ 0.9 kV (at 3 kA / L1-L2) |
Residual voltage Ures (L-PE) | ≤ 2.8 kV (at In / L1-PE) |
Residual voltage Ures (L-PE) | ≤ 2.4 kV (at 10 kA / L1-PE) |
Residual voltage Ures (L-PE) | ≤ 2 kV (at 5 kA / L1-PE) |
Residual voltage Ures (L-PE) | ≤ 1.8 kV (at 3 kA / L1-PE) |
Residual voltage Ures (L-PE) | ≤ 1.5 kV (at In / L2-PE) |
Residual voltage Ures (L-PE) | ≤ 1.2 kV (at 10 kA / L2-PE) |
Residual voltage Ures (L-PE) | ≤ 1 kV (at 5 kA / L2-PE) |
Residual voltage Ures (L-PE) | ≤ 0.9 kV (at 3 kA / L2-PE) |
TOV behavior at UT (L-PE) | 415 V AC (5 s / withstand mode) |
Response time tA | ≤ 25 ns |
Max. backup fuse with V-type through wiring | 125 A (gG) |
Max. backup fuse with branch wiring | 315 A (gG) |
Ambient conditions
Degree of Protection | IP20 (only when all terminal points are used) |
Ambient Temperature (Operation) | -40 °C ... 80 °C |
Ambient temperature (storage/transport) | -40 °C ... 80 °C |
Altitude | ≤ 2000 m (amsl) |
Permissible humidity (operation) | 5 % ... 95 % |
Shock (operation) | 25g (Half-sine / 11 ms / 3x ±X, ±Y, ±Z) |
Vibration (Operation) | 5g (5 - 500 Hz/2.5 h/X, Y, Z) |
Standards and Regulations
Standards/specifications | IEC 61643-11 |
Note | 2011 |
EN 61643-11
Standards/specifications | EN 61643-11 |
Note | 2012 |
Mounting
Mounting Type | DIN rail: 35 mm |
Accessories
Why Proax for Phoenix Contact 1044388?
Proax is an authorized distributor of Phoenix Contact 1044388 and one of Phoenix Contact's largest distributors in North America. Our highly skilled in-house technical team is ready to assist with any technical needs.
Have a question in mind? to help you get the right product as quickly as possible for your project. We're always here to help!
Short Lead Time
Highly Trained Staff
Live Chat
Technical Support
Local Inventory
60+ Years Experience
Additional Information
Pack Size | 1 |