Series FLT-SEC-T

FLT-SEC-T1+T2-3IT-350/25-FM - Type 1+2 special combined lightning current and surge arrester

Plug-in lightning and surge protective device combination, in accordance with Type 1+2 / Class I+II, for 3-phase power supply networks in isolated operation with separate N and PE (L1, L2, L3, N, PE).

Technical Specifications

General

NoteUsable in all low-voltage systems between L-N or L-PEN.Only usable in IT Systems between L-PE, if the exposed-conductive-parts (bodies) of the equipment of the low-voltage installation is connected to the earthing arrangement of the transformer substation. (interconnected earthing arrangement of the HV-transformer substation with the bodies of the LV-installation. RE = RA accordance to IEC 60364-4-442 / VDE 0100-442 Fig. 44D / Example a)

Product properties

Product familySEC Family
IEC test classificationI + II
IEC test classificationT1 + T2
EN typeT1 + T2
IEC power supply systemIT
TypeDIN rail module, two-section, divisible
Number of Positions4
Surge protection fault messageOptical, remote indicator contact

Insulation characteristics

Overvoltage categoryIII
Pollution degree2

Electrical properties

Nominal frequency fN50 Hz (60 Hz)

Indicator/remote signaling

Connection nameRemote fault indicator contact
Switching functionChangeover contact
Operating Voltage12 V AC ... 250 V AC
Operating Voltage125 V DC (200 mA DC)
Operating current10 mA AC ... 1 A AC
Operating current1 A DC (30 V DC)

Connection data

Connection MethodScrew terminal blocks
Screw threadM5
Tightening torque4.5 Nm
Stripping length18 mm
Conductor cross section flexible2.5 mm² ... 35 mm²
Conductor cross section rigid2.5 mm² ... 35 mm²
Conductor cross section AWG13 ... 2
Connection MethodFork-type cable lug
Conductor cross section flexible1.5 mm² ... 16 mm²

Remote fault indicator contact

Connection MethodPlug-in/screw connection via COMBICON
Screw threadM2
Tightening torque0.25 Nm
Stripping length7 mm
Conductor cross section flexible0.14 mm² ... 1.5 mm²
Conductor cross section rigid0.14 mm² ... 1.5 mm²
Conductor cross section AWG28 ... 16

Dimensions

Width142.4 mm
Height95.2 mm
Depth74.5 mm
Horizontal pitch8 Div.

Material specifications

Color (Male connector)light grey (RAL 7035)
Color (Base element)gray (RAL 7042)
Flammability rating according to UL 94V-0
CTI value of material600
Insulating materialPA6.6-FR 20% GF
Insulating materialPBT-FR
Material groupI
Housing MaterialPA 6.6-FR 20 % GF
Housing MaterialPBT-FR

Mechanical data

Open side panelNo

Protective circuit

Mode of protectionL-N
Mode of protectionL-PE
Mode of protectionN-PE
Direction of action3L-N & N-PE
Nominal voltage UN240/415 V AC (IT)
Nominal frequency fN50 Hz (60 Hz)
Maximum continuous voltage UC350 V AC
Rated load current IL125 A (< 55 °C)
Residual current IPE≤ 0.5 mA
Nominal discharge current In (8/20) µs25 kA
Impulse discharge current (10/350) µs, charge12.5 As
Impulse discharge current (10/350) µs, specific energy160 kJ/Ω
Impulse discharge current (10/350) µs, peak value limp25 kA
Follow current interrupt rating Ifi25 kA (264 V AC)
Follow current interrupt rating Ifi3 kA (350 V AC)
Short-circuit current rating ISCCR25 kA (264 V AC)
Short-circuit current rating ISCCR3 kA (350 V AC)
Voltage protection level Up (L-N)≤ 1.5 kV
Voltage protection level Up (L-PE)≤ 2.8 kV
Voltage protection level Up (N-PE)≤ 1.5 kV
Residual voltage Ures (L-N)≤ 1.5 kV (at In)
Residual voltage Ures (L-N)≤ 1.2 kV (at 10 kA)
Residual voltage Ures (L-N)≤ 1 kV (at 5 kA)
Residual voltage Ures (L-N)≤ 0.9 kV (at 3 kA)
Residual voltage Ures (L-PE)≤ 2.8 kV (at In)
Residual voltage Ures (L-PE)≤ 2.4 kV (at 10 kA)
Residual voltage Ures (L-PE)≤ 2 kV (at 5 kA)
Residual voltage Ures (L-PE)≤ 1.8 kV (at 3 kA)
Residual voltage Ures (N-PE)≤ 1.5 kV (at In)
Residual voltage Ures (N-PE)≤ 1.2 kV (at 10 kA)
Residual voltage Ures (N-PE)≤ 1 kV (at 5 kA)
Residual voltage Ures (N-PE)≤ 0.9 kV (at 3 kA)
TOV behavior at UT (L-N)415 V AC (5 s / withstand mode)
TOV behavior at UT (L-N)440 V AC (120 min / safe failure mode)
Response time tA≤ 25 ns
Max. backup fuse with V-type through wiring125 A (gG)
Max. backup fuse with branch wiring315 A (gG)

Ambient conditions

Degree of ProtectionIP20 (only when all terminal points are used)
Ambient Temperature (Operation)-40 °C ... 80 °C
Ambient temperature (storage/transport)-40 °C ... 80 °C
Altitude≤ 2000 m (amsl)
Permissible humidity (operation)5 % ... 95 %
Shock (operation)25g (Half-sine / 11 ms / 3x ±X, ±Y, ±Z)
Vibration (Operation)5g (5 - 500 Hz/2.5 h/X, Y, Z)

Standards and Regulations

Standards/specificationsIEC 61643-11
Note2011

EN 61643-11

Standards/specificationsEN 61643-11
Note2012

Mounting

Mounting TypeDIN rail: 35 mm
Accessories

Why Proax for Phoenix Contact 1044386?

Proax is an authorized distributor of Phoenix Contact 1044386 and one of Phoenix Contact's largest distributors in North America. Our highly skilled in-house technical team is ready to assist with any technical needs.

Have a question in mind? to help you get the right product as quickly as possible for your project. We're always here to help!

Short Lead Time
Highly Trained Staff
Live Chat
Technical Support
Local Inventory
60+ Years Experience
Additional Information

Pack Size1
Recommended

Not in stock

Request lead time or order—we'll ensure quick delivery

Phoenix Contact Availability