3.062 kg
Series QUINT4-UPS
QUINT4-UPS/1AC/1AC/500VA/USB - Uninterruptible power supply
QUINT AC-USV, IQ Technology, DIN rail mounting, input: 120 V AC / 230 V AC, output: 120 V AC / 230 V AC / 500 VA.
Technical Specifications
Input data
Input Voltage | 120 V AC |
Input Voltage | 230 V AC |
Input voltage range | 90 V AC ... 264 V AC |
Nominal input voltage range | 100 V AC ... 240 V AC |
Typical national grid voltage | 120 V AC |
Voltage type of supply voltage | AC |
Frequency range (fN) | 45 Hz ... 65 Hz |
Permissible backup fuse | max. 25 A |
Current consumption | 6.9 A (100 V AC) |
Current consumption | 2.86 A (240 V AC) |
Current consumption | 19 A (24 V DC) |
Output data
Efficiency | > 97 % (100 % load, with charged energy storage) |
Efficiency | ~ 87 % (100 % load ) |
Apparent power | 500 VA |
Real power | 400 W |
Power factor (cos phi) | 0.8 |
Crest factor | 2.8 |
Switch-over time | < 10 ms |
UPS classification | VFD-SS-311 |
Connection in parallel | no |
Connection in series | No |
Overload capability Mains operation | in accordance with internal fuse |
Overload capability Battery operation | 105 % (Permanent) |
Overload capability Battery operation | 120 % ... 150 % (20 s / 5 s, then shutdown) |
Mains operation
Output Voltage | 120 V AC |
Output Voltage | 230 V AC |
Nominal output current (IN) | 4.17 A (120 V AC) |
Nominal output current (IN) | 2.17 A (230 V AC) |
Maximum no-load power dissipation | typ. 9 W (120 V AC) |
Maximum no-load power dissipation | typ. 10 W (230 V AC) |
Power loss nominal load max. | typ. 10 W (120 V AC) |
Power loss nominal load max. | typ. 11 W (230 V AC) |
Nominal output frequency | 60 Hz ±5 Hz |
Nominal output frequency | 50 Hz ±5 Hz |
Output fuse | 10 A 400 V gRL |
Battery operation
Output Voltage | 120 V AC ±2 % |
Output Voltage | 230 V AC ±2 % |
Form of output voltage | Pure sine |
Maximum no-load power dissipation | approx. 23 W (120 V AC) |
Maximum no-load power dissipation | approx. 24 W (230 V AC) |
Power loss nominal load max. | approx. 57 W (120 V AC) |
Power loss nominal load max. | approx. 54 W (230 V AC) |
Nominal output frequency | 60 Hz |
Nominal output frequency | 50 Hz |
Nominal output frequency | ±5 % (grid-guided) |
Nominal output frequency | ±0.5 % (self-guided) |
Total harmonic distortion factor (THD) | < 3 % (linear load) |
Total harmonic distortion factor (THD) | < 8 % (non-linear load) |
Electronic current limitation | > 2,5 x IN (> 200 ms) |
Input
Input Voltage | 24 V DC |
Deep discharge protection | 20 V DC ... 24 V DC (can be parameterized) |
Nominal capacity range | 3.4 Ah ... 200 Ah (5x 40 Ah) |
Charging current | max. 5 A |
End-of-charge voltage | 24 V DC ... 31 V DC (temperature compensated) |
General
Battery technology | VRLA, VRLA-WTR, LI-ION (see section: Ordering data) |
Charge characteristic curve | IU0U |
Permissible backup fuse | 50 A |
Interfaces
Interface | USB (Modbus/RTU) |
Number of interfaces | 1 |
Connection Method | MINI-USB Type B |
Connection marking | 5.1 |
Locking | Screw |
Transmission physics | USB 2.0 |
Maximum cable length | 3 m |
Electrical isolation | yes |
Signal input Bat.-Start
Low signal | Connection to SGnd with < 2.7 kΩ |
High signal | Open (> 200 kΩ between Bat.-Start and SGnd) |
Signal input Remote
Low signal | Connection to SGnd with < 2.7 kΩ |
High signal | Open (> 35 kΩ between Remote and SGnd) |
Signal output Alarm
Position | 3.x |
Signalization designation | Alarm |
Position marking | 3.1 (Alarm) |
Switching output | Transistor output, active |
Output Voltage | 24 V |
Continuous load current | ≤ 20 mA |
LED status indicator | red |
Signal output Battery mode
Position | 3.x |
Signalization designation | Bat.-Mode |
Position marking | 3.2 (Bat.-Mode) |
Switching output | Transistor output, active |
Output Voltage | 24 V |
Continuous load current | ≤ 20 mA |
LED status indicator | yellow |
Signal output AC OK
Position | 3.x |
Signalization designation | AC OK |
Position marking | 3.3 (AC OK) |
Switching output | Transistor output, active |
Output Voltage | 24 V |
Continuous load current | ≤ 20 mA |
LED status indicator | green |
Signal output Ready
Position | 3.x |
Signalization designation | Ready |
Position marking | 3.4 (Ready) |
Switching output | Transistor output, active |
Output Voltage | 24 V |
Continuous load current | ≤ 20 A |
LED status indicator | green |
Signal output P > PN
Position | 3.x |
Signalization designation | P>Pn |
Position marking | 3.5 (P>Pn) |
Switching output | Transistor output, active |
Output Voltage | 24 V |
Continuous load current | ≤ 20 mA |
Signal ground SGnd
Connection labeling | 3.9 |
Function | Signal ground |
Reference potential | For signal inputs and signal outputs |
Electrical properties
Number of phases | 1.00 |
Product properties
Product family | QUINT AC-USV |
MTBF (IEC 61709, SN 29500) | 445469 h (40 °C) |
Insulation characteristics
Protection class | I |
Overvoltage category | II |
Pollution degree | 3 (≤ 130 V AC) |
Pollution degree | 2 (> 200 V AC) |
Item dimensions
Width | 180 mm |
Height | 130 mm |
Depth | 125 mm |
Installation dimensions
Installation distance right/left | 0 mm / 0 mm |
Installation distance top/bottom | 50 mm / 50 mm |
Mounting
Mounting Type | DIN rail mounting |
Material specifications
Housing Material | Metal |
Ambient conditions
Degree of Protection | IP20 |
Ambient Temperature (Operation) | -25 °C ... 60 °C (> 50 °C: 2,5 % / K) |
Ambient temperature (storage/transport) | -40 °C ... 85 °C |
Maximum altitude | ≤ 3000 m (> 2000 m: 0,6 % / 100 m) |
Max. permissible relative humidity (operation) | ≤ 95 % |
Shock | 20g in all directions (EN 60068-2-27) |
Vibration (Operation) | 5 Hz ... 100 Hz, 0.7g (EN 60068-2-6) |
Uninterruptible power supply systems
Standard designation | Uninterruptible power supply systems |
Standards/specifications | EN 62040-1 |
UL
Identification | UL/C-UL Recognized UL 1778 |
EMC data
Low Voltage Directive | Conformance with Low Voltage Directive 2014/35/EC |
Interference emission | Noise emission in accordance with EN 62040-2 |
Noise immunity | Immunity in accordance with EN 62040-2 |
Electromagnetic compatibility | Conformance with EMC Directive 2014/30/EU |
Conducted noise emission | EN 62040-02 (Class C2) |
Electrostatic discharge
Standards/regulations | EN 61000-4-2 |
Contact discharge | ± 6 kV |
Discharge in air | ± 8 kV |
Comments | Criterion A |
Electromagnetic HF field
Standards/regulations | EN 61000-4-3 |
Frequency Range | 80 MHz ... 6 GHz |
Test field strength | 10 V/m |
Comments | Criterion A |
Fast transients (burst)
Standards/regulations | EN 61000-4-4 |
Input | ± 2 kV |
Input | ± 2 kV |
Output | ± 2 kV |
Signal | ± 2 kV |
Signal | ± 2 kV (USB) |
Comments | Criterion A (B for USB) |
Surge voltage load (surge)
Standards/regulations | EN 61000-4-5 |
Signal | 1 kV (asymmetrical) |
Comments | Criterion B |
Input/Output | ± 1 kV (symmetrical) |
Input/Output | ± 2 kV (asymmetrical) |
Conducted interference
Standards/regulations | EN 61000-4-6 |
Frequency Range | 0.15 MHz ... 80 MHz |
Signal | 1 kV (asymmetrical) |
Comments | Criterion A |
Power frequency magnetic field
Standards/regulations | EN 61000-4-8 |
Frequency | 50 Hz |
Signal | 30 A/m |
Comments | Criterion A |
Criteria
Criterion A | Normal operating behavior within the specified limits. |
Criterion B | Temporary impairment to operational behavior that is corrected by the device itself. |
Accessories
Why Proax for Phoenix Contact QUINT4-UPS/1AC/1AC/500VA/USB?
Proax is an authorized distributor of Phoenix Contact QUINT4-UPS/1AC/1AC/500VA/USB and one of Phoenix Contact's largest distributors in North America. Our highly skilled in-house technical team is ready to assist with any technical needs.
Have a question in mind? to help you get the right product as quickly as possible for your project. We're always here to help!
Short Lead Time
Highly Trained Staff
Live Chat
Technical Support
Local Inventory
60+ Years Experience
Additional Information
Alternate Names | QUINT4UPS1AC1AC500VAUSB |
Pack Size | 1 |
Recommended
- 2320283 - Uninterruptible power supply with IQ technology for DIN rail mounting. Input: 120/230 V AC, output: 120/230 V AC/1 kVA. Provides information regarding the state of charge, remaining runtime, and service life of the rechargeable battery module at any time, thereby increasing system availability.