Official Distributor
SKU
MPN
QUINT4-UPS/24DC/24DC/10
Weight
0.511 kg
Series QUINT4-UPS
QUINT4-UPS/24DC/24DC/10 - Uninterruptible power supply
QUINT USV, IQ Technology, DIN rail mounting, Screw connection, input: 24 V DC, output: 24 V DC / 10 A, charging current: 3 A
- Easy integration into networks using PROFINET, EtherNet/IP, EtherCAT® and USB interfaces
- Evaluation of state of health (SOH) and state of charge (SOC), thanks to the intelligent battery management system (BMS)
- Automatic recognition of the battery capacities and technologies (VRLA-WTR, LI-ION)
- Monitoring of output current and voltage, as well as manual connection and disconnection of the system
- SFB Technology selectively trips standard miniature circuit breakers. Loads connected in parallel continue working.
Technical Specifications
Input data
Input Voltage | 24 V DC |
Input voltage range | 18 V DC ... 30 V DC |
Electric strength, max. | 35 V DC (Protected against polarity reversal) |
Internal input fuse | no |
Typical national grid voltage | 24 V DC |
Voltage type of supply voltage | DC |
Inrush Current | ≤ 7 A (≤ 4 ms) |
Reverse polarity protection | yes |
Fixed backup threshold | 22 V DC |
Fixed backup threshold | 30 V DC |
Dynamic activation threshold | > 1 V / 100 ms |
Switch-on time | max. 3 s |
Switch-on time during battery operation (Bat.-Start) | 8 s |
Voltage drop, input/output | 0.4 V DC |
Current consumption IN (UN, IOUT = IN, Icharge = 0) | 10.1 A |
Current consumption Imax (UN, IOUT = IStat.Boost, Icharge = max) | 16.2 A |
Current consumption INo-Load(UN, IOUT = 0, Icharge = 0) | 48 mA |
Current consumption Icharge (UN, IOUT = 0, Icharge = max) | 3.5 A |
Power consumption PN (UN, IOUT = IN, Icharge = 0) | 241 W |
Power consumption Pmax (UN, IOUT = IStat.Boost, Icharge = max) | 384 W |
Power consumption PNo-Load (UN, IOUT = 0, Icharge = 0) | 1.2 W |
Power consumption Pcharge (UN, IOUT = 0, Icharge = max) | 90 W |
Signal state Bat.-Start
Connection labeling | 3.8 (+) |
Channel | DI (digital input) |
State | Bat.-Mode |
State condition | Low level (30 ms) |
Low signal | Input connected with SGnd (3.9) or Bat |
High signal | Input not connected or connected with >UBat |
Signal - state assignment | low - active |
Reference potential | 3.9 (SGnd, identical to 1.2, 2.2, 4.2) |
LED status indicator | Yellow (Bat.-Mode) |
Signal state PS Boost
Connection labeling | 3.7 (+) |
Channel (configurable) | DI (digital input) default, AI (analog input) |
State (configurable) | Charging current reduced |
State condition | Low level |
Low signal | Input connected with SGnd (3.9), <5 V DC or not connected |
High signal | Input connected with 13 … 30 V DC |
Signal - state assignment | low - active |
Analog | 4 mA ... 20 mA (Offset zero point) |
Unit signal | I (mA) |
Load | 390 Ω |
Reference potential | 3.9 (SGnd, identical to 1.2, 2.2, 4.2) |
Signal state Remote
Connection labeling | 3.6 (+) |
Channel | DI (digital input) |
State (configurable) | Disconnection |
State condition | Low level |
Low signal | Input connected with SGnd (3.9) or <5 V DC |
High signal | Input not connected or connected with 13 … 30 V DC |
Signal - state assignment | low - active |
Reference potential | 3.9 (SGnd, identical to 1.2, 2.2, 4.2) |
LED status indicator | Green, flashing (DC OK) |
Output data
Efficiency | typ. 98 % |
Number of Outputs | 1 |
Short-circuit-proof | yes |
No-load proof | yes |
Switch-over time | 0 ms |
UPS connection in parallel | no |
UPS connection in series | no |
Energy storage device connection in parallel | Yes, 5 (observe line protection) |
Energy storage device connection in series | no |
Mains operation
Output Voltage | 24 V DC (UOUT = UIN - 0.4 V DC) |
Output voltage range | 18 V DC ... 30 V DC (UOUT = UIN - 0.4 V DC) |
Output voltage range | 18 V DC ... 32 V DC |
Output current IN | 10 A |
Static Boost (IStat.Boost) | 12.5 A |
Dynamic Boost (IDyn.Boost) | 20 A (5 s) |
Selective Fuse Breaking (ISFB) | 60 A (15 ms) |
Output power POUT (UN, IOUT = IN) | 240 W |
Output power POUT (UN, IOUT = Istat.Boost) | 300 W |
Output power POUT (UN, IOUT = Idyn.Boost) | 480 W (5 s) |
Power dissipation No load (UN, IOut = 0, ICharge = 0) | 3 W |
Power dissipation Nominal load (UN, IOut = IN, ICharge = 0) | 8 W |
Battery operation
Output Voltage | 24 V DC (UOUT = UBAT - 0.4 V DC) |
Output voltage range | 19 V DC ... 28 V DC (UOUT = UBAT - 0.4 V DC) |
Output current IN | 10 A |
Static Boost (IStat.Boost) | 12.5 A |
Selective Fuse Breaking (ISFB) | 60 A (15 ms) |
Output power POUT (UN, IOUT = IN) | 240 W |
Output power POUT (UN, IOUT = Istat.Boost) | 300 W |
Output power POUT (UN, IOUT = Idyn.Boost) | 480 W (5 s) |
Power dissipation No load (UN, IOut = 0, ICharge = 0) | 2 W |
Power dissipation Nominal load (UN, IOut = IN, ICharge = 0) | 8 W |
Signal supply 24 V DC, 20 mA, SGnd
Connection labeling | 3.1 (+), 3.9 (SGnd) |
Output Voltage | 24 V DC |
Output can be loaded | max. 20 mA |
Reference potential | 3.9 (SGnd, identical to 1.2, 2.2, 4.2) |
Signal state Alarm
Connection labeling | 3.2, 3.3 |
Channel | DO (digital output) |
Switching voltage | max. 30 V AC/DC |
Switch contact (floating) | OptoMOS |
State (configurable) | Group alarm |
State condition (configurable) | Alarm threshold |
Current carrying capacity | max. 100 mA |
State - signal assignment | NC (Normally Closed) |
LED status indicator | red (Alarm) |
Signal state Bat. mode
Connection labeling | 3.4 (+) |
Channel | DO (digital output) |
Semiconductor output | MOSFET |
State (configurable) | Bat.-Mode |
State condition (configurable) | UIN < 18 V DC, UIN > 30 V DC, Bat.-Start |
Output Voltage | 19 V DC ... 28 V DC (buffered) |
Output can be loaded | max. 20 mA |
State - signal assignment | active - high |
Reference potential | 3.9 (SGnd, identical to 1.2, 2.2, 4.2) |
LED status indicator | Yellow (Bat.-Mode) |
Signal state Ready
Connection labeling | 3.5 (+) |
Channel | DO (digital output) |
Semiconductor output | MOSFET |
State (configurable) | Ready |
State condition (configurable) | SOC = 100 % |
Output Voltage | 19 V DC ... 28 V DC (buffered) |
Output can be loaded | max. 20 mA |
State - signal assignment | active - high |
Reference potential | 3.9 (SGnd, identical to 1.2, 2.2, 4.2) |
LED status indicator | Green (state of charge - SOC) |
Energy storage
Nominal voltage UN | 24 V DC |
End-of-charge voltage (temperature-compensated) | 25 V DC ... 32 V DC |
End-of-charge voltage (configurable) | 27.6 V DC |
Charging current (configurable) | max. 3 A |
Nominal capacity (without additional charger) | 1.2 Ah ... 80 Ah |
Max. capacity | 80 Ah |
Charging time | 160 min. (7.2 Ah) |
Buffer time | 25 min. (7.2 Ah) |
Deep discharge protection (configurable) | 19.2 V DC |
Battery technology | VRLA, VRLA-WTR, LI-ION |
Charge characteristic curve | IU0U |
IQ-Technology | yes |
Temperature sensor | yes |
Temperature compensation (configurable) | 42 mV/K |
Input
Position | 1.x |
Conductor connection
Connection Method | Screw connection |
rigid | 0.2 mm² ... 2.5 mm² |
rigid | recommended |
flexible | 0.2 mm² ... 2.5 mm² |
flexible with ferrule without plastic sleeve | 0.2 mm² ... 2.5 mm² |
flexible with ferrule with plastic sleeve | 0.2 mm² ... 2.5 mm² |
rigid (AWG) | 30 ... 12 (Cu) |
Stripping length | 6.5 mm (rigid/flexible) |
Tightening torque | 0.5 Nm ... 0.6 Nm |
Drive form screw head | Slotted L |
Output
Position | 2.x |
Conductor connection
Connection Method | Screw connection |
rigid | 0.2 mm² ... 2.5 mm² |
flexible | 0.2 mm² ... 2.5 mm² |
flexible with ferrule without plastic sleeve | 0.2 mm² ... 2.5 mm² |
flexible with ferrule with plastic sleeve | 0.2 mm² ... 2.5 mm² |
rigid (AWG) | 30 ... 12 (Cu) |
Stripping length | 6.5 mm (rigid/flexible) |
Tightening torque | 0.5 Nm ... 0.6 Nm |
Drive form screw head | Slotted L |
Signal
Position | 3.x |
Conductor connection
Connection Method | Push-in connection |
rigid | 0.2 mm² ... 1 mm² |
flexible | 0.2 mm² ... 1 mm² |
flexible with ferrule without plastic sleeve | 0.2 mm² ... 0.75 mm² (Cu) |
flexible with ferrule without plastic sleeve | 0.5 mm² (recommended) |
flexible with ferrule with plastic sleeve | 0.2 mm² ... 0.75 mm² |
rigid (AWG) | 24 ... 16 (Cu) |
Stripping length | 8 mm (rigid/flexible) |
Battery
Position | 4.x |
Connection technology
Position marking | 4.1 (+), 4.2 (-), 4.3 () |
Conductor connection
Connection Method | Screw connection |
rigid | 0.2 mm² ... 2.5 mm² |
flexible | 0.2 mm² ... 2.5 mm² |
flexible with ferrule without plastic sleeve | 0.2 mm² ... 2.5 mm² |
flexible with ferrule with plastic sleeve | 0.2 mm² ... 2.5 mm² |
rigid (AWG) | 30 ... 12 (Cu) |
Stripping length | 6.5 mm (rigid/flexible) |
Tightening torque | 0.5 Nm ... 0.6 Nm |
Drive form screw head | Slotted L |
LED signaling
Types of signaling | DC OK (green) |
Types of signaling | Alarm (red) |
Types of signaling | Bat.-Mode (yellow) |
Types of signaling | SOC (red, green) |
Types of signaling | Data (red, green) |
Product properties
Product family | QUINT USV |
MTBF (IEC 61709, SN 29500) | > 2065000 h (25 °C) |
MTBF (IEC 61709, SN 29500) | > 1184000 h (40 °C) |
MTBF (IEC 61709, SN 29500) | > 522600 h (60 °C) |
Environmental protection directive | RoHS Directive 2011/65/EU |
Environmental protection directive | WEEE |
Environmental protection directive | Reach |
Insulation characteristics
Protection class | III (without PE) |
Degree of pollution | 2 |
Life expectancy (electrolytic capacitors)
Time | 137895 h |
Item dimensions
Width | 35 mm |
Height | 130 mm |
Depth | 132 mm |
Depth | 125 mm (Device depth (DIN rail mounting)) |
Item dimensions with alternative mounting
Width | 123 mm |
Height | 130 mm |
Depth | 37 mm |
Installation dimensions
Installation distance right/left (active) | 5 mm / 5 mm (POut ≥50% ) |
Installation distance right/left (passive) | 0 mm / 0 mm (POut ≥50% ) |
Installation distance right/left (active, passive) | 0 mm / 0 mm (POut ≤50 %) |
Installation distance top/bottom (active) | 50 mm / 50 mm (POut ≥50% ) |
Installation distance top/bottom (passive) | 40 mm / 20 mm (POut ≥50% ) |
Installation distance top/bottom (active, passive) | 40 mm / 20 mm (POut ≤50 %) |
Mounting
Mounting Type | DIN rail mounting |
Mounting Position | On horizontal DIN rail NS 35/7.5 and NS 35/15 acc. to EN 60715 |
Material specifications
Flammability rating according to UL 94 (housing / terminal blocks) | V0 |
Housing Material | Metal |
Hood version | Stainless steel X6Cr17 |
Side element version | Aluminum AlMg3 |
Ambient conditions
Degree of Protection | IP20 |
Ambient Temperature (Operation) | -25 °C ... 70 °C (> 60 °C Derating: 2,5 %/K) |
Ambient temperature (storage/transport) | -40 °C ... 85 °C |
Ambient temperature (start-up type tested) | -40 °C |
Maximum altitude | ≤ 4000 m |
Climatic class | 3K3 (EN 60721) |
Max. permissible relative humidity (operation) | ≤ 95 % (at 25 °C, non-condensing) |
Shock | 18 ms, 30g, in each space direction (according to IEC 60068-2-27) |
Vibration (Operation) | 2.3g |
Overvoltage category
EN 61010-1 | II (≤ 4000 m) |
EN 61010-2-201 | II (≤ 4000 m) |
Protective extra-low voltage
Standard designation | Protective extra-low voltage |
Standards/specifications | IEC 61010-1 (SELV) |
Standards/specifications | IEC 61010-2-201 (PELV) |
UL approval
Identification | UL/C-UL Listed UL 61010-1 |
Identification | UL/C-UL Listed UL 61010-2-201 |
Identification | UL/C-UL Listed ANSI/ISA-12.12.01 Class I, Division 2, Groups A, B, C, D T4 (Hazardous Location) |
CSA
Identification | CAN/CSA-C22.2 No. 61010-1-12 |
Identification | CAN/CSA-IEC 61010-2-201 |
Identification | CAN/CSA-C22.2 No. 213 Class I, Division 2, Groups A, B, C, D T4 (Hazardous Location) |
CB scheme
Identification | IEC 61010-1 |
Identification | IEC 61010-2-201 |
DNV
Identification | Class Guideline DNVGL-CG-0339 |
Note | Location classes: Temperature D (see Application/Limitation), Humidity B, Vibration A/C, EMC B |
EMC data
Low Voltage Directive | Conformance with Low Voltage Directive 2014/35/EC |
EMC requirements for noise emission | EN 61000-6-3 |
EMC requirements for noise emission | EN 61000-6-4 |
EMC requirements for noise immunity | EN 61000-6-1 |
EMC requirements for noise immunity | EN 61000-6-2 |
Noise immunity | Immunity in accordance with EN 61000-6-1 (residential), EN 61000-6-2 (industrial), and EN 61000-6-5 (power station equipment zone), IEC/EN 61850-3 (power supply) |
Electromagnetic compatibility | Conformance with EMC Directive 2014/30/EU |
Noise emission | Additional basic standard EN 61000-6-5 (immunity in power station), IEC/EN 61850-3 (energy supply) |
Electrostatic discharge
Standards/regulations | EN 61000-4-2 |
Contact discharge | 8 kV (Test Level 4) |
Discharge in air | 15 kV (Test Level 4) |
Comments | Criterion B |
Electromagnetic HF field
Standards/regulations | EN 61000-4-3 |
Frequency Range | 80 MHz ... 1 GHz |
Test field strength | 20 V/m (Test Level 3) |
Frequency Range | 1 GHz ... 6 GHz |
Test field strength | 10 V/m (Test Level 3) |
Frequency Range | 1 GHz ... 6 GHz |
Test field strength | 10 V/m (Test Level 3) |
Comments | Criterion A |
Fast transients (burst)
Standards/regulations | EN 61000-4-4 |
Input | 4 kV (Test Level 4 - asymmetrical) |
Output | 4 kV (Test Level 4 - asymmetrical) |
Signal | 4 kV (Test Level 4 - asymmetrical) |
Comments | Criterion B |
Surge voltage load (surge)
Standards/regulations | EN 61000-4-5 |
Input | 1 kV (Test Level 3 - symmetrical) |
Input | 2 kV (Test Level 3 - asymmetrical) |
Output | 1 kV (Test Level 3 - symmetrical) |
Output | 2 kV (Test Level 3 - asymmetrical) |
Signal | 1 kV (Test Level 2 - asymmetrical) |
Comments | Criterion B |
Conducted interference
Standards/regulations | EN 61000-4-6 |
I/O/S | asymmetrical |
Frequency Range | 0.15 MHz ... 80 MHz |
Comments | Criterion A |
Voltage | 10 V (Test Level 3) |
Power frequency magnetic field
Standards/regulations | EN 61000-4-8 |
Frequency | 16.67 Hz |
Frequency | 50 Hz |
Frequency | 60 Hz |
Test field strength | 100 A/m |
Additional text | 60 s |
Comments | Criterion A |
Frequency | 50 Hz |
Frequency | 60 Hz |
Frequency Range | 50 Hz ... 60 Hz |
Test field strength | 1 kA/m |
Additional text | 3 s |
Frequency | 0 Hz |
Test field strength | 300 A/m |
Additional text | DC, 60 s |
Criteria
Criterion A | Normal operating behavior within the specified limits. |
Criterion B | Temporary impairment to operational behavior that is corrected by the device itself. |
Accessories
Why Proax for Phoenix Contact 2907066?
Proax is an authorized distributor of Phoenix Contact 2907066 and one of Phoenix Contact's largest distributors in North America. Our highly skilled in-house technical team is ready to assist with any technical needs.
Have a question in mind? to help you get the right product as quickly as possible for your project. We're always here to help!
Short Lead Time
Highly Trained Staff
Live Chat
Technical Support
Local Inventory
60+ Years Experience
Additional Information
Pack Size | 1 |
Recommended