Proax

Currency
0 Items
proax logo
Cart
Phoenix ContactOfficial Distributor

By Phoenix Contact

SKU
MPN
QUINT4-UPS/1AC/1AC/1KVA
Weight
5.63 kg
Series QUINT4-UPS

QUINT4-UPS/1AC/1AC/1KVA - Uninterruptible power supply

Uninterruptible power supply with IQ technology for DIN rail mounting. Input: 120/230 V AC, output: 120/230 V AC/1 kVA. Provides information regarding the state of charge, remaining runtime, and service life of the rechargeable battery module at any time, thereby increasing system availability.

  • Smooth transition due to online topology
  • Pure sine curve in mains and battery operation
  • USB interface for connecting to industrial PCs, for example
  • Startup from energy storage possible, even without mains input
  • Can be switched in parallel for redundancy and increased performance
Technical Specifications

AC operation

Input Voltage100 V AC -10 % / +20 %
Input Voltage110 V AC -10 % / +20 %
Input Voltage120 V AC -10 % / +20 %
Input Voltage130 V AC -10 % / +20 %
Input Voltage200 V AC -20 % / +20 %
Input Voltage210 V AC -20 % / +20 %
Input Voltage220 V AC -20 % / +20 %
Input Voltage230 V AC -20 % / +15 %
Input Voltage240 V AC -20 % / +10 %
Input voltage range90 V AC ... 264 V AC
Input Voltage Range AC184 V AC ... 264 V AC
Input Voltage Range AC96 V AC ... 144 V AC
Typical national grid voltage120 V AC
Typical national grid voltage230 V AC
Voltage type of supply voltageAC
AC frequency range45 Hz ... 65 Hz
Buffer period1 h (38 AH)
Current consumption10.4 A (100 V AC)
Current consumption10.5 A (110 V AC)
Current consumption10.5 A (120 V AC)
Current consumption9.7 A (130 V AC)
Current consumption6.4 A (200 V AC)
Current consumption6 A (210 V AC)
Current consumption5.7 A (220 V AC)
Current consumption5.5 A (230 V AC)
Current consumption5.3 A (240 V AC)
Variable connect thresholdCan be configured using UPS-CONF software
Power factor (cos phi)0.9
Bypass fuseT 15 A / 250 V (MDA -15-R)
Permissible backup fuseB16 230 V AC
Permissible backup fuse20 A (120 V AC, Listed breaker)

Digital Control (configurable)

DesignationRemote
Low signalConnection to SGnd with < 2.7 kΩ
High signalOpen (> 35 kΩ between Remote and SGnd)

Digital Control Low-Active (configurable)

Battery-operated start 120 V AC low signalConnection to SGnd with < 2.7 kΩ
Battery-operated start 120 V AC high signalOpen (> 200 kΩ between Bat.-Start and SGnd)

Output data

Classification according to IEC 62040-3VFI-SS-111
Efficiency> 92 % (120 V AC)
Efficiency> 94 % (230 V AC)
Nominal Output Voltage100 V AC
Nominal Output Voltage110 V AC
Nominal Output Voltage120 V AC
Nominal Output Voltage130 V AC
Nominal Output Voltage200 V AC
Nominal Output Voltage210 V AC
Nominal Output Voltage220 V AC
Nominal Output Voltage230 V AC
Nominal Output Voltage240 V AC
Form of output voltagePure sine
Nominal output current (IN)7.8 A (100 V AC)
Nominal output current (IN)8.1 A (110 V AC)
Nominal output current (IN)8.3 A (120 V AC)
Nominal output current (IN)7.7 A (130 V AC)
Nominal output current (IN)5 A (200 V AC)
Nominal output current (IN)4.8 A (210 V AC)
Nominal output current (IN)4.5 A (220 V AC)
Nominal output current (IN)4.3 A (230 V AC)
Nominal output current (IN)4.2 A (240 V AC)
POWER BOOST (IBoost)13 A (120 V AC)
POWER BOOST (IBoost)7 A (230 V AC)
Output Power778 VA (700 W)
Output Power889 VA (800 W)
Output Power1000 VA (900 W)
Output Power1000 VA (900 W)
Output Power1000 VA (900 W)
Output Power1000 VA (900 W)
Output Power1000 VA (900 W)
Output Power1000 VA (900 W)
Output Power1000 VA (900 W)
Apparent power1 kVA (UN  120 V AC)
Nominal power900 W (UN  120 V AC)
Maximum no-load power dissipationtyp. 17 W (120 V AC)
Maximum no-load power dissipationtyp. 25 W (230 V AC)
Power loss nominal load max.typ. 79 W (120 V AC)
Power loss nominal load max.typ. 55 W (230 V AC)
Crest factor2.8
Switch-over time0 ms
Connection in parallelyes, 2
Connection in seriesNo

Mains operation

Nominal Output Voltage120 V AC ±2 %
Nominal Output Voltage230 V AC ±2 %
Nominal output current (IN)8.3 A
Nominal output current (IN)4.3 A (230 V AC)
POWER BOOST (IBoost)13 A
POWER BOOST (IBoost)7 A

Battery operation

Nominal Output Voltage120 V AC ±2 %
Nominal Output Voltage230 V AC ±2 %
Nominal output current (IN)4.3 A (230 V AC)
Nominal output current (IN)8.3 A (120 V AC)
POWER BOOST (IBoost)7 A (230 V AC)
POWER BOOST (IBoost)13 A (120 V AC)
Nominal output frequency± 60 Hz ±0.5 % (At an input frequency of 55 Hz to < 65 Hz)
Nominal output frequency± 50 Hz ±0.5 % (At an input frequency of 45 Hz to < 55 Hz)

Signal: AC OK

Output Voltage24 V
Continuous load current≤ 20 mA

Signal: Alarm

Output Voltage24 V
Continuous load current≤ 20 mA

Signal: Battery mode

Output Voltage24 V
Continuous load current≤ 20 mA

Signal: Ready

Output Voltage24 V
Continuous load current≤ 20 mA

Signal: P>Pn

Output Voltage24 V (SELV)
Continuous load current≤ 20 mA

Energy storage

Nominal voltage UN2x 24 V DC
End-of-charge voltage58 V (temperature compensated)
Charging current5 A
Nominal capacity range3.4 Ah ... 190 Ah (5x 38 Ah)
Battery technologyVRLA, VRLA-WTR
Charge characteristic curveIU0U
Permissible backup fuse50 A /  58 V

Input

Connection MethodScrew connection
Conductor cross section, rigid min.0.2 mm²
Conductor cross section, rigid max.6 mm²
Conductor cross section flexible min.0.2 mm²
Conductor cross section flexible max.4 mm²
Single conductor/flexible terminal point with ferrule with plastic sleeve, min.0.25 mm²
Single conductor/flexible terminal point with ferrule with plastic sleeve, max.4 mm²
Single conductor/flexible terminal point with ferrule without plastic sleeve, min.0.25 mm²
Single conductor/flexible terminal point with ferrule without plastic sleeve, max.4 mm²
Conductor cross section AWG min.30
Conductor cross section AWG max.10
Stripping length8 mm
Tightening torque, min0.5 Nm
Tightening torque max0.6 Nm

Output

Connection MethodScrew connection
Conductor cross section, rigid min.0.2 mm²
Conductor cross section, rigid max.6 mm²
Conductor cross section flexible min.0.2 mm²
Conductor cross section flexible max.4 mm²
Single conductor/flexible terminal point with ferrule with plastic sleeve, min.0.25 mm²
Single conductor/flexible terminal point with ferrule with plastic sleeve, max.4 mm²
Single conductor/flexible terminal point with ferrule without plastic sleeve, min.0.25 mm²
Single conductor/flexible terminal point with ferrule without plastic sleeve, max.4 mm²
Conductor cross section AWG min.30
Conductor cross section AWG max.10
Stripping length8 mm
Tightening torque, min0.5 Nm
Tightening torque max0.6 Nm

Signal

Connection MethodScrew connection
Conductor cross section, rigid min.0.2 mm²
Conductor cross section, rigid max.2.5 mm²
Conductor cross section flexible min.0.2 mm²
Conductor cross section flexible max.2.5 mm²
Single conductor/flexible terminal point with ferrule with plastic sleeve, min.0.2 mm²
Single conductor/flexible terminal point with ferrule with plastic sleeve, max.2.5 mm²
Single conductor/flexible terminal point with ferrule without plastic sleeve, min.0.2 mm²
Single conductor/flexible terminal point with ferrule without plastic sleeve, max.2.5 mm²
Conductor cross section AWG min.30
Conductor cross section AWG max.12
Stripping length8 mm
Tightening torque, min0.5 Nm
Tightening torque max0.6 Nm

Interfaces

InterfaceMINI-USB type B
Featureslockable
Maximum cable length3 m

Signaling

Types of signalingLED
Types of signalingActive switching output

Signal output: Transistor output, active

Signalization designationAC OK
Status displayLED
Colorgreen
Signalization designationAlarm
Status displayLED
Colorred
Signalization designationBattery mode
Status displayLED
Coloryellow
Signalization designationReady
Signalization designationP>Pn
Status displayLED
Colorgreen

Signal output

Signalization designationReference potential for the signal inputs and outputs

Electrical properties

Number of phases1.00

Product properties

Product familyQUINT AC-USV
MTBF (IEC 61709, SN 29500)217546 h (230 V AC, at 40 °C)

Insulation characteristics

Protection classI
Overvoltage categoryII
Pollution degree3 (≤ 130 V AC)
Pollution degree2 (> 200 V AC)

Life expectancy (electrolytic capacitors)

Time68970 h

Dimensions

Width290 mm
Height130 mm
Depth125 mm

Installation dimensions

Installation distance right/left5 mm / 5 mm
Installation distance top/bottom50 mm / 50 mm

Mounting

Mounting TypeDIN rail mounting

Material specifications

Housing MaterialMetal
Hood versionSheet steel, DIN EN ISO2081 coat - Fe/Zn 18/B/TopCoat transparent blue
Side element versionAluminum plate, DIN EN 573-3

Ambient conditions

Degree of ProtectionIP20
Ambient Temperature (Operation)-25 °C ... 60 °C (> 50 °C: 2,5 % / K)
Ambient temperature (storage/transport)-40 °C ... 85 °C
Maximum altitude≤ 3000 m (> 2000 m: 0,6 % / 100 m)
Climatic class3K3 (EN 60721)
Max. permissible relative humidity (operation)≤ 95 %
Shock15g in all directions (EN 60068-2-27)
Vibration (Operation)5 Hz ... 100 Hz, 0.7g (EN 60068-2-6)

Uninterruptible power supply systems

Standard designationUninterruptible power supply systems
Standards/specificationsEN 62040-1

UL

IdentificationUL/C-UL Recognized UL 1778

EMC data

Low Voltage DirectiveConformance with Low Voltage Directive 2014/35/EC
Interference emissionNoise emission in accordance with EN 62040-2
Noise immunityImmunity in accordance with EN 62040-2
Noise immunityImmunity in accordance with EN 61000-6-1 (residential), EN 61000-6-2 (industrial)
Electromagnetic compatibilityConformance with EMC Directive 2014/30/EU
Conducted noise emissionEN 62040-02 (Class C2)

Electrostatic discharge

Standards/regulationsEN 61000-4-2
Contact discharge± 6 kV
Discharge in air± 8 kV
CommentsCriterion A

Electromagnetic HF field

Standards/regulationsEN 61000-4-3
Frequency Range80 MHz ... 6 GHz
Test field strength10 V/m
CommentsCriterion A

Fast transients (burst)

Standards/regulationsEN 61000-4-4
Input± 2 kV
Input± 2 kV
Output± 2 kV
Signal± 2 kV
Signal± 2 kV (USB)
CommentsCriterion A (B for USB)

Surge voltage load (surge)

Standards/regulationsEN 61000-4-5
Signal1 kV (asymmetrical)
CommentsCriterion B
Input/Output± 1 kV (symmetrical)
Input/Output± 2 kV (asymmetrical)

Conducted interference

Standards/regulationsEN 61000-4-6
Frequency Range0.15 MHz ... 80 MHz
CommentsCriterion A
Voltage10 V

Power frequency magnetic field

Standards/regulationsEN 61000-4-8
Frequency50 Hz
Frequency60 Hz
Test field strength100 A/m
CommentsCriterion A

Criteria

Criterion ANormal operating behavior within the specified limits.
Criterion BTemporary impairment to operational behavior that is corrected by the device itself.
Accessories

Why Proax for Phoenix Contact 2320283?

Proax is an authorized distributor of Phoenix Contact 2320283 and one of Phoenix Contact's largest distributors in North America. Our highly skilled in-house technical team is ready to assist with any technical needs.

Have a question in mind? to help you get the right product as quickly as possible for your project. We're always here to help!

Short Lead Time
Highly Trained Staff
Live Chat
Technical Support
Local Inventory
60+ Years Experience
Additional Information

Pack Size1
Recommended

Not in stock

Request lead time or order—we'll ensure quick delivery

Phoenix Contact Availability