UT 4-HESI (5X20) - Fuse modular terminal block
Fuse modular terminal block, fuse type: Glass / ceramics / ..., fuse type: G / 5 x 20, nom. voltage: 500 V, nominal current: 6.3 A, connection method: Screw connection, Rated cross section: 4 mm2, cross section: 0.14 mm2- 6 mm2, mounting type: NS 35/7,5, NS 35/15, color: black
- An extremely compact design
- Test pick-off on both sides in the fuse lever
- Tested for railway applications
Technical Specifications
Product properties
Area of application | Railway industry |
Area of application | Machine building |
Area of application | Plant engineering |
Number of Connections | 2 |
Number of rows | 1 |
Potentials | 1 |
Insulation characteristics
Overvoltage category | III |
Degree of pollution | 3 |
Electrical properties
Fuse type | Glass / ceramics / ... |
Rated surge voltage | 6 kV |
Maximum power dissipation for nominal condition | 1.02 W |
Fuse | G / 5 x 20 |
Maximum power dissipation | max. 1.6 W (with single arrangement of the fuse terminal block in the event of overload) |
Maximum power dissipation | max. 1.6 W (With interconnected arrangement of several fuse terminal blocks in the event of overload) |
Maximum power dissipation | max. 4 W (with single arrangement of the fuse terminal block in the event of a short-circuit) |
Maximum power dissipation | max. 2.5 W (With interconnected arrangement of several fuse terminal blocks in the event of a short-circuit) |
Connection data
Number of connections per level | 2 |
Nominal cross section | 4 mm² |
Screw thread | M3 |
Tightening torque | 0.6 ... 0.8 Nm |
Stripping length | 9 mm |
Internal cylindrical gage | A4 |
Connection in acc. with standard | IEC 60947-7-3 |
Conductor cross section rigid | 0.14 mm² ... 6 mm² |
Cross section AWG | 26 ... 10 (converted acc. to IEC) |
Conductor cross section flexible | 0.14 mm² ... 6 mm² |
Conductor cross section, flexible [AWG] | 26 ... 10 (converted acc. to IEC) |
Conductor cross-section flexible (ferrule without plastic sleeve) | 0.25 mm² ... 4 mm² |
Flexible conductor cross section (ferrule with plastic sleeve) | 0.14 mm² ... 4 mm² |
2 conductors with same cross section, solid | 0.14 mm² ... 1.5 mm² |
2 conductors with same cross section, flexible | 0.14 mm² ... 1.5 mm² |
2 conductors with same cross section, flexible, with ferrule without plastic sleeve | 0.14 mm² ... 1.5 mm² |
2 conductors with the same cross section, flexible, with TWIN ferrule with plastic sleeve | 0.5 mm² ... 1.5 mm² |
Nominal Current | 6.3 A |
Maximum Load Current | 6.3 A (the current is determined by the fuse used) |
Nominal Voltage | 500 V (The voltage is determined by the fuse or selected LED display) |
Nominal cross section | 4 mm² |
Dimensions
Width | 6.2 mm |
Height | 57.8 mm |
Depth on NS 35/7,5 | 75.6 mm |
Depth on NS 35/15 | 83.1 mm |
Material specifications
Color | black |
Flammability rating according to UL 94 | V0 |
Insulating material group | I |
Insulating material | PA |
Static insulating material application in cold | -60 °C |
Temperature index of insulation material (DIN EN 60216-1 (VDE 0304-21)) | 125 °C |
Relative insulation material temperature index (Elec., UL 746 B) | 130 °C |
Fire protection for rail vehicles (DIN EN 45545-2) R22 | HL 1 - HL 3 |
Fire protection for rail vehicles (DIN EN 45545-2) R23 | HL 1 - HL 3 |
Fire protection for rail vehicles (DIN EN 45545-2) R24 | HL 1 - HL 3 |
Fire protection for rail vehicles (DIN EN 45545-2) R26 | HL 1 - HL 3 |
Calorimetric heat release NFPA 130 (ASTM E 1354) | 27,5 MJ/kg |
Surface flammability NFPA 130 (ASTM E 162) | passed |
Specific optical density of smoke NFPA 130 (ASTM E 662) | passed |
Smoke gas toxicity NFPA 130 (SMP 800C) | passed |
Surge voltage test
Test voltage setpoint | 7.3 kV |
Result | Test passed |
Temperature-rise test
Requirement temperature-rise test | Increase in temperature ≤ 45 K |
Result | Test passed |
Result | Test passed |
Power-frequency withstand voltage
Test voltage setpoint | 1.89 kV |
Result | Test passed |
Mechanical data
Open side panel | No |
Mechanical strength
Result | Test passed |
Attachment on the carrier
Result | Test passed |
Test for conductor damage and slackening
Rotation speed | 10 (+/- 2) rpm |
Revolutions | 135 |
Conductor cross section/weight | 0.14 mm² / 0.2 kg |
Conductor cross section/weight | 4 mm² / 0.9 kg |
Conductor cross section/weight | 6 mm² / 1.4 kg |
Result | Test passed |
Needle-flame test
Time of exposure | 30 s |
Result | Test passed |
Oscillation/broadband noise
Specification | DIN EN 50155 (VDE 0115-200):2008-03 |
Spectrum | Service life test category 1, class B, body mounted |
Spectrum | Service life test category 2, bogie-mounted |
Frequency | f1 = 5 Hz to f2 = 150 Hz |
Frequency | 5 - 250 Hz |
ASD level | 1.857 (m/s²)²/Hz |
ASD level | 6.12 (m/s²)²/Hz |
Acceleration | 0.8g |
Acceleration | 3.12g |
Test duration per axis | 5 h |
Test duration per axis | 5 h |
Test directions | X-, Y- and Z-axis |
Test directions | X-, Y- and Z-axis |
Result | Test passed |
Result | Test passed |
Shocks
Specification | DIN EN 50155 (VDE 0115-200):2008-03 |
Specification | DIN EN 50155 (VDE 0115-200):2018-05 |
Pulse shape | Semi-sinusoidal |
Pulse shape | Half-sine |
Acceleration | 5g |
Acceleration | 30g |
Shock duration | 30 ms |
Shock duration | 18 ms |
Number of shocks per direction | 3 |
Number of shocks per direction | 3 |
Test directions | X-, Y- and Z-axis (pos. and neg.) |
Test directions | X-, Y- and Z-axis (pos. and neg.) |
Result | Test passed |
Result | Test passed |
Ambient conditions
Ambient Temperature (Operation) | -60 °C ... 110 °C (Operating temperature range incl. self-heating; for max. short-term operating temperature, see RTI Elec.) |
Ambient temperature (storage/transport) | -25 °C ... 60 °C (for a short time, not exceeding 24 h, -60 °C to +70 °C) |
Ambient temperature (assembly) | -5 °C ... 70 °C |
Ambient temperature (actuation) | -5 °C ... 70 °C |
Permissible humidity (operation) | 20 % ... 90 % |
Permissible humidity (storage/transport) | 30 % ... 70 % |
Standards and Regulations
Connection in acc. with standard | IEC 60947-7-3 |
Mounting
Mounting Type | NS 35/7,5 |
Mounting Type | NS 35/15 |
Accessories
Why Proax for Phoenix Contact 3046032?
Proax is an authorized distributor of Phoenix Contact 3046032 and one of Phoenix Contact's largest distributors in North America. Our highly skilled in-house technical team is ready to assist with any technical needs.
Have a question in mind? to help you get the right product as quickly as possible for your project. We're always here to help!
Short Lead Time
Highly Trained Staff
Live Chat
Technical Support
Local Inventory
60+ Years Experience
Additional Information
Pack Size | 50 |
Recommended
- 3046540 - Fuse modular terminal block, With test socket screws for insertion of test plugs, fuse type: Glass / ceramics / ..., fuse type: G / 5 x 20, nom. voltage: 24 V, nominal current: 6.3 A, number of positions: 1, connection method: Screw connection, Rated cross section: 4 mm2, cross section: 0.14 mm2- 6 mm2, mounting type: NS 35/7,5, NS 35/15, color: black
- 3074172 - Fuse modular terminal block, fuse type: Glass / ceramics / ..., fuse type: G / 5 x 20, nom. voltage: 24 V, nominal current: 6.3 A, number of positions: 1, connection method: Screw connection, Rated cross section: 4 mm2, cross section: 0.14 mm2- 6 mm2, mounting type: NS 35/7,5, NS 35/15, color: gray
- 3214363 - Multi-level terminal block, nom. voltage: 500 V, nominal current: 32 A, number of connections: 2, connection method: Screw connection, Rated cross section: 4 mm2, cross section: 0.14 mm2 - 6 mm2, Screw connection, Rated cross section: 4 mm2, cross section: 0.14 mm2 - 6 mm2, mounting type: NS 35/7,5, NS 35/15, color: gray
- 3044623 - Feed-through terminal block, With breakout partition plate in the bridge shaft, nom. voltage: 1000 V, nominal current: 32 A, number of connections: 2, number of positions: 1, connection method: Screw connection, Rated cross section: 4 mm2, cross section: 0.14 mm2 - 6 mm2, mounting type: NS 35/7,5, NS 35/15, color: gray