PT 2X1-VF-230AC-ST - Surge protection plug
Protective connector with protective circuit free of leakage current for two floating signals. Connection in series, consisting of varistor and gas-filled surge arrester between signal wires and ground.
- Easy testing and documentation with CHECKMASTER 2 with pluggable protective modules
- Maximum ease of maintenance, thanks to the 2-piece design
- Easy selection for all possible demands in MCR applications with a complete product portfolio
- The signal is not influenced during maintenance work, thanks to the impedance-neutral insertion and removal of protective plugs
PT
The Phoenix Contact PT Series comprises feed-through terminal blocks that utilize Push-in connection technology, offering efficient and reliable wiring solutions for various industrial applications. These terminal blocks are designed for straightforward conductor insertion, enhancing installation speed and ensuring secure connections.
Key Features:
- ✅ Push-in Connection Technology: The PT Series employs a direct plug-in method, allowing solid conductors or conductors with ferrules to be inserted easily without the need for tools. This design facilitates quick and reliable wiring.
- ✅ Compact Design: The terminal blocks feature a space-saving form factor, making them suitable for applications where installation space is limited.
- ✅ High Electrical Ratings: Depending on the specific model, the PT Series terminal blocks can handle nominal voltages up to 800 V and nominal currents up to 32 A, accommodating a wide range of electrical requirements.
- ✅ Versatile Conductor Compatibility: These terminal blocks support various conductor types and sizes, providing flexibility in wiring configurations.
- ✅ Integration with CLIPLINE Complete System: The PT Series is compatible with Phoenix Contact's CLIPLINE complete system, allowing for standardized bridging, marking, and testing accessories, which simplifies inventory management and enhances system modularity.
Product properties
Product family | PLUGTRAB PT |
IEC test classification | C1 |
IEC test classification | C2 |
IEC test classification | C3 |
IEC test classification | D1 |
Type | Male |
Number of Positions | 2 |
Surge protection fault message | none |
Electrical properties
Nominal voltage UN | 230 V AC |
Indicator/remote signaling
Switching function | N/C contact |
Connection data
Connection Method | Screw connection (in connection with the base element) |
Screw thread | M3 |
Tightening torque | 0.8 Nm |
Conductor cross section flexible | 0.2 mm² ... 2.5 mm² |
Conductor cross section rigid | 0.2 mm² ... 4 mm² |
Conductor cross section AWG | 24 ... 12 |
Dimensions
Width | 17.5 mm |
Height | 44.8 mm |
Depth | 51.7 mm |
Horizontal pitch | 1 Div. |
Complete module width | 17.7 mm |
Complete module height | 90 mm |
Complete module depth | 65.5 mm |
Material specifications
Color | black (RAL 9005) |
Flammability rating according to UL 94 | V-0 |
Housing Material | PA 6.6 |
Mechanical data
Open side panel | No |
Protective circuit
Direction of action | Line-Line & Line-Earth Ground |
Maximum continuous voltage UC | 250 V AC |
Rated current | 6 A |
Operating effective current IC at UC | ≤ 2 µA |
Residual current IPE | ≤ 2 µA (at UN) |
Nominal discharge current In (8/20) µs | 3 kA |
Pulse discharge current Iimp (10/350) µs | 500 A |
Total discharge current Itotal (8/20) µs | 8 kA |
Total discharge current Itotal (10/350) µs | 1 kA |
Max. discharge current Imax (8/20) µs | 8 kA |
Nominal pulse current Ian (10/1000) µs (line-earth) | 100 A |
Output voltage limitation at 1 kV/µs (line-earth) static | ≤ 1.4 kV |
Residual voltage at In (conductor-conductor) | ≤ 2 kV |
Residual voltage at In (conductor-ground) | ≤ 1 kV |
Residual voltage with Ian (10/1000) µs (line-line) | ≤ 1.4 kV |
Residual voltage with Ian (10/1000) µs (line-earth) | ≤ 700 V |
Max. energy absorption (2 ms) | 150 J |
Voltage protection level Up (line-line) | ≤ 2.5 kV (C2 - 4 kV / 2 kA) |
Voltage protection level Up (line-line) | ≤ 1.8 kV (C3 - 100 A) |
Voltage protection level Up (line-line) | ≤ 2.6 kV (D1 - 500 A) |
Voltage protection level Up (line-earth) | ≤ 1.1 kV (C1 - 500 A) |
Voltage protection level Up (line-earth) | ≤ 1.5 kV (C2 - 4 kV / 2 kA) |
Voltage protection level Up (line-earth) | ≤ 1.6 kV (C3 - 100 A) |
Voltage protection level Up (line-earth) | ≤ 1.8 kV (D1 - 500 A) |
Response time tA | ≤ 100 ns |
Capacity (core-core) | typ. 1.5 pF |
Capacity (core-earth) | typ. 3 pF |
Resistance per path | 0 Ω |
Surge protection fault message | none |
Max. required back-up fuse | 6 A (gL/gG) |
Impulse durability (line-earth) | C2 - 4 kV / 2 kA |
Impulse durability (line-earth) | C3 - 100 A |
Impulse durability (line-earth) | D1 - 500 A |
Ambient conditions
Degree of Protection | IP20 |
Ambient Temperature (Operation) | -40 °C ... 80 °C |
Ambient temperature (storage/transport) | -40 °C ... 80 °C |
Altitude | ≤ 2000 m (amsl) |
Standards and Regulations
Standards/specifications | EN 61643-21 |
Note | 2002 |
Mounting
Mounting Type | on base element |
Why Proax for Phoenix Contact 2921365?
Proax is an authorized distributor of Phoenix Contact 2921365 and one of Phoenix Contact's largest distributors in North America. Our highly skilled in-house technical team is ready to assist with any technical needs.
Have a question in mind? to help you get the right product as quickly as possible for your project. We're always here to help!
Pack Size | 10 |
- PT 2X10/9X4 - Potential collective terminal, nom. voltage: 1000 V, nominal current: 57 A, Line contact, connection method: Push-in connection, Rated cross section: 10 mm2, cross section: 0.5 mm2 - 16 mm2, Load contact, connection method: Push-in connection, Rated cross section: 4 mm2, cross section: 0.5 mm2 - 6 mm2, mounting: NS 35/7,5, color: gray